| 1 | Safe loading & carriage including & proper stracking of following store material from ESC Lucknow /JE store to site of work . |
| 2 | 33 KV 3x300 sq mm XLPE Cable |
| 3 | 33 KV 3x300 sq mm XLPE St/Th J/Kit |
| 4 | 33 KV 3x300 sq mm XLPE O/D J/Kit |
| 5 | Panther Conductor |
| 6 | 33 KV VCB 800 Amp 750 MVA |
| 7 | Single Feeder Control Panel |
| 8 | 33 KV LINE ISOLATOR 400/800 A |
| 9 | 33 KV Lightening Arrestor |
| 10 | 33 KV CT 400/200/1 amp |
| 11 | ST Pole 11 Mtr Long (Galvanised Bottom) |
| 12 | 33 KV Composit Pin Insulator |
| 13 | MS earthing rod 20x2500 mm |
| 14 | MS angle 65x65x6MM 5.8 kg / Mtr. |
| 15 | M.S. Channel 100x50 sq mm 10 kg / Mtr. |
| 16 | Top Channel 125x65 sq mm |
| 17 | LT PVC Cable 1x400 sq mm |
| 18 | M.S.Angle 75x75x6, 2.6 Mtr, 2 Nos Total [email protected] Kg./M with wastage |
| 19 | Laying of 33 kV 3x300 sq. mm XLPE cable S/C including digging of trench 1050 mm deep, 450 mm wide along with required material Sand (0.115 Cub/Mtr), Ist class bricks (17.52 Nos/Mtr), stone pad (1.67 Nos size 600x750x50 mm). The inter axial spacing between two cable should be in between 0.32 M to 0.40 M. (As per JE instruction) and back filling the trench by soil (All the material required for laying will be supplied by the contractor except 33 kV XLPE cable) |
| 20 | 33 kv3x300 Sq. Mm XLPE cable laying in MS/GI pipe 150mm dia single circuit (All the material shall be provided by the contractor except cable) as per resspo norms. |
| 21 | Cable laying by drill method HDD single circuit with HDPE/GI/MS Pipe. 150mm dia (All the material shall be provided by the contractor except 33kvcables) |
| 22 | Hoisting of 33 kv 3x300 sq. mm XLPE Cable on D/P with GI/MS Pipe dia 6\\" its jumpring complete with clamps , nuts and bolts .(All the material shall be provided by the contractor except33kv cables & O/D J/K. )as per RESSPO NORMS |
| 23 | Hoisting of 33 kv 3x300 sq. mm XLPE Cable on cable stand its jumpring complete with clamps , nuts and bolts .(All the material shall be provided by the contractor except 33kv cables & O/D J/K. )as per RESSPO NORMS |
| 24 | Digging of pit of size 3x2x1 mtr. For making straight through joint 33KV work included filling of soil levelling and ramming of the same(ST/Th Providing by department ) |
| 25 | High pressure testing of 33kv 3x300 sq.mm.XLPE cable .Testing equipment will be arranged by the contractor |
| 26 | Providing ,fixing &grouting of stone cable route marker on cable route .displaying feeder name, voltage & depth.(All the material shall be provided by the contractor) as per norms. |
| 27 | Earthing by way of boring and lowering of \\"B\\" Class GI pipe 50 mm dia from ground upto the water level(minimum 30 mtr. Deep )as per standard practice (All material shall be provided by the contractor except the supplied items )as per resspo norms. |
| 28 | FABRICATION ,ERECTION & GROUTING OF ISOLATOR STRUCTURE:- Fabrication of isolator structures 3.5 Mtr. In height as per drawing No. RES 39.Digging of two Nos.pits of size 1.075x0.9x0.3 Mtr. Providing stone pad at the bottom of the pit and grouting pad at the bottom of the pit and grouting of two legs of the isolator structure in CC (cement coarse sand and stone grit of 20m.m gauge)of the ratio 1:4:8 in block of 1.075 Mtrx0.3 mm including supply of all T&P complete in all respect. Both plinths of the isolator structure shall be properly finished with smoothening of edges. |
| 29 | Assembling and installation of line / bus isolator on the isolator structure , In case of line isolator proper operator of earth links shall also be insured. The work includes fabrication for proper flexing if required. |
| 30 | LIGHTENING ARRESTOR /C.T.STRUCTURE:- Fabrication of lightening arrestor/CT structure/.as per drawing No. Res-39 Digging of two Nos.pits of size 1.075x0.3x0.3Mtr providing stone pad at the bottom of the pit and grouting of two legs of the above structures in CC (Cement, coarse sand and stone grit of 20mm gauge ) of ratio 1:4:8 in block of 1.075Mtr X0.3Mtr including supply of all civil material complete in all respect. Both plinths of the structures shall be properly finished with champering of edges etc. |
| 31 | Installation of PT/CTs on the PT/CT structure along with PT/C.T. junction box .(junction box provided by contractor). |
| 32 | Assembling and installation/ Mounting of lightning arrestors on the L.A. Structure as per Resspo norms. |
| 33 | Construction of plinth of size 2.0 mtr x 1.5 mtr x 0.9 mtr suitable for erection of upper structure for 33KV VCB including grouting of anchor bolts in proper alignment and level. Scope of work includes excavation of foundation base concreting in CC 1:6:12 (cement, fine sand & brick ballast ),1 st class brick work in cement mortar of ratio 1:4 CC in ratio 1:4:8 and RCC work in ratio 1:2:4 (cement coarse sand and stone grit of 20mm gauge ) as per RESSPO norms. |
| 34 | Installation of 33KV VCB- complete work including commissioning |
| 35 | Shifting carefully & installation of 33KV single feeder / transformer control panel in control room including its grouting & painting of Feeder/TF Name |
| 36 | Jumpering of all equipments in switch yard with Panther conductor P.G.clams & proper size aluminium lugs including striging Busbar. |
| 37 | Fabrication & erection of 33 KV cable exposure type double pole with the provision of separate bus bar for each cable with fixing of necessary clamps and other accessories like danger board, number plate, barbed wire, 9 no. pin insulators with pins,2 no. channels 100x50 mm (1600mm each),1 no.MS channel 100x50 mm(3200mm in length) and 2 no.MS angle 65x65x6 mm (each 3200mm in length ) for supporting the hoisting of cable etc. Its jumpering by single core PVC aluminium cable with proper size of lug as per RESSPO norms.(All material to be arranged by contractor except PCC Pole, MS Channel, MS Angle, 33 KV Pin Insulator, 33 KV Pin with nut &PVC cable). |
| 38 | Fabrication & erection of cable stand with grouting & plinthing as per resspo norms .(steel material provided by department) |
| 39 | Grouting of Pole in depth of 1/6th the length of pole in ratio 1:4:8 in cement sand and brick ballast and construction of pole plinth 300mm x 45mm above ground level in 1:2:4 in cement, coarse sand and stone grit as per RESSPO norms. |
| 40 | Painting of STP with one coat of red oxide & two coats of best quality top 2 mtr PO Red paint and remaining al. Paint (ISI mark) as per RESPO norms. |
| 41 | Painting of 33 kv feeder Name on the End type Double Pole/Cable Exposure/ Cable stand as per instruction of site engineer |
| 42 | Painting of all structures & equipment. (All materials shall be provided by the contractor ).as per RESSPO Norms. |
| 43 | All earthing strip shall be painted by green colour (All Material Shall be arranged by the contractor) GST will be paid extra as applicable. Please Enable Macros to View BoQ information |