Tender For Construction Of Otm Accn (Klp) At Bde Hq In Pallanwala Under Ge (S) Akhnoor
Tender Overview
Project Description
Tender for Construction Of Otm Accn (Klp) At Bde Hq In Pallanwala Under Ge (S) Akhnoor
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 29-Jun-2026 | CorrNo01 | Date | 15-Jul-2026 |
| 2 | 10-Jul-2026 | CorrNo02 | Date | 25-Jul-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | Sch 'A' Part-I (Building Work):-This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as \\"Rs. 0.00\\" under col.5 signifies this fact only. |
| 2 | Construction of building block for Office and Adminstrative Accn complete all as shown on drawings and as specified. |
| 3 | Construction of building block for Covered Accn for LT Veh including Staff Car complete all as shown on drawings and as specified. |
| 4 | Construction of building block for Offres Mess for service Offrs (19-28) for 20 Offrs including open court yard & porch complete all as shown on drawings and as specified. |
| 5 | Construction of building block for Single living accn for service Officers (07 No) including open to sky area & pathway arround the OTS complete all as shown on drawings and as specified.Note: Four building structures for total 7 Nos single living accn shall be considered as one block |
| 6 | Construction of building block for Single living accn for service Officers (for Bde Cdr Accn) (01 No), Servant Qtr for service Officers (01 No) & Single Living Accn for Guard (01 Hav & 03 ORS) at Officers Residences complete all as shown on drawings and as specified. |
| 7 | Total Amount of Sch 'A' Part - II (Site Clearance and Development Work) |
| 8 | Total Amount of Sch 'A' Part - III (Internal Water Supply Work) |
| 9 | Total Amount of Sch 'A' Part - IV (Internal Electric Supply Work) |
| 10 | Total Amount of Sch 'A' Part - V (Plumbing Work) |
| 11 | Total Amount of Sch 'A' Part - VI (Area Drainage Work) |
| 12 | Total Amount of Sch 'A' Part - VII (Sewage Disposal Work) |
| 13 | Total Amount of Sch 'A' Part -VIII (Road, Path and Culver Work) |
| 14 | Total Amount of Sch 'A' Part -IX (External Water Supply Work) |
| 15 | Total Amount of Sch 'A' Part -X (External Electric Supply Work) |
| 16 | Total Amount of Sch 'A' Part -XI (Fencing/Compound Wall and Gate Work) |
| 17 | Sch 'A' Part - XII (Misc Items of work) Note: This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as \\"Rs. 0.00\\" under col.5 signifies this fact only. |
| 18 | Bib cock fancy type with wall flange, made of high quality premium brass, crome finish, equipped with an aerator for a soft, uniform, and splash-free water flow, compatible with standard to high water pressure system, screwed down screwed for iron pipe or brass ferrule and fixed for 15mm bore of pipe, complete all as specified and directed. (Note: Make & Cart part shall be approved by GE). |
| 19 | Stop valve/angle cock, made of high quality premium brass, crome finish, sleek body with an included wall flange screwed both ends for iron pipe or for unions for 15mm bore of pipe, complete all as specified and directed.(Note: Make & Cart part shall be approved by GE). |
| 20 | CP over head shower (fancy type), round 180mm dia, high quality crome plated ABS (with gray phase plate) single function rain shower, equipped with Rubit cleaning system for easy limescale removal, 360 degree rotation feature complete all as specified and directed.(Note: Make & Cart part shall be approved by GE). |
| 21 | Two way wall mixture (fancy type), made of brass with sleek crome finish, knob-based diverter and a 115mm bend pipe, wall mounted with provision for top/overhead shower 15mm wall mixture screwed down for iron pipe and fixed complete all as specified and directed.(Note: Make & Cart part shall be approved by GE). |
| 22 | Tall pillar cock (fancy type) 15mm dia, brass made, micro chromium plated 200mm standard body pillar cock screwed for iron pipe and fixed complete all as specified and directed.(Note: Make & Cart part shall be approved by GE). |
