| 1 | Supply of 630 KVA 3.3 KV/415 V distribution Transformer,3 Phase, 50 Hz Copper Winding,CRGO Core Material, Vector Group Dyn-11,ONAN type of cooling.( Detail as per annexure A given in GTC) |
| 2 | Supply of 10 Mtr height swaged type tubular pole as per IS:2713 of 1980( Detail as per annexure B given in GTC) |
| 3 | Supply and Installation of JB for connection, Outdoor type includes Enclosure with Connector and 10/16Amp MCB and related accessories |
| 4 | Timer based control panel comprising 3 phase 100 A Contactor and all other suitable accessories as per the instruction of engineer in charge |
| 5 | Providing of 50 sq.mm. 3.5 core 1.1 kv grade alumunium armoured cable (XLPE ALU.ARM.CABLE 3.5CX50 A2XFY) |
| 6 | Providing of 16 sq.mm. four core 1.1 kv grade alumunium armoured cable (XLPE ALU.ARM.CABLE 4CX16 A2XFY) |
| 7 | Laying of one number PVC insulated and PVC shethed / XLPE power cable of 1.1 KV grade above 35 sq.mm . up to 95 sq mm direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. |
| 8 | Laying of one number PVC insulated and PVC shethed / XLPE power cable of 1.1 KV grade up to 35 sq.mm . direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. |
| 9 | Erection of metallic pole of above 8 mtrs & up to 10Mtr. length in cement concrete 1:3:6 (1 cement :3 course sand:6 grade stone aggregrate 40mm normal size) foundation including excavation and refilling etc as reqd. |
| 10 | Supplying and erection of stay set complete (galvanised) with 19/20 mm dia X 1.8 metres long stay rod, anchor plate of size 45 cm X 45 cm X 7.5 mm, thimble, stay clamps, turn buckle ( 20 mm X 60 cm), 7/ 3.15 mm dia G.I. stay wire and strain insulator etc in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size ) foundation including excavation and refilling etc. as required. |
| 11 | Providing of HDPE pipe dia 50 mm for 16 & 50 sq mm cable |
| 12 | Supply & erection of 11 KV, 800 A, 25KA for 3 sec, 3 phase double break, center post rotating, off load, manual Isolator without Earth Switch, the swich shall be completed with 09 nos, 11KV grade ploymer post insulators ( Cantilever strength-6KN) (Mechanical strength-5K), Creepage distance-25mm/KV, vertical operating pipe, phase coupling pipe. |
| 13 | Supplying of two lengths of channel iron 75 mm X 40 mm X 6 mm (7.14 kg per metre) double pole cross arm for three wire 11KV over head line conductors complete with through bolts and nuts for clamping to the poles, 50 mm X 6 mm M.S. flats welded on one side to the channel iron and with bolts and nuts on the other side for tying the cross arms together, including drilling holes for insulator pins/ fittings, bolts, nuts and washers etc (as per drawing) and painting with primer and finish paint as required. |
| 14 | Erection of double pole 3 wire cross arm for 11KV/ 22KV/ 33 KV over head lines as required. |
| 15 | Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required. (200 Amp TP&N) |
| 16 | Supply, installation and commissioning of maintenance free earthing system earth resistance upto 01 ohm with test certificate: Specification: Earthing electrode - 50/3 MTPCB, 3M X 58mm, THK:50, 250 Micron copper coating on GI pipe, Terminal size-40/6, inner strip- 25 x 3, filling material BFC silica base bentonite powder 50kg, Earth pit digging by spiral machine, Pit cover- Poly Plastic (BIG) primary earthing electrode (outer pipe) of 99.9% pure copper coating (250 micron) on GI pipe (diameter 58mm) X 3 mtrs. The hollow space of the electrode is duly filled with a highly conductive and non-corrosive compound (graphite power) which safeguards the secondary electrode getting corrode over a long period of time under the soil. Also the compound ensures the easy distribution of leakage/fault current lands on the electrode, Both the end s of the electrode are permanenetly sealed and the top portion of the earth electrode is compressed to form and extended lead with 2 holes on the terminal for connecting to the load/equipment. ( Detail as per annexure F given in GTC) |
| 17 | Supply & erection of 4.5KV 10KA, SM-Station Medium Duty (Old line discharge class-III) with QRS=1.6C & Wth=7kj/KV as per IEC-60099-4 of 2014 & IS:15086 (Part-4) of 2017 gapless type single Phase Surge Arrestor comprising of Metal Oxide elements housed in FRP Wrap duty moulded with silicone Polymer to be used on a nominal system voltage of 3.3 KV & maximum system voltage of 6.6KV with an MCOV of 3.8Kvrms and with terminal clamps suitable for AAA conductor with creepage distance :31mm/KV, Pressure Relief class-25Ka @0.2sec, cantilever strength 150kgf ( As per CEA guidlines, TTRs validity is 10 Yrs) |
| 18 | Supplying at site angle iron post & strut of required size including bottom to be split and bent at right angle in oposite direction for 10 cm length and drilling holes upto 10mm dia etc complete with angle of 65mm X 65m X 65mm @ 5.4 kg per/m |
| 19 | Providing and making steel pole collar with cement concrete (1 cement: 3 coarse sand :6 stone aggregate 20mm) of specified size and shape including form work, plastering if required, curing etc as required. (volume of pole/ pipe not to be deducted) |
| 20 | Supplying and fixing of 32 mm dia X 2.00 metres long GI. pipe (medium class) bracket for mounting of fluorescent / HPMV / HPSV street light fitting on pole including bending the pipe to the required shape, 2 nos 40 mm X 3 mm flat iron clamps with nuts, bolts and washer, painting the flat iron with primer and finish paint etc. as required. |
| 21 | Supply, installation, testing & commissioning of 20 mtr High Mast Tower comprising of 12 nos LED flood light, foundation board manufcature from special steel with Nuts, washrs, Anchor plate & common template including foundation, earthing the feeder pilar with all accessories etc as required.( Detail as per annexure C given in GTC) |
| 22 | Supply of LED Street light 300 watt, 220-230V( Detail as per annexure E given in GTC) |
| 23 | Design, supply,installation,tetsting and commissioning of motoring type raising / lowerng typr, hot dip galvanised 25 mtr polygonal stadium high masts having thickness 5 mm PCD 630mm with following items:High Mast sections with base plate,Lantern carriage suitable to fix upto 12 Nos. of (LED) luminaries asymmetrically ,3 suspensionHead frame, L-Stopper (3 Nos.), Mounting Plates,Lightening Arrestor andEarthing Spikes (MS GI) Double Drum Winch 1500 Kg. (Gear Ratio- 53:1), 3 HP Motor ,Ø6 mm. SS WireRope (Grade-AISI 316), Manual Operating Handle, Trailing Cable (1 sets 5 coreX 4 sq. mm. EPR PCP Round Copper, GI Junction BoxAVIATION OBSTRUCTION LIGHT: LED type Double Dome , Warranty- 2yrs ( Detail as per annexure D given in GTC) |
| 24 | Supply, installation, testing and commissioning of 1000W LED sports lighting floodlight stadium type fixtures complete with all accessories, outdoor type with following specification1. With highly efficient strong aluminium die cast housing and with heat resistant toughened glass along with proper heat dissipation system in the housing. 2. LED light Fixture should be Adjustable along both Horizontal and vertical axis3. Operating voltage: 150-250V, pf>0.95, frequencly:50Hz+3, Lumen level: 120lumen/watt (min.), pure white light colour, with narrow beam angle: 20-40 deg, should have surge protection-min 4kV and CCT should be 5500-6500K, CRI>70 and LED chip of reputed make, THD<10%, IP66 protection, Warranty-2 yrs |
| 25 | Supply of suitable foundation accessories bolts, made of special steel, along with anchor plate for the above masts.( Detail as per annexure G given in GTC) |
| 26 | SITC of IP-68 waterproof gel connectors having 3/4 pole cable connector, 3 wires x 2.5sqmm (Application: 01 IN and 02 Out for 03 core (2.5sqmm) rubber cable) Such specialized waterproof gel connectors, secure connections form all type of adverse weather threats for outdoor connections and secure it from moisture and carbon accumulation, long -lasting and reliable. |
| 27 | Design, supply, installation, testing and comissioning of cubicle type LT panel complete including all switch gears ( MCCB with adjustable s/c thermal trip and MCB) (mention the rating of income and incoming and outgoing and number of outgoing feeders, with provision of two spare feeder with MCCB) to be kept for protection and contractors suitable for 415volts, 3-phase , 4 wire 50hz AC supply system, fabricated in ip 55 compartmentalized desgin from CECA steel of 3mm thick for frame work and covers, 3mm thick for gland plates, including cleaning and finishing complete with 7 tank process for powder coating in approved shade. TPN aluminium alloy bus bar of high conductivity. DMC/SMC busbar supports with short circuit withstand capacity, bottom base channel of M.S.section of not less than 100mm*50mm*5mm thick , entire panel shall have a common copper earth bar of size 25mm*5mm at th rear with 2nos. earth stud, solid connections from main busbar to switchgear with required size of all busbar and control wiring with PVC insulated copper conductor wire, cable alleys, cable gland plates, in two half including providing all components required as per bidders desgin. the incomer shall be provided with energy meter. Oncluding subpanel/control for each Mast Control with pendant type switch, having 100 AMP TPN MCCB as incomer with 5DA contractor and 02nos, 9A auxillary contractors for Mast. Most operation and outgoing circuits shall be having 10nos, 10DP MCB for outgoing circuit for individual operation of lighting fixtures |
| 28 | Supply and laying of pole/mast wire with 2.5 sq mm 2 C Copper cable ISI mark FR Grade |
| 29 | Supply of 4C*35 sq mm AI armoured cable in underground cable trenching |
| 30 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.Upto 35 sq. mm |
| 31 | supply of 63 mm ID mm Dia HDPE pipe for cable protection |
| 32 | laying of 50mm Dai HDPE pipe for cable protection |
| 33 | supplying and fixing 25mm*5mm G.I. strip at 0.5 meter below ground as strip rath electrode including connection/teminating with G.I. nut bolt ,spring,washer,etc as required ( jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer sprased at 50mm) |
| 34 | Providing & fixing of G I chain link fabric fencing of required wih in mesh size 50X 50 mm including strengthening with 2mm dia wire or nuts, bolts and washers aas required complete as per the direction of Engineer I/C (Made G.I. wire of dia 4mm) |
| 35 | Earth work in excavation by mechanical means( Hydraulic excavator) / manual means in foundation trenches or drams (not exceeding 1.5 m in width or 10 sqm on plan) including of sides and rammng of bottoms, lift upto 1.5 m including getting out the excavated soil and disposal of surplus excavated soil as directed within a lead of 50 m (All kinds of Soil) |
| 36 | Providing & laying in position cement concrete of specified grade excluding the cost of centering and shuttering- All work upto plinth level 1:3:6 (1 cement : 3 coarse sand: 6 graded stone aggregate 20 mm nominal size) |
| 37 | Extra for providing & fixing wind ties of 40 x 6mm flat iron section. |
| 38 | Applying primming coat with ready mixed red oxide zinc chromate primer of approved brand and manufacture on steel galvanished iron/steel works (over angle post and wind ties) |
| 39 | Painting with Alluminium paint of approved brand and manufacture to give and even shed 2 or more coats on new work (over angle post and wind ties) |
| 40 | Supplying and filling in plinth with sand under floors,includng watering,ramming,consolidating and dressing complete. |
| 41 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering -All work up to plinth level 1:2:4 (1 cement ;2 coarse sand {zone-III} derived from natural sources :4 graded stone aggregate 20 mm nominal size derived from natural sources ) |
| 42 | Cement plaster 1:3 ( 1 cement 3 coarse sand )finished with a floting coat of neat cement. 12 mm cement plaster, |
| 43 | Filling available excavated earth (excluding rock ) in trenches, plinth,sides of foundation etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, leadup to 50 m and lift upto 1.5 m |
| 44 | Retaining walls,return walls,walls (any thickness ) including attached pilasters,buttresses,plinth and string courses fillets, kerbs and steps etc. |
| 45 | Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-in-charge. All kinds of soil including Hard Soil. |
| 46 | Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and for all lift, as directed by Engineer-in-charge. |
| 47 | Supplying and filling in plinth with sand under floors, including watering, ramming, consolidating and dressing complete. |
| 48 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level: 1:4:8 (1 Cement : 4 coarse sand (zone-III) : 8 graded stone aggregate 40 mm nominal size) |
| 49 | Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana /Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 1.10 times of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement: concrete of M25 grade with minimum cement content of 330 kg/cum. |
| 50 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding allcomplete upto plinth level : thermo mechanically treated bars of grade 500D ir more |
| 51 | Centering and shuttering including strutting, propping etc. and removal of form for Columns, Pillars, Piers, Abutments, Posts and Struts |
| 52 | Total impact of GST plus Labour Cess [@ 1 % (BOCW Cess to be deducted from the RA bill as per the value of the work progress)] for the purpose of CTC Please Enable Macros to View BoQ information |