| 1 | Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/recessed steel/PVC conduit including dismantling as required.Group C |
| 2 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/recessed steel/ PVC conduit as required. |
| 3 | 3 x 1.5 sq. mm |
| 4 | 6 x 1.5 sq. mm |
| 5 | 3 x 4 sq. mm |
| 6 | 6 x 4 sq. mm |
| 7 | Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required |
| 8 | 20 mm |
| 9 | 25 mm |
| 10 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 11 | 5/6 A switch |
| 12 | 15/16 A switch |
| 13 | 6 pin 15/16 A socket outlet |
| 14 | Providing, supplying, and fixing factory-made insulated PUF (Polyurethane Foam) Sandwich Panels consist of pre-painted galvanized iron (PPGI) sheet on both sides with injected high-density rigid polyurethane foam insulation in between, complete with tongue and groove interlocking arrangement, suitable fasteners, sealant, accessories, and supporting arrangements etc. as required at site. Outer/Inner PPGI sheet thickness: 0.45–0.50 mm,PUF insulation density: 40 ± 2 kg/m³, Panel thickness: 40/50/60 mm as per requirement, Fire-retardant grade insulation, Weatherproof and corrosion-resistant finish |
| 15 | 3 Module (100mmX75mm) |
| 16 | 6 Module (200mmX75mm) |
| 17 | 8 Module (125mmX125mm) |
| 18 | 12 Module (200mmX150mm) |
| 19 | Supplying & fixing suitable size GI box with modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, \\"C\\" curve including connections, painting etc. as required. |
| 20 | Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required. |
| 21 | LED Batten light (System lumen efficacy ≥105 <120 lm/Watt) Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85% ,Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, Flicker free, (flicker should be below 5 %), life time (LED,Driver & electrical circuitary), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast / Extruded aluminium Body (Thickness ≥ 1.20 mm)18- 22 Watt |
| 22 | LED Panel light 4x1 ft.Supplying, installation, Testing & Commissioning of 36-40 Watt LED Panel light 4x1 ft., of CRCA LED Panel light 4x1 ft.Supplying, installation, Testing & Commissioning of 36-40 Watt LED Panel light 4x1 ft., of CRCA powder-coated aluminum housing with LED driver as per the requirement Operating voltage AC 140-270 Volt, frequency 50/60 hz, life time of minimum 50000 Burning Hours with, CCT 3000°K / 4000°K / 5700°K /6500°K complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. |
| 23 | Supplying, installation, Testing & Commissioning of Panel light 2x2 ft., of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140- 270 Volt, freq 50/60 hz, Operating temp range -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with , 1.7 centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with, 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6000°K / 6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum ower consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. ..........................Cont..................... |
| 24 | (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C).36 Watt |
| 25 | Supplying and Fixing of Ventilating Exhaust fan upto 250mm sweep in the existing opening, including making the hole to suit the size of the above fan, making good the damage, connection, testing, commissioning etc. as required. |
| 26 | Replacement of defective by S.I.T.C. of electric ceiling fans 1200mm sweep shall be capacitor type, with double ball bearing complete with capacitor, 300mm down rods, canopies, three number blades made of aluminum alloy, suitable for operation on single phase, AC 230 volt, 50Hz supply and but without regulator. |
| 27 | Replacement of defective exhaust fan by Supplying and Installation of exhaust fan 375-380mm sweep 900 RPM in the existing opening, including making the hole to suit the size of the above fan, making good the damage, connection, testing, commissioning i/c dismentling the existing etc. as required. |
| 28 | HI - WALL SPLIT SYSTEMSSupplying, Installation, Testing and Commissioning of Air Cooled Hi Wall split type Air conditioners complete with ndoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R-407 Green Refrigerant, wireless Remote control, suitable for working between 180- 260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 0C. Min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). Must comply: Electrical cable IS 694 or IS 9968 temperature sensing control IS /International Electrotechnical Commission (IEC) 60730, hermetic compressor IS 10617, heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per CPWD specification and IS : 1391 Part II 2023. The system shall be able to operate up to 50 0C (out door ambient temperature).Inverter Type - Cooling only2.0 TR with 5 Star BEE Rating |
| 29 | Supplying and installation of 1/2\\" and 1/4\\" copper pipe with insulation and copper cable insulation & drain pipe i/c brazing, testing, commissioning etc. as reqd. |
| 30 | S & fixing 3 Core 2.5 Sq.mm Round P.V.C insulated Copper Control cable i/c connection testing etc. as required. |
| 31 | Supply and installation of MS (Mild Steel) powder-coated stand suitable for supporting 1.0 / 1.5 / 2.0 Ton split AC outdoor units, wall/floor mounted type, including fasteners, clamps, rubber pads, and necessary accessories for proper fixing etc. complete as required. |
| 32 | Supplying, Installation, Testing and Commissioning of stainless steel storage type water coller 150/150 Ltr. capacity, fully stainless steel suitable for operation on 230 V+10% 50 Hz single phase AC supply i/c making water line and electrical connection etc as required. |
| 33 | Supplying, Installation, Testing and Commissioning of Reverse Osmosis (R.O. System) water Purification unit as per Technical specification attached i/c Providing suitable wall/floor mounting bracket, water connection from the available water inlet point with suitable C.P. angle valve and outlet upto the nearest drain with suitable PVC pipe, complete etc. as required. Capacity:- 50 LPH Capacity Membrane:- 75/100 GPD (4 Nos)Input Power Rating:- 230 Volt AC, 50 Hz % of Rejection in TDS - 90% (Approx.)Indicator:- TD level of output water Tank full indication Audio Beep and No waterAuto Flush Timer Dry Run ProtectionU.V. Sterilization |
| 34 | Less credit for following dismantle materials received from the work. |
| 35 | Assorted size Copper Wire |
| 36 | Assorted size Air Conditioners |
| 37 | Assorted MS Conduit, MD Box |
| 38 | Assorted Switch Socket |
| 39 | Assorted LED fittings |
| 40 | Assorted Ventilation Fan/Wall Fan |
| 41 | Assorted Exhaust Fan/Ceiling Fan |
| 42 | Assorted Water Cooler & RO Please Enable Macros to View BoQ information |