| 1 | Supply, installation, testing in replacement of PLC CPU which is considered digital inputs and digital outputs, analog inputs, serial communication RS232/ RS485 x 1, ethernet Port x 1 including re-wiring of the entire control wiring system, control fuses, relays etc existing panel with respect to the required inputs & outputs and bring its original working condition complete all as specified and as directed by Engineer-in-Charge. Make: Mitsubishi |
| 2 | Supply, installation, testing and commissioning in replacement of HMI 7'' graphic touch screen display for Programmable Logic Controller having port type 1 x ethernet, 1 x RS 232, 1 x RS422/ 485, 1 x USB port and compatible for supply voltage 24V DC complete all as specified and as directed by Engineer-in-Charge. Make: Mitsubishi, Renu or equivalent as approved by GE |
| 3 | Supply, installation, testing and commissioning in replacement of Motor Actuated Butterfly valve with the following specifications including all accessories as required complete all as specified and as directed by Engineer-in-Charge. (a) Valve size: 50 mm dia. (b) Designed line pressure: 16 kg/sq cm. (c) Operating Angle: 90 degrees (d) Disc Material: C.I. with nylon coating (e) Limit switches: 02 nos. for open and close (f) Type: In Direct mounting (Extended Type) Make: RITE TORK / HASEL HOFENER / EMTORK/ MARSH |
| 4 | Supply, installation, testing and commissioning in replacement of Motor Actuated Butterfly valve with the following specifications including all accessories as required complete all as specified and as directed by Engineer-in-Charge. (a) Valve size: 80 mm dia. (b) Designed line pressure: 16 kg/sq cm. (c) Operating Angle: 90 degrees (d) Disc Material: C.I. with nylon coating (e) Limit switches: 02 nos. for open and close (f) Type: In Direct mounting (Extended Type) Make: RITE TORK / HASEL HOFENER / EMTORK/ MARSH |
| 5 | Supply, installation, testing and commissioning in replacement of Motor Actuated Butterfly valve with the following specifications including all accessories as required complete all as specified and as directed by Engineer-in-Charge. (a) Valve size: 100 mm dia.(b) Designed line pressure: 10 kg/sq cm.(c) Operating Angle: 90 degrees(d) Disc Material: C.I. with nylon coating(e) Limit switches: 02 nos. for open and close(f) Type: Indirect type with universal joint for installation above ground level with angle iron mounting arrangementMake: RITE TORK / HASEL HOFENER / EMTORK/ MARSH |
| 6 | Supply, installation, testing and commissioning in replacement of Motor Actuated Butterfly valve with the following specifications including all accessories as required complete all as specified and as directed by Engineer-in-Charge.a) Valve size: 150 mm dia.b) Designed line pressure: 10 kg/sq cm.c) Operating Angle: 90 degreesd) Disc Material: C.I. with nylon coatinge) Limit switches: 02 nos. for open and closef) Type : direct type Make: RITE TORK / HASEL HOFENER / EMTORK |
| 7 | Supply, installation, testing and commissioning in replacement of Motor Actuated Butterfly valve with the following specifications including all accessories as required complete all as specified and as directed by Engineer-in-Charge.a) Valve size: 200 mm dia.b) Designed line pressure: 16 kg/sq cm.c) Operating Angle: 90 degreesd) Disc Material: C.I. with nylon coatinge) Limit switches: 02 nos. for open and closef) Type: In Direct mounting (Extended Type)Make: RITE TORK / HASEL HOFENER / EMTORK |
| 8 | Supply, installation, testing and commissioning in replacement of Pressure Switch with following specifications complete all as specified and as directed.Range 0-10 kg/sq. cm.Enclosure: Weather proof IP 65Make: Indfoss/ Danfoss/ Switzer |
| 9 | Supply, installation, testing and commissioning in replacement of solenoid valve SS/ Forged Brass/ Cast Bronze, pressure rating: 6 kg / Sqcm suitable for 25mm GI pipe for priming of pump including suitable bypass with necessary GI fittings complete all as specified and as directed. Make: Avcon/ Rotox/ JOHNSON CONTROL |
| 10 | Supply, installation, testing and commissioning in replacement of solenoid valve of 10mm suitable for GI pipe for priming of pump including bypass arrangement using 10mm gate /ball valve with necessary GI fittings with following specifications complete all as specified and as directed. Size: 10 mmMaterial : SS/ Forged Brass/ Cast BronzeType: Pilot operated, diaphragm type / direct acting type.Pressure rating: 6 kg / sq. cm.Normally closedMake: Avcon/ Rotox/ JOHNSON CONTROL |
| 11 | Supply and fixing in repairs 1 KVA UPS with maximum configurable (watts): 800 watts, output frequency (sync to main) 50 Hz normal input 230V AC, LED status display with indicators complete all as specified and as directed. Make:- APC |
| 12 | Supply and fixing in repairs UPS battery capacity 7AH complete all as specified and as directed. Make: Amaron |
| 13 | Supply and fixing in repairs controller for AMF panel compatible for RS 485/ RS 232/ modem/ modubus communication complete all as specified and as directed. |
| 14 | Supply and fixing in repairs 9DB Antenna GPRS Modem complete all as specified and as directed. |
| 15 | Supply and fix in replacement of GPRS Modem 2G/ 3G/ 4G cellular network connections having features of IP sec/ Open VPN/ GRE/ L2TP/ PPTP/ DMVPN with 1 Ethernet Port, 1 RS232/ RS485 Port complete all as specified and as directed.Make: Robustel |
| 16 | Material and labour for customized communication cable for Mitsubishi PLC extension Module to Robustel modem for RS 485 interface complete all as specified and as directed. |
| 17 | Material and labour for repairs to existing SCADA LT Panel by welding and providing new locking system with proper hinges, door gas kit for PLC Panels complete all as specifed and as directed by Engr-in-Charge. |
| 18 | Material and labour for Re-commisionning of existing PLC based panels, to Configuration of IPsec tunnels/assigning the IPv4 address with compatible subnet mask for 4G dual SIM based modem, ISP router reconfiguration for virtual server and port forwarding complete all as specified and as directed. |
| 19 | Excavation in trenches not exceeding 1.5 mtr depth and n exc 1.5 mtr wide and getting out in hard/dense soil complete all as specified and as directed |
| 20 | Returning, filling in, including spreading, leveling, watering and well ramming in layer not exceeding 25cms thick after laying and testing of cable complete all as specified and as directed |
| 21 | Removing of excavated material to a distance not exceeding 50 metre and depositing where directed at level not exceeding 1.5 metre above the starting point complete all as specified and as directed Please Enable Macros to View BoQ information |
| 22 | Removing of excavated material to a distance not exceeding 50 metre and depositing where directed at level not exceeding 1.5 metre above the starting point complete all as specified and as directed Please Enable Macros to View BoQ information |