| 1 | Project No. 959 |
| 2 | OD533959/2025-2026:Supply, Installation , Testing and commissioning of 20KW / 25 KVA Silent, Diesel Generator set on the platform 2.7m high from the ground level using crane after removing the temporary roof at the top, with integral acoustic enclosure as per CPCB norms with required control devices , protection schemes, as per technical details given below1. Engine, a) Make of Engine - Cummins /Kirloskar/Caterpillar Engine model X2.6 GI radiator cooled, developing 41.2BHP at 1500 RPM, complete with standard accessories and coupled to b) Alternator Satmford/BHEL/Leroy Saumer rated at 20KW / 25KVA at 415V mounted on channel Iron base frame Complete with fuel tank of 85 litres capacity with 12V battery set, standard and manual control system. c) Type of Engine - Diesel Engine, d) No. of Cylinders - As per manufactures standards. e) Method of Cooling - Water cooled with radiator. f) Aspiration Turbo charged after cooled. 2.Standard accessories with Diesel Engine a) Fly wheel to suit flexible coupling b) Close Coupling c) Air cleaner d) Radiator with fan provided with fan guard. i) Exhaust silencer j) Exhaust Muffler k) Battery charger/Generator 3. Engine Instrument Panel with the following items a) Starting switch with key or button b) Lubricating oil pressure gauge. c) Water temperature gauge. d) RPM Indicator with hour meter e) Battery charging Ammeter 4. Safety Controls for Engine a) Trip for low lubricating oil pressure b) Trip for high water temperature. Voltage regulation band - +/-5% of rated voltage 7. Fuel Tank Suitable size built in type integrated with the acoustic enclosure Suitable size built in type integrated battery with leads and terminals of appropriate AH capacity as per Manufactures requirement. Automatic Battery charger Standard Control Panel 63A, MCCB with all standard accessories such as Ammeter, Volt Meter, Frequency Meter, etc. Necessary measuring CT's of appropriate ratio and burden for the required meters Push button switch for ON/OFF - 1 set Solid state phase indication lamp for supply ON/OFF with HRC protection. Metallic DNB - 1No 10,Supply and providing inbult Battery charger suitable for 25KVA DG set ,11 Tools kit .The DG should have warranty of 3 years from the date of installation. |
| 3 | OD533960/2025-2026:Charges for arranging load test of 25 KVA DG set at factory in presents of department officials before dispatching including supply of fuels and all incidental charges. |
| 4 | OD533967/2025-2026:Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :50 mm dia |
| 5 | OD534221/2025-2026:Dismantling existing damaged 15KVA Diesel Generator from a platform of 2.7m high after removing the temporary roof provided to the platform and fixing it propery after the removal and installation of new generator set using crane without any further damages to the Generator and the surroundings |
| 6 | OD534222/2025-2026:Supply of Diesel to the Generator set |
| 7 | 90.14.5:Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board |
| 8 | 90.12.1.42:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in ground including excavation of trench of size 35 x 75 cm, refilling the trench etc. as required but excluding sand cushioning and protective covering (in ordinary soil).4 core 25 sq mm |
| 9 | 90.12.1.40:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in ground including excavation of trench of size 35 x 75 cm, refilling the trench etc. as required but excluding sand cushioning and protective covering (in ordinary soil).4 core 10 sq mm |
| 10 | 90.12.1.2:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in ground including excavation of trench of size 35 x 75 cm, refilling the trench etc. as required but excluding sand cushioning and protective covering (in ordinary soil).2 core 6 sq mm |
| 11 | 90.12.7.2:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.2 core 6 sq mm with factory made clamp |
| 12 | 90.12.7.3:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.2 core 10 sq mm with factory made clamp |
| 13 | 90.12.7.42:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 25 sq mm with factory made clamp |
| 14 | 90.12.7.40:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 10 sq mm with factory made clamp |
| 15 | 9.1.34:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 25 sq. mm (28mm) |
| 16 | 9.1.32:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm) |
