| 1 | S/Burying of 75mm dia 3 mtr long electrode casted with maintainence free conductive concerete non corrosive mixture in the ratio of 3:1:1 with hole will be vertically installed for earthing with Gl strip connected with nut bolts the earth electrode will be installed into the 100mm pitup to 3000 mm depth normal soil will be used as backfill material (PWD Electrical 2018, 729 (C) |
| 2 | Supply and fixing of plain or pin type copper tin plated 16mm cable socket (lug) to the cable leads, insulating with tape and making connection etc. (PWD Electrical 2018, 504 (D) |
| 3 | S&F of 6 Amp. To 32 Amp. DP MCB (10KA) C. (PWD Electrical 2018, 1009 Cat-A) |
| 4 | Supply and fixing following capacity of automatic street light cubicle control panel painted with anti corrosive alkali and acid proof paint consisting of time switch TSO 100 series with contactors, HRC fuses, Solating switch metering instrument & instrument box with CTs etc. in case of TPN complete in all respect. 40 AmpTPN. (PWD Electrical 2018, 807 (F) (ii) |
| 5 | Supply and fixing of brass Nickle plated compression gland for 16 sq. mm. PVC insultated & armoured served sheathed, underground cable including rubber ring. (PWD Electrical 2018, 503 (1) |
| 6 | Supply and laying of 16 Sq. mm 4 core aluminium conductor PVC insulated armoured served sheathed Cables 1100 Volts grade at a depth of 750mm below ground level over a cushion of 75mm. Thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size of as directed by the engineer-incharge, complete in all respect. the armouring of the cable shall be properly connected with the earth conductor by clamps etc. (PWD Electrical 2024, 20.1.9) |
| 7 | Supply and fixing of 07 mtr. GI Octagonal pole of approved make (Top dia 70mm, Bottom dia 130mm and base plate 12mm thick) having 3mm thickness with single arm bracket (1 mtr length) on RCC foundation including the cost of foundation, foundation bolts, excavation & back filling and required T&P complete in all respect. (PWD Electrical 2024, 21.20) |
| 8 | Supply and fixing of LED Street light fitting having die cast aluminium body and diffuser with driver set suitable for 110 to 130 Watt. Confirming to IP 66 and above (CAT-AAA). (PWD Electrical 2024, 23.17) |
| 9 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 2.5sq. mm + 1 X 2.5 sq. mm earth wire. DSR (E&M) 2025-1.14.2. |
| 10 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required. 63 mm dia (OD-63 mm & ID-51 mm nominal) DSR (E&M) 2025-15.15.1 |
| 11 | Numbering of pole as per direction of engineer in charge (previous sanction rate) MR |
| 12 | Supply and fixing of 3M Radium strip red & yellow on pole complete as per direction of engineer in charge (previous sanction rate) MR Please Enable Macros to View BoQ information |