| 1 | Carriage of all the concerning material from store centre to JE's dump store& from dump store to the site work including loading, unloading and proper stacking at the site etc. |
| 2 | 33 KV VCB 800 Amp 750 MVA |
| 3 | 11 KV VCB I/C CTR 600/300/5 amp, 350 MVA |
| 4 | 11 KV VCB O/G CTR 200/100/5 amp, 350 MVA |
| 5 | Repairing of existing 33 KV VCB Plinth for fixing of New VCB stand (all material will be provided by the contractor except 33 KV VCB & its existing stand) and Replacment of Damaged 11 KV VCB of Various SS in Jankipuram |
| 6 | Installation of new 33 KV VCB in place of damaged 33 KV VCB at 33/11 KV S/S Bauramaun (1 No), Kumharawan (2 No), Itaunja (1 No) & Goyal Churaha (1 No) complete work including its commissioning and connecting to the earthing |
| 7 | Providing and Laying of following size copper ,control cable through underground /cable trench/trenching SGR interlinking through proper connections to transformer control panel/protection board /Battery and Batter Charger /Relays 33/11 KV Transformer junction box/ 33KV VCB, CT etc. as per conditions. |
| 8 | 2x2.5 mm2 |
| 9 | 4x2.5 mm2 |
| 10 | 6x2.5 mm2 |
| 11 | Dismantling Charges of 33 KV VCB accessory etc. and carriage of receive back material from site to store ESC |
| 12 | 33 KV VCB Damaged Scrap |
| 13 | Shifting carefully & safely 11KV I/C & O/G switchgear from outside of the switchgear room in proper position and alignment and checking-complete work with Mounting of P.T on incoming Switch gear. |
| 14 | Fixing and making bus bar connections in between all switchgears after cleaning and taping with H.T. Tape, empire tape and PVC tape properly. Providing and fixing of 6 mm thick Bakelite separators and plugging of all opening & holes with plastic compound-complete work including cost of all material strictly to the satisfaction of site in- charge.(All material shall be agganged by the contractor except supplied item) |
| 15 | De-hoisting and re-hoisting of 11 KV I/C and O/G Cables with connecting and packing Properly |
| 16 | Earthing by way of boring and lowering of \\"B\\" Class GI pipe 50 mm dia from ground upto the water level(minimum 30 mtr. Deep )as per standard practice (All material shall be provided by the contractor except the supplied items )as per resspo norms. |
| 17 | Earthing of indoor equipment by means of M.S strip 50x6mm & connecting to Pipe boaring type earthing as per RESSPO norms. Joints will be welded with high quality arc welding. (all material shall be supplied by the contractor) |
| 18 | Dismantling Charges of 11KV Panel with accessory etc and carriage of receive back material from site to store ESC |
| 19 | 11 KV I/C VCB Scrap |
| 20 | 11 KV O/G VCB Scrap |
| 21 | Carriage of all the concerning material from store centre to JE's dump store& from dump store to the site work including loading, unloading and proper stacking at the site etc. |
| 22 | Panther Conductor |
| 23 | 33 KV LINE ISOLATOR 400/800 A |
| 24 | 33 KV BUS ISOLATOR 400/800 A |
| 25 | 33 KV PT,33KV/110V-1P (outdoor) |
| 26 | Top Channel 125x65 sq mm |
| 27 | M.S.Angle 75x75x6, 2.6 Mtr, 2 Nos Total [email protected] Kg./M with wastage |
| 28 | Battery Charger 24 Volt |
| 29 | Battery Set 24 Volt |
| 30 | FABRICATION,ERECTION, GROUTING PLINTHING OF S/S STRUCTURE. |
| 31 | (A) ISOLATOR STRUCTURE :- Erection,Plinthing & grouting (1.9 Mtr Below & 2.6 mtr above ground level because of earth filling) of Isolator structure (All material shall be provided by the contractor except the supplied item)as per RESSPO Norms/Schedule No 41. |
| 32 | (B) LIGHTNING ARRESTOR ,C.T. & PT STRUCTURE:- Erection Plinthing & grouting (1.9 Mtr Below & 2.6 mtr above ground level because of earth filling)of L.A. & C.T. structure (All material shall be provided by the contractor except the supplied item)as per RESSPO Norms/Schedule No 42. |
| 33 | INSTALLATION OF ISOLATORS :-Assembling and installation of line /bus isolator on the isolator structure, In case of line isolator proper operation of earth links shall also be insured. The work includes fabrication for proper flexing if required.(All material shall be provided by the contractor except the supplied item)as per RESSPO Norms |
| 34 | INSTALLATION OF PT:- Installation of PTs on the PT structure, along with Junction box .(All material shall be provided by the contractor except the supplied item) as per RESSPO Norms |
| 35 | Jumpering of all equipments in switch yard with ACSR Conductor P.G. clamps & proper size aluminium lugs.(All material shall be provided by the contractor except the supplied item)as per RESSPO Norms |
| 36 | Providing & fixing of connector for LA,CT,PT,Isolator etc.(All material shall be provided by the contractor except the supplied item)as per RESSPO Norms |
| 37 | Earthing by way of boring and lowering of \\"B\\" class GI pipe 50mm dia from ground upto the water level (minimum 30 meter deep) as per standard practice (All material shall be provided by the contractor except the supplied item)as per RESSPO Norms/Schedule No 53. |
| 38 | Providing and Laying of following size Armoured copper control cable through underground/cable trench/trenching SGR interlinking through proper connections to transformer control panel/protection board /Battery and Battery Charger/Relays 33/11 KV Transformer junction box/ 33KV VCB ,CTs etc as per site conditions.(All material shall be provided by the contractor except the supplied item)as per RESSPO Norms |
| 39 | a) 2x2.5mm2 |
| 40 | b) 4x2.5mm2 |
| 41 | Providing & fixing of control cable tray.(All material shall be provided by the contractor except the supplied item)as per RESSPO Norms |
| 42 | Painting of all structures & equipments.(All material shall be provided by the contractor except the supplied item)as per RESSPO Norms |
| 43 | Installation of 24 Volt, 15 AH sine wave Battery and battery Charger and its cabinate complete and including its commissioning. (All material shall be provided by the contractor except the supplied item)as per RESSPO Norms |
| 44 | All earthing strip shall be painted by green colour (All Material Shall be arranged by the contractor) |
| 45 | Dismantling Charges of 33 KV VCB accessory etc. and carriage of receive back material from site to store ESC |
| 46 | Old & Used/Damaged Line Isolator |
| 47 | Old & Used/Damaged Bus Isolator |
| 48 | Old & Used/Damaged 33 KV PT GST will be paid extra as applicable. Please Enable Macros to View BoQ information |