| 1 | Taking down carefully copper/ aluminium point wiring of light, fan, socket 5/15Amps or power point complete including fittings such as switches, ceiling rose, pendant, regulator, socket, lamp holders, brackets, lamp fittings, tube light fittings etc including switch boards/sunken box and making good the disturbed of wall/ceiling/floors etc so as to match with the existing surface complete all as specified and as directed. |
| 2 | Material and labour for point wiring for one light point controlled by one way switch complete with 1100Volts grade 1.50 Sqmm PVC insulated unsheathed multistranded FRLSH grade copper conductor cable fixed/ drawn through and including white/ ivory colour heavy duty PVC casing/ capping with accessories and fixing on wall/ ceiling including PVC board with cover (ISI marked) for mounting switches, sockets, regulators etc and providing one run of 1.5 sqmm PVC insulated unsheathed multistranded FRLSH grade copper conductor cable as earth continuity wire and connecting to common earth and carrying out IR test for each circuit including making good the disturbed surface by cement mortar 1:3 and matching/ finishing surfaces by distemper/ colour wash as per existing colour surfaces over plaster of perish/ putty complete all as specified and directed. |
| 3 | For one light point controlled by one switch |
| 4 | For one ceiling fan point controlled by one switch |
| 5 | For one exhaust fan point controlled by one switch |
| 6 | For one bell point controlled by one switch |
| 7 | For one 5 Amp independent socket point controlled by one switch |
| 8 | For one 5 Amp socket point controlled by one switch on same board |
| 9 | For one light point Controlled by two 2-way Switch |
| 10 | Material and labour for point wiring for 15Amp independent socket point controlled by one switch complete with 1100 Volts grade 4.0 Sqmm PVC insulated unsheathed multistranded FRLSH grade copper conductor cable fixed/ drawn through and including white/ ivory colour heavy duty PVC casing/ capping with accessories and fixing on wall/ ceiling including PVC board with cover (ISI marked) for mounting switches, sockets, regulators etc and providing one run of 4.0 sqmm PVC insulated unsheathed multistranded FRLSH grade copper conductor cable as earth continuity wire and connecting to common earth and carrying out IR test for each circuit including making good the disturbed surface by cement mortar 1:3 and matching/ finishing surfaces by distemper/ colour wash as per existing colour surfaces over plaster of perish/ putty complete all as specified and directed. |
| 11 | Material and labour for point wiring for 15Amp independent socket point controlled by one switch complete with 1100 Volts grade 2.50 Sqmm PVC insulated unsheathed multistranded FRLSH grade copper conductor cable fixed/ drawn through and including white/ ivory colour heavy duty PVC casing/ capping with accessories and fixing on wall/ ceiling including PVC board with cover (ISI marked) for mounting switches, sockets, regulators etc and providing one run of 2.5 sqmm PVC insulated unsheathed multistranded FRLSH grade copper conductor cable as earth continuity wire and connecting to common earth and carrying out IR test for each circuit including making good the disturbed surface by cement mortar 1:3 and matching/ finishing surfaces by distemper/ colour wash as per existing colour surfaces over plaster of perish/ putty complete all as specified and directed. |
| 12 | Supply and fix switch flush type, single pole, one way, 6Amps, 240 Volts, white finish complete all as specified |
| 13 | S & F stepped type electronic fan regulator flush type 1 Module on the existing phenolic laminated sheet etc. as reqd |
| 14 | Supply and fix switch flush type 16Amps, 240 Volts, single pole white finish complete all as specified and directed. |
| 15 | Supply and fix bell push, 5Amps, 240 Volts white finish complete all as specified |
| 16 | Supply and fix socket outlet, 5 pin, 6 Amps, flush type, white finish complete all as specified |
| 17 | Supply and fix socket outlet, 2 in1, 3 pin, 6/16 Amps, flush type universal, 240 Volt, white finish complete all as specified |
| 18 | M&L for point wiring complete with PVC insulated and unsheathed cable 1.5 sqmm (nominal area) ISI marked multi-stranded copper conductor single core including ISI marked 20mm dia 'medium grade' PVC conduit for point wiring concealed in wall/false ceiling with pressed steel concealed Sunken boxes suitable for Modular Switch & Socket not less than 1.6mm thick of reqd size (factory painted) and with top cover 3 mm thick of Hylam sheets of required colour, painting Sunken boxes inside and out side with one coat of red oxide primer complete including 1.5 sqmm PVC insulated and unsheathed ISI marked copper cable to common earth connected to earth dolly colour coding of cable as per IE Rule complete all as specified & directed |