| 17 | 9.1.1:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.2 X 6 sq. mm (19mm) |
| 18 | OD533972/2025-2026:Supply and providing earth clamp for cable gland earthing up to 25 to 95 sq mm AYFY cables with 25x2 mm copper strip and 25X3 mm brass bolt and nut etc as required. |
| 19 | OD533982/2025-2026:Supply and providing earth clamp for cable gland earthing from 4sqmm to 16sqmm AYFY cables with 20x1 mm copper strip and 12X3 mm brass bolt and nut etc as required. |
| 20 | OD533986/2025-2026:Supply and installation of 63 A 4 pole on load change over switch gear unit in sheet steel enclosure complete with handle assembly, door interlock and pad locking arrangements etc. on existing angle iron frame work or directly to wall using necessary bolts & nuts, fixing the unit to wall, making good the damages, colour washing etc. including giving necessary connections as required. |
| 21 | 90.11.1.14:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43) |
| 22 | 2.3.3:Supplying and fixing following way, single pole and neutral, sheet steel, MCBdistribution board, 240 volts, on surface/ recess, complete with tinned copperbus bar, neutral bus bar, earth bar, din bar, interconnections, powder paintedincluding earthing etc. as required. (But without MCB/RCCB/Isolator)12 way, Double door |
| 23 | 2.10.1:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required.Single pole |
| 24 | 2.10.4:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required.Triple pole |
| 25 | 2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 26 | 2.13.2:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps |
| 27 | 2.14.2:Supplying and fixing following rating, double pole, (single phase and neutral),240 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 28 | 2.15.2:Supplying and fixing following rating, four pole, (three phase and neutral), 415volts, residual current circuit breaker (RCCB), having a sensitivity current 30milli Amperes in the existing MCB DB complete with connections, testing andcommissioning etc. as required.40 amps |
| 29 | OD534441/2025-2026:Supply and installation of switch gear units in sheet steel enclosure complete with handle assembly, door interlock and pad locking arrangement of the following ratings on existing angle iron frame work or directly to wall using necessary bolts & nuts, fixing the unit to wall, making good the damages, colour washing etc. including giving necessary connections as required. (including cost of HRC fuse links in case of SDF/ SDFCO), 63 A, 415 V, 50 Hz, AC 23 A duty, TPN switch disconnector unit with fuses |
| 30 | OD534401/2025-2026:Supply and installation of switch gear units in sheet steel enclosure complete with handle assembly, door interlock and pad locking arrangement of the following ratings on existing angle iron frame work or directly to wall using necessary bolts & nuts, fixing the unit to wall, making good the damages, colour washing etc. including giving necessary connections as required. including cost of HRC fuse links in case of SDF/ SDFCO),32 A, 415 V, 50 Hz, AC23 A duty, TPN switch disconnector unit with fuses |
| 31 | OD534402/2025-2026:Supply and providing dust and vermin proof, wall mounting, Hot press moulded SMC Meter Box of following sizes suitable for fixing KSEB meter, fuse units, CT etc, hinged door construction for the front side with compartments if necessary, providing vision panel for the meter compartment, knock out for cable entry and exit, with 700x480x200 mm or nearest size. (Sintex GS-MB 7450 or equivalent make). |
| 32 | OD534403/2025-2026:Supply and fixing 63A backelite HRC Fuse unit with HRC fuse link in the existing meter board and giving connections as required. |
| 33 | OD534404/2025-2026:Supply and fixing 63A, 415 V, 2 way neutral link mounted on DMC/ SMC base in the existing meter board and giving connections as required. |
| 34 | 90.2.1.1:Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Single Control light point with 6A, plate ceiling rose - Short point |
| 35 | 90.2.1.3:Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Single control light point without ceiling rose - Short point |
| 36 | 90.2.1.4:Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Single control ceiling fan point with 6 A, 3 plate ceiling rose & with socket size stepped electronic regulator. - Short point |
| 37 | 90.2.1.6:Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Combined plug point with 6 A, 5 pin plug socket controlled by 6 A, switch in the same switch board as that of light points |
| 38 | 90.2.1.7:Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Independent plug - Short point |
| 39 | 90.3.19.3:Supply conveyance, installation, testing and commissioning the light fittings of following types made from CRCA sheet 0.5mm thickness with all accessories and lamps directly on wall and giving connections with 16/0.20 mm 3 core PVC insulated and sheathed round copper conductor flex wire or extending the original wiring and giving connections as required1200 mm 1X20W LED Lamp with box type fixture |
| 40 | 1.34:Supplying and fixing brass batten/ angle holder including connection etc. as required. |
| 41 | OD534533/2025-2026:Supply and providing Normal size 9 W LED lamp in the existing light fittings/holder as required. |
| 42 | 90.4.5.4:Supply, Installation, testing and commissioning of ceiling fan of following sizes including wiring the down rods of standard length (up to 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required.1200mm sweep - ceiling fan complete with service value minimum 4.0(cub meter/minute/Watt), Air delivery minimum 210(cubic meter/minute), Copper winding suitable for 230V/240V single phase AC supply |
| 43 | OD534539/2025-2026:Supply and providing 18 W, LED out door bulk head fittings on wall/ceiling and giving connections with required length of 16/0.20 mm PVC insulated and sheathed 3 core round copper conductor flex wire etc as required. (LUKER eco LBKOVSL18 or equivalent make). |
| 44 | 90.15.4.2:Supply Conveyance, installation, testing and commissioning of 36/40W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer) |
| 45 | 90.6.4.54:Supply and drawing 650/1100 V grade FRLS PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.10.00 sq.mm 4 Run |
| 46 | 1.17.11:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.2 x 2.5 sq. mm |
| 47 | 1.17.20:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.2 x 4 sq. mm |
| 48 | 1.17.29:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.2 x 6 sq. mm |
| 49 | 1.24.3:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch |
| 50 | 1.24.5:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet |
| 51 | 1.27.2:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm) |
| 52 | 90.10.3.33:Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )25A 3pin Shuttered socket |
| 53 | 90.12.9.2:Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench50/38 mm or nearest size |
| 54 | 90.16.1.1:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.00 mm copper conductor ( 14 SWG) |
| 55 | 90.16.1.2:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.65 mm copper conductor (12 SWG) |
| 56 | 90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG) |
| 57 | 90.16.1.5:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required4.75 mm copper conductor (6 SWG) |
| 58 | 90.16.5.1:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.00 mm (14 SWG) |
| 59 | 90.16.5.2:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.65 mm (12 SWG) |
| 60 | 90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG) |
| 61 | 90.16.5.5:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.4.75 mm (6 SWG) |
| 62 | 5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 63 | 5.15:Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 64 | OD533978/2025-2026:Supply and providing Test joint for earthing made up of 2 nos, 25x5 mm GI strip, 25 cm long placed on either sides of earth leads and watering pipe, bending, drilling and tightening with 4 sets of brass/SS nut, bolt, washer etc as required. |
| 65 | OD533980/2025-2026:Supply and providing 25X6mm brass nut bolt for plate earthing test joint |
| 66 | OD533985/2025-2026:Supply and providing 25X3mm brass nut bolt for plate earthing test joint |
| 67 | 90.16.2.5:Supply and laying of the following sizes of B class GI pipe laid 0.6 m below ground level including excavating trench of suitable size and refilling etc, as required.50 mm dia. G.I. pipe (medium class) |
| 68 | 90.16.2.2:Supply and laying of the following sizes of B class GI pipe laid 0.6 m below ground level including excavating trench of suitable size and refilling etc, as required.20 mm dia. G.I pipe ( medium class) |
| 69 | 90.3.17.2:Supply, conveyance and erection of the following sizes of 'B' class GI pipe in single section for post top lantern of all types on concrete base (excluding charges for concrete base and excavation) and painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer etc. as required.40 mm dia GI pipe |
| 70 | 90.16.3.9:Supply and clamping the following size of strips on surface of wall/ parapet/ existing cable tray using clamps fabricated from 20 X 3 mm GI flat duly painted or heavy duty GI spacer saddles spacing of clamps not exceeding 1 m, making good the damages, colour washing etc. as required ( for horizontal run)25 x 3 mm copper strip |
| 71 | 90.14.1.1:Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623.Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.Supply and fabrication of MV panel board using 2.00mm CRCA sheet, powder coated (excluding base frame) |
| 72 | 90.14.2.2:Supply and providing 3mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc. |
| 73 | 90.14.3.3:Supply and providing heavy duty 'A' section neoprene gasket in the panel boardSupply and providing 'U' section PVC beeding in the panel board |
| 74 | 90.14.6:Supply and providing copper bus bars including finger type SMC bus bar supports in the bus chamber, suitable size nut & bolt, providng heat shrink sleeves etc. as required. |
| 75 | 90.14.7:Supply and providing copper earth bus in the panel board |
| 76 | 90.6.4.1:Supply and drawing 650/1100 V grade FRLS PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.1.00 sq.mm 1 Run |
| 77 | OD535380/2025-2026:Supply and providing 0.5A -2A SP MCB on the existing DIN bar and giving connetcion etc as required. |
| 78 | OD533970/2025-2026:Supply and providing blue colour LED on the existing frame and giving connetcion etc as required. |
| 79 | OD533979/2025-2026:Supply and providing orange/red/green LED on the existing frame and giving connetcion etc as required. |
| 80 | 90.6.10.1:Supply and fixing of following sizes of light gauge PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required20 mm |
| 81 | 90.6.10.2:Supply and fixing of following sizes of light gauge PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required25 mm |
| 82 | 90.6.10.3:Supply and fixing of following sizes of light gauge PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required32 mm |
| 83 | 1.21.5:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.50 mm |
| 84 | OD533966/2025-2026:Charges towards the preparation of necessary plan, scheme and other related papers for submission to KSELB & KSEB - First A3 Shee |
| 85 | OD533976/2025-2026:Charges towards the preparation of necessary plan, scheme and other related papers for submission to KSELB & KSEB - Each Additional A3 Shee |
| 86 | OD533957/2025-2026:Supply and providing First Aid Chart duly framed and placed in a conspicuous location for clear vision |
| 87 | OD533963/2025-2026:Supply and providing 4 Kg. Dry Chemical Powder type Fire Extinguisher with hose and clamps including fixing it to wall as required |
| 88 | OD533981/2025-2026:Supply and providing 2mm thick Elastomeric fire retardent insulating mat as per IS 15652/2006 towithstand 3.3 KV dielectric strength. |
| 89 | OD533969/2025-2026:Supply and providing 9 Litre capacity GI Fire Bucket painted in post office red with primer coat of red oxide and written with white paint 'FIRE' mounted on MS angle frame work/ wall bracket filled with fine sand, painting the bracket/ floor stand including making good the damages, colour washing etc. as required |
| 90 | OD533962/2025-2026:Painting letters or figures of the following sizes with enamel paint as identification mark to SB, DB, panel board etc as required.- 2.50 cm, 4 cm or 5 cm height |
| 91 | OD533961/2025-2026:Fee to be paid to KSELB towards scrutiny & inspection , meter testing etc (actual amount will bereimbursed on production of original documents |
| 92 | OD533975/2025-2026:Supply and providing M8 eye bolt hook in wall / parapet for binding support for KSEB service main. |
| 93 | OD533965/2025-2026:Truss work for refixing MS pipe, Installation of necessary angles, supply and installation of necessary GI square pipes of size 2"x 2" , 2" x1" used for truss & purling wherever necessary in an A type structure, covering sides and covering the roof using 3.5mm gauge GI sheets as requires using the materials as per PWD standard |
| 94 | OD533973/2025-2026:Charges for preparation of application and test report for KSEB connection Please Enable Macros to View BoQ information |