| 23 | Tubular towel ring (fancy type), heavy duty brass made with chromium plating 178mm to 185mm ring dia/55mm depth, modern and sleek complete all as specified and directed.(Note: Make & Cart part shall be approved by GE). |
| 24 | Wall mounted toiled roll holder (fancy type) made of high quality brass with a flap of premium stainless steel, modern and sleek complete all as specified and directed.(Note: Make & Cart part shall be approved by GE). |
| 25 | Supply, installation and comminssioning of refrigerator, electric driven (single phase) double door BEE 5 star rated frost free, digital inverter with hermetically sealed compressor of min capacity 460 litres suitable to use on 230 volt, AC supply complete all as specified and directed. |
| 26 | Supply, installation and comminssioning of water cooler, fully stainless steel, electric driven single phase having approx storage capacity 180 litres and nominal cooling capacity of 150 Litres per hour, fitted with hermetically sealed air compressor operating on refrigerant R-134a, complete all as specified and directed. |
| 27 | Voltage stabilizer for automatic operation, single phase naturally air cooled, copper wound, indoor type, wall mounted type & designed for input variation between 140 volts to 280 volts with output stabilized voltage at 230 volts with accuracy of ± 2.5% and of capacity 1 KVA, complete all as specified and directed. |
| 28 | Desert Cooler of over all size 23'X23\\"X30\\", electrric driven (single phase), having nominal air flow capacity of 5000 Cum/Hr (or nearest size) made out of mild steel body 22 gauge, duly painted with synthetic anti-corrosive paint with suitable capacity copper wound motor, three step speed regulator (high/medium/low) with metallic blade, submersible pump of suitable capacity, 230 Volts, 50Hz and including wood wool pad of proper thickness and 2.50Sqmm three core copper wire with connected 3 pin top plug complete all as specified and directed. |
| 29 | Ceiling fan complete with blades, down rods modular fan step regulator, 120W, 2 module and accessories, 230V, 1200mm sweep, min air delivery 210CFM, with service value 6.00 BEE, five star rated with brushless direct current motor (BLDC), complete all as specified and directed. |
| 30 | Ceiling fan complete with blades, down rods modular fan step regulator, 120W, 2 module and accessories, 230V, 1400mm sweep, min air delivery 245CFM, with service value 6.00 BEE, five star rated with brushless direct current motor (BLDC), complete all as specified and directed. |
| 31 | Exhaust fan, steel body AC single phase, 230V of size 300mm sweep, heavy duty, with blades, frame and louvers, complete all as specified and directed. |
| 32 | Electric water heater, storage type steel body with copper inner tank and heating element 2 KW capacity 25 litre, BEE 5 star rated complete with all accessories such as safety valve, thermostate, NRV, connection piece etc; complete all as specified and as directed. |
| 33 | HI wall split units indoor/outdoor complete with cordless remote control unit and with in built heating and cooling arrangement and digital inverter twin rotary of capacity 1.5 TR complete all as specified and directed. |
| 34 | Voltage stabilizer for automatic operation, single phase naturally air cooled indoor wall mounted type & designed for input variation between 140 volts to 280 volts with output stabilized voltage at 230 volts with accuracy of ± 2.5% and of capacity 4 KVA, complete all as specified and directed. |
| 35 | Concealed sub main wiring of two run with 06 sqmm single core PVC insulated, FRLSH, flexible multi stranded copper conductor cable 1100 volts grade, drawn through and including PVC conduit 25mm dia , medium grade, ISI marked and fixed, including cutting /chasing as required and its accessories including one run of 6 Sqmm single core PVC insulated, FRLSH, multi stranded copper conductor cable as earth continuity conductor in green colour, connected to common earth dolly, complete all as specified and as directed. Note No1: Two run of 6 sqmm single core copper conductor cable and one run of 6 sqmm single core copper conductor cable as earth continuity and one run of PVC conduit shall be measured as one unit only.Note No 2: Any cutting /leaving /forming holes, chases etc., in walls, floors and ceiling as required and making good the same, shall be deemded to be included in lump sum Sch 'A' Part-I as per para 10(b) in Sch 'A' BOQ Notes. |
| 36 | RCC hume spun pipe 450mm dia, type NP-2 culvert, 7.00 mtr length PCC 1:3:6 in foundation, brick with sub class ‘B’ bricks in cm 1:4 in any type of soil etc; complete all as shown in drawing No CEUZ/TD-1293/08, sheet No.1/2 to 2/2. |
| 37 | Construction of valve pit of size (40x40x60)mm (Internal dimensions) using PCC (1:4:8) type D-2, using 40mm graded crushed stone aggregate for foundation, 75mm thick and 100mm off sets on all sides, 230mm thick brick masonary walls built in cement mortar (1:4), 15mm thick rendering all around the masonry work in cement (1:4), for internal and up to 15cm below GL for external surfaces of walls, 50mm thick PCC (1:3:6) type C-1 using with 20mm graded crushed stone aggregate including necessary form work for grouting including 3mm thick, MS top sheet cover double door with locking arrangement welded to MS frame made out of (1000x1000x1000)mm angle iron frame fixed with hold fasts including painting of steel surface with two coats of synthetic enamel paint over a coat of red oxide primer including necessary excavation in any kind of soil, returning filling in and removal of surplus soil to a distance not exceeding 50m complete all as specified and shown on drawing. |
| 38 | Supply, installation, testing and commisioning transformer of capacity 315 KVA, 11/0.433 KV, 3phase, 50Hz, ONAN cooled oil immersed copper wound out door type step down transformer with off circuit tap changer having +7.5% tapping in steps of 2.5% tapping confirming to IS 1180-2014, complete with all fittings and accessories EEL-2 all as specified and directed comprising following accessories:-i) Off circuit changing switch with indicating plate and ii) Oil conserverter with filling hole and cap -01 Noiii) Silica gel breather with initial charging -01 setiv) Drain /sampling/filter valve with plug -01 Nov) Top filter valve with plug -01 No vi) Explosion vent with diaphram -01 Novii) Thermometer pocket -2 Noviii) Rating and diaphragm plate -1 Noix) Earthing terminal -2 Nox) Additional neutral bushing for solid earthing -1 No (Contd..../) |
| 39 | xi) Plain oil level guage -1 Noxii) Lifting plug -2 Noxiii) Air release plug -2 Noxiv) BI directional & uni directional plate roll -4 Noxv) HV bushing outdoor (03) No & LV end box with bushing complete set.xvi) Temp gauge dial typexvii) Provn of neutral earthing Note:- (i) Cost of RCC Foundation for transformer and cattle fencing (1.5 Mtr high) around transformer is included in the above rates.(For Officer Mess, Single Living Accn for Service Officres, Bde Cdr Accommodation and Existing Electric Load) |
| 40 | Supply, installation, testing and commisioning transformer of capacity 160 KVA, 11/0.433 KV, 3phase, 50Hz, ONAN cooled oil Immersed copper wound out door type step down transformer with off circuit tap changer having +7.5% tapping in steps of 2.5% tapping confirming to IS 1180-2014, complete with all fittings and accessories EEL-2 all as specified and directed comprising following accessories:-i) Off circuit changing switch with indicating plate and ii) Oil conserverter with filling hole and cap -01 Noiii) Silica gel breather with initial charging -01 setiv) Drain /sampling/filter valve with plug -01 Nov) Top filter valve with plug -01 No vi) Explosion vent with diaphram -01 Novii) Thermometer pocket -2 Noviii) Rating and diaphragm plate -1 Noix) Earthing terminal -2 Nox) Additional neutral bushing for solid earthing -1 No (Contd.../) |
| 41 | xi) Plain oil level guage -1 Noxii) Lifting plug -2 Noxiii) Air release plug -2 Noxiv) Bi directional & uni directional plate roll -4 Noxv) HV bushing outdoor (03) Nos & LV end box with bushing complete set.xvi) Temp gauge dial typexvii) Provn of neutral earthing Note:- (i) Cost of RCC Foundation for transformer and cattle fencing (1.5 Mtr high) around transformer is included in the above rates.(For Adm Block) |
| 42 | Supply, fixing, commissioning and testing of outdoor, gang operated air-break switch, tilting type, 11KV of current rating upto 400 Amps, triple pole, each pole consisting of galvanized steel base, HT insulators as per IS, non ferrous knife and spray, loaded contacts, arcing horns of adequate section to break magnetizing current of the transformers, horizontal GI pipe of adequate length for phase separation, adequate length of GI pipes for operation from ground level and operating handle with locking arrangement complete in both OFF & ON positions. All ferrous parts hot dripped galvanized and non ferrous heavily tinned to with stand weather and suitable for vertical mounting, Complete all as specified and as directed. |
| 43 | Factory made LT electrical panel board, AC, 3 phase, 4 wire, 415 / 500 V, 50 Hz, cubical outdoor type, fabricated with 3.15mm thick, made out of mild steel sheet /CRCA (1200mm x 1500mm x 500mm), powder coated, thickness of inner shell to be not less 2mm, CPRI Approved , bottom with detachable plates, front and rear with hinged type double door and locking arrangements, chamber for cable entry and exit, chamber for copper bus bars including copper bus bars 4 No, 300 amps capacity insulated with colored PVC sleeves mounted on frame of mild steel angle iron 25mm x 25mm x 5mm, 30cm above from the ground level duly supported with mild steel angle iron 50mm x 50mm x 6mm, embedded in plain cement concrete M-10 (1:3:6), type C-1 (using 20mm graded crushed stone aggregate) 300mm below the ground level and required masonry in brick work in cement mortar 1:6 including suitable insulators and separators, holes drilled for connections, complete suitable for mounting following switch gear items internally connected with suitable capacity copper strip insulated, complete all as specified and comprising of the followings:- (Contd.../) |
| 44 | (a) MCCB 250 Amps adjustable type capacity, 36 KA 4P, 415 V -01 No (incoming)(b) MCCB 100 Amps adjustable type capacity, 16 KA 4P, 415 -03 No (outgoing) (02 No working and 01 No standby)(c) MCCB 63 Amps adjustable type capacity, 25 KA 4P, 415- 02 No (outgoing) (01 No working and 01 No standby)(d) Change over switch on load 415 volts TPN in sheet metal enclosure of capacity 63 Amps -01 No(e) AC Three phase static energy meter of accuracy class 1.0, 3 X 240 V, 50 Hz with backlit LCD display of rating 10 - 60 A (measures and displays KWH, V, Current I, KW, pf last month history of KWH, MD in KW) with special features like TOD, temper logging, optical communication port display in absence of power with transparent hinge type box-01 No (f) Capacitor metalized poly propylene heavy duty (MPP-H) for 3 phase, 440 V, 50 Hz System for permissible non- linear load 15% of 20 KVAR capacity -01 No (g) Ammeter flush pattern type square dial 96mm x 96 mm alongwith selector switch - 01 No and suitable CT ratio 0-1000 Amps(h) Voltmeter flush pattern type square dial 96mm x 96mm alongwith selector switch - 01 No 0-500 V (j) complete control panel wiring with stranded copper conductor of suitable size along with one set indicator lamp for R,Y & B for each incoming and outgoing feeder (For Adm Block) |
| 45 | Factory made LT feeder pillar box type AC, 3 phase, 4 wire, 415/500 V, 50 Hz, cubical OUTDOOR type, fabricated with CRCA sheet 3.15mm thick of size 50mm x 50mm x 25mm (H X W X D), powder coated, CPRI Approved, bottom with detachable plates, front and rear with hinged type double door and locking arrangements, chamber for cable entry and exit, chamber for copper bus bars including copper bus bars 4 No, 100 amps capacity insulated with colored PVC sleeves, floor mounted on frame of mild steel angle iron 25mm x 25mm x 5mm, 30cm above from the ground level duly supported with mild steel angle iron, embedded in plain cement concrete M-10 (1:3:6), type C-1 (using 20mm graded crushed stone aggregate) 300mm below the ground level and required masonry in brick work in cement mortar 1:6 including offsets all as per manufacturer's instructions and including suitable insulators and separators, holes drilled for connections, complete all as specified. |