| 19 | For one light point controlled by one switch |
| 20 | For one ceiling fan point controlled by one switch |
| 21 | For one exhaust fan point controlled by one switch |
| 22 | For one bell point controlled by one switch |
| 23 | One 6A, 5 pin socket outlet point on same board with other switches including earth wire and connected to common earth and earth terminal |
| 24 | One 6A, 5 pin socket outlet point on independent board with including earth wire and connected to common earth and earth terminals |
| 25 | For one light point Controlled by two 2-way Switch |
| 26 | M&L for point wiring complete with PVC insulated and unsheathed cable 2.5 sqmm (nominal area) ISI marked multi-stranded copper conductor single core including ISI marked 20mm dia 'medium grade' PVC conduit for point wiring concealed in wall/false ceiling with pressed steel concealed Sunken boxes suitable for Modular Switch & Socket not less than 1.6mm thick of reqd size (factory painted) and with top cover 3 mm thick of Hylam sheets of required colour, painting Sunken boxes inside and out side with one coat of red oxide primer complete including 2.5 sqmm PVC insulated and unsheathed ISI marked copper cable to common earth connected to earth dolly colour coding of cable as per IE Rule complete all as specified & directed. |
| 27 | M&L for point wiring complete with PVC insulated and unsheathed cable 4.0 sqmm (nominal area) ISI marked multi-stranded copper conductor single core including ISI marked 20mm dia 'medium grade' PVC conduit for point wiring concealed in wall/false ceiling with pressed steel concealed Sunken boxes suitable for Modular Switch & Socket not less than 1.6mm thick of reqd size (factory painted) and with top cover 3 mm thick of Hylam sheets of required colour, painting Sunken boxes inside and out side with one coat of red oxide primer complete including 4.0 sqmm PVC insulated and unsheathed ISI marked copper cable to common earth connected to earth dolly colour coding of cable as per IE Rule complete all as specified & directed |
| 28 | S & F Modular switch 1 way 6A, 1 module complete all as specified |
| 29 | S & F Modular switch 1 way 16A, 1 module complete all as specified |
| 30 | S & F Modular Bell push 6A 1 module complete all as specified |
| 31 | S & F Socket, 6A - 2/3 pin combined 2 module complete all as specified |
| 32 | S & F Socket 6A/16A - 2/3 pin combined 2 module, complete all as specified |
| 33 | S & F Modular Fan step regulator, 120W - 2 module complete all as specified |
| 34 | Note:The rate will be inclusive of suitable cover, and module frame for group of switches, sockets etc all as required as per site requirement. |
| 35 | S & F Buzzer, Ding dong AC 230 Volts ,single complete all as specified |
| 36 | S & F in repairs modular surface mounted plastic boxes 1/2 module for fixing of switches, sockets and regulators etc ISI marked complete all as specified and as directed |
| 37 | S & F in repairs modular surface mounted plastic boxes 3/4 module for fixing of switches, sockets and regulators etc ISI marked complete all as specified and as directed |
| 38 | S & F in repairs modular surface mounted plastic boxes 4/6 module for fixing of switches, sockets and regulator etc ISI marked complete all as specified and as directed |
| 39 | S & F in repairs modular surface mounted plastic boxes 8 module for fixing of switches, sockets and regulator etc ISI marked complete all as specified and as directed |
| 40 | M & L for fixing AC single phase static energy meter of accuracy class 1.0 ,240 volt , 50 Hz with backlit LCD display of rating 05 to 60 Amps and with 1 push button (measures and display KWH, KVAh,V, I, P.F) with transparent hinge type box (The company should provide a meter replacement warranty of 5 years) incl taking down of old unsv meter complete all as specified |
| 41 | M&L Sub main wiring using two runs of FRLSH grade PVC insulated ,unsheathed ,stranded, copper conductor cable of size 6 Sqmm and one run of 6 Sqmm FRLSH grade PVC insulated, unsheathed, stranded, single core, copper wire as earth wire to be drawn in and including white/ ivory colour heavy duty PVC casing/ capping with accessories and fixing on wall/ ceiling Including wiring of suitable size including taking down old submain wiring with fittings & fixtures and all as specified.Note : Two runs of 6 Sqmm copper wire,one run of 6 Sqmm earth wire & one run PVC Conduit shