| 1 | WIRING |
| 2 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 3 | 4 X 10 sq. mm + 2 X 6 sq. mm earth wire |
| 4 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 5 | 3 x 1.5 sq. mm |
| 6 | 3 x 2.5 sq. mm |
| 7 | 3 x 4 sq. mm |
| 8 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 9 | 20 mm |
| 10 | 25 mm |
| 11 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 12 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. |
| 13 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 14 | MCCB, MCB & DB'S |
| 15 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator). |
| 16 | 8 way (4 + 24), Double door |
| 17 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) |
| 18 | 8 way (4 + 24), Double door |
| 19 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 20 | Single pole |
| 21 | Double pole |
| 22 | Triple pole |
| 23 | Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 24 | Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top along with 20 A \\"C\\" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 25 | CABLE TRAYS |
| 26 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with two numbers GI Suspenders i/c base of suitable size GI angle, GI bolts & nuts, fastner etc as required. |
| 27 | 225 mm width X 50 mm depth X 1.6 mm thickness |
| 28 | MV CABLE LAYING |
| 29 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. |
| 30 | Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 31 | MV CABLE JOINTING & END TERMINATION |
| 32 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 33 | 4 X 25 sq. mm (28mm) |
| 34 | REMOVAL |
| 35 | Charges for removing the existing DB, (All, cable wires & PVC conduits) making good the damages of the wall / floor including painting other accessories without any damage and conveyance of the material to the godown excluding transportation but including loading and un loading of materials etc, as required |
| 36 | Supplying and fixing 40 A to 63 A rating, 415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of four poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.. |
| 37 | Supplying and fixing 40-63A , Triple pole, 430 V, C curve Miniature circuit breaker (MCB) in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 38 | EARTHING |
| 39 | Supply and laying one number of the 8 SWG good quality bare copper wire along the cable with connections etc. as required. |
| 40 | UG CABLE |
| 41 | Supply of 4C X 25 Sq.mm PVC/ XLPE Aluminium Armoured Cable, 650/1100V. Grade confirming to IS:7098 (Pt-1)1988 |
| 42 | Supplying and fixing of DLP Pastic Trunking 105x50mm with cover including all accessories (flexible cover,end cap, junctions, joints, wall crossing, VDI accessories etc. as per site condition) |
| 43 | Supplying and fixing suitable size modular plate and cover in front on existing DLP trunking 105 x 50 mm, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet (3 modular) and 20 A modular switch, connections etc. as required. |
| 44 | Supplying and fixing suitable size modular plate and cover in front on existing DLP trunking 105 x 50 mm, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. |
| 45 | uPVC TRUNKING |
| 46 | Supplying and fixing of uPVC mini/maxi trunking of size 100 mm x 50 mm on the wall with suitable flexible cover,Internal angle ,external angle , elbow, Tee, End cap, necessary as required fitted with steel screws,fastners cup washers etc. |
| 47 | ENCLOSURE |
| 48 | Supplying and fixing four Pole Enclosure complete with connections, testing and commissioning etc. as required. Please Enable Macros to View BoQ information |