| 46 | Earthing complete with galvanized steel earth plate electrode 600mm x 600mm x 6.0mm thick buried directly in ground ( earth pit not less than 2.25 mtr below normal ground level) with top edge plate not less than 1.5 metre below normal ground level connected to galvanized earth strip of size (32x6)mm as earthing lead by means of bolts, nuts, chuck nuts and washers of galvanized iron earth lead with 15 cm thick alternate layers of charcoal dust & common slat including PCC pit in PCC 1:2:4 type B-1, RCC cover made out of cement concrete 1:2:4 type B-1 (using 20 mm graded crushed stone aggregate) reinforced with TMT steel bars 8 mm dia @150 mm c/c both ways with suitable handle and angle iron (40x40x5)mm frame, GI medium grade watering pipe 20mm bore and funnel with wire mesh, GI light grade protection pipe 40mm bore up to main board complete as shown on electrical plate No 3 of MES Sch 2009 (Part-I) and testing on completion complete all as specified and directed. Note: - On testing after completion of earthing, if desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk & cost to the entire satisfaction. |
| 47 | Earthing complete with galvanized steel earth plate electrode 600mm x 600mm x 6mm buried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of earth plate not less than 1.5m below normal ground level connected with galvanized iron earth lead wire 4mm dia by means of bolts, nuts, check nuts and washers of galvanized iron or steel complete, 20mm dia GI medium grade watering pipe with funnel including charcoal, dust, salt, PCC M-15 type B1 in pit with angle iron (25x25x3)mm frame work with precast RCC 1:2:4 type B-1 cover reinforced with 8mm dia TMT bars @ 150mm C/C both ways and 12mm dia MS fabricated handle, test point etc. in and including light grade GI protection pipe 15mm bore up to 7.5m length for drawing in earth lead wire, all as shown in electric plate No. 3 of SSR Part-I complete with necessary earth work in any type of soil, removal of soil to a distance not exc. 50m, testing on completion complete all as specified and directed.Note:- On testing after completion of earthing, if desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk & cost to the entire satisfaction. |
| 48 | Cable route indicator /marker made up of PCC block in cement mortar 1:3:6, type C-1, (using 20mm graded crushed stone aggregate) of size 900mm x 300mm x 100mm thick with danger/11KV cable/mes embossing on cable route indicator/marker including painting as per approved colour and buried in ground 45cms including necessary earth work (as required /order at site), complete all as specified and as directed.(f) Capacitor metalized poly propylene heavy duty (MPP-H) for 3 phase ,440 V, 50 Hz System for permissible non- linear load 15% of 20 KVAR capacity -01 No |
| 49 | Construction of PCC platform for transformer of size 3m x 2.5m and 1.5m high from ground level with brick construction in walls and steps, PCC 1:5:10 type E-2 in foundation, brick work in CM 1:4, 10mm thick rendering in CM 1:4 to walls, 50mm thick PCC 1:2:4 type B-1 (using 20mm graded crushed stone aggregate). In flooring 40mm thick PCC on steps, painting to fencing with two coats of synthetic enamel paint over a coat of red oxide primer complete duly surrounded with XPM fencing of length not less than 15 meter and width not less than 10 meter complete with 40mmx5mm angle iron & 12mm dia steel bars, fixed on PCC gate pillers complete including sliding bolt, locking arrangements hinges and all accessories,shown on drawing No CE/TD/1129/96 sheet No. 1/2 & 2/2 complete all as specified. |
| 50 | Supply, installation and testing of silent diesel engine driven generating set, 50kVA, conforming to IS:10002-1981, complete with diesel engine of suitable BHP & AC brushless SPDP alternator, conforming to IS: 13364-1992, mounted on a common base frame & coupled through a flexible coupling or close coupled and AMF panel complete with platform, control panel having meters, sound-proof canopy etc; of capacity 50kVA complete all as specified and directed having following features:-a) Engine: 4/6 cylinder, in line, 4 stroke, radiator cooled engine, well designed air handling system with dry type, heavy duty, replaceable paper element air cleaner with restriction indicator, air to air aftercooling, optimised turbocharger for increased altitude, inline fuel pump with A1 class mechanical governing, spin on fuel filter, standard integral set mounted radiator system, designed and tested for 50o C ambient temperature, full glow spin on lube oil filter, electrical starter motor with soft start engagement feature, battery charging alternator with 1x12V, DC battery. (Contd..../) |
| 51 | b) ALternator: Brushless type, screen protected, revolving field, self-excited alternator, conforming to winding specially designed for single operation, impregnation on all wound components for better mechanical strength.c) Control panel: Manufactured with 14/16 gauge CRCA sheet and powder coated for weather-proof and long lasting finish. The control panel consists of the following parts:-i) Controller: Aluminium bus bars with suitable capacity with incoming/outgoing terminals.ii) Indicating lamps for 'Load ON' and 'Set Running'.iii) Instrument fuses duly wired and ferruled.iv) MCCB of suitable rating with overload and short circuit protections. |
| 52 | Construction of septic tank for 50 users (Brick construction) complete all as shown on drg No. CEUZ /TD-1585/2021 sheet 1/4 to 4/4 and as specified. |
| 53 | LLDPE septic tank designed to carry sewage and sludge water, comprising earth work , excevation, returning filling, disposal of surplus spoils to a distance not exceeding 50 mtr from starting point in any type of soil, PCC 1:4:8 type D-2 (using 40mm graded crushed stone aggregate) in foundation, 200mm thick, vent shaft, connections etc.for 25 users (4000liter capacity) including all fittings, fixtures, testing on completion complete all as specified. |
| 54 | Construction of soakage well (Brick construction) 2.4m dia and 3.40m deep below inlet pipe level (depth from inlet pipe to ground level 45cm), complete all as specified and shown on drg No. CEUZ/TD-1585/2021 sheet 1/4 to 4/4. |
| 55 | Construction of soakage well (Brick construction) 1.80m dia and 2.9m deep below inlet pipe level (depth from inlet pipe to ground level 45cm), complete all as specified and shown on drg No. CEUZ/TD-1585/2021 sheet 1/4 to 4/4. |
| 56 | Point wiring complete with 1.5 sqmm PVC insulated, FRLSH type, ISI marked, conforming to IS-694/1990 unsheathed, multistranded, single core, copper conductor cable 1100 volts grade colour code cables drawn through and including PVC Conduit 20mm dia medium grade (MMS) and all accessories are concealed in walls / roofs / floors / ceiling etc; including modular metal flush box with top, bottom, side/back wall knockout for conduit entry from any direction made out of 1.60mm thick including modular top cover plate as per numbers of switch modules for fixing of modular switches, sockets, fan regulators, red colour indicator, blank plates etc. as approved colours and including 1.5 Sqmm PVC insulated multistranded FRLSH type unsheathed (Green colour), single core cable with copper conductor cable as earth continuity conductor and connecting to common earth dolly and including making good the disturbed surfaces to match with existing surface and colour coat including providing putty and white cement for smooth finishing of existing surface complete all as specified and directed for the following:- Note No1: All necessary accessories such as modular steel box, top cover plate, blank plate, screws, washers and all modular electrical fixtures are to be used of same make/brand only. Note No 2: Any cutting /leaving /forming holes, chases etc., in walls, floors and ceiling as required and making good the same, shall be deemded to be included in lump sum Sch 'A' Part-I as per para 10(b) in Sch 'A' BOQ Notes. |
| 57 | All as per Srl item No. 47.00 here-in-before above but one light/fan/bell point controlled by one switch |
| 58 | All as per Srl item No. 47.00 here-in-before above but with one 3/5 pin socket outlet, 5/6 Amp on independent board |
| 59 | All as per Srl item No. 47.00 here-in-before above but with one socket outlet 3 Pin, 5 Amps, on the same board |
| 60 | All as per Srl item No. 47.00 here-in-before above but with 2.5 sqmm and earth conductor, 2.5 sqmm one 6 pin, 16/6 amps socket outlet point controlled by one switch on indendent board. |
| 61 | Vertical type sheet metal enclosure, DB, TPN, 4 way double door made powder coated out of CRCA mild steel sheet 1.6mm thick, IP-43, 15 volts, 200 amps rated fitted bus bar dust and vermin proof suitable for incorporation of MCCB as incomer and MCBs as out going duly concealed on wall and making good the distribution surface including MCCB, four pole, 125Amps, 415 volts, 50Hz, 16KA complete all as specified and as directed. |
| 62 | Sub main wiring with two run of single core FRLSH PVC insulated unsheathed 1100 volts grade cable with stranded copper conductor of size 4 Sqmm drawing through and including concealed rigid non metallic PVC conduit medium grade ISI marked 25mm dia or above required including one single core FRLSH PVC insulated unsheathed 1100 volts grade cable with stranded copper conductor of size 4 sqmm as earth continuity conductor connected to commen earth dolly complete all as specified and directed.Note No1: Two run of 4 sqmm single core copper conductor cable and one run of 4 sqmm single core copper conductor cable as earth continuity and one run of PVC conduit shall be measured as one unit only.Note No 2: Any cutting /leaving /forming holes, chases etc., in walls, floors and ceiling as required and making good the same, shall be deemded to be included in lump sum Sch 'A' Part-I as per para 10(b) in Sch 'A' BOQ Notes. |
| 63 | Sub main wiring with four run of single core FRLSH PVC insulated unsheathed 1100 volts grade cable with stranded copper conductor of size 10 Sqmm drawing through and including concealed rigid non metallic PVC conduit medium grade ISI marked 25mm dia or above required including one single core FRLSH PVC insulated unsheathed 1100 volts grade cable with stranded copper conductor of size 10 sqmm as earth continuity conductor connected to commen earth dolly complete all as specified and directed.Note No1: Four run of 10 sqmm single core copper conductor cable and one run of 4 sqmm single core copper conductor cable as earth continuity and one run of PVC conduit shall be measured as one unit only.Note No 2: Any cutting /leaving /forming holes, chases etc., in walls, floors and ceiling as required and making good the same, shall be deemded to be included in lump sum Sch 'A' Part-I as per para 10(b) in Sch 'A' BOQ Notes. |
| 64 | Earth work in excavation by mechanical means Hydraulic excavator)/ in foundation trenches or drains (exceeding 1.5 m in width or 10sqm on plan), including dressing of sides and ramming of bottoms, lift upto 3m, including getting out in all kind of soil (the excavated soil) and disposal of surplus excavated soil, within a lead of 50m complete all as specified and directed.Note:- Contractor may at his discretion use any means for excavation and width required at site. However payment shall be made for authorized width only as defined in preamble para 3.2.3 to section 3 of MES SSR Part-II. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
CompletedCorrigendum-2 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 9 daysBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 9 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 11 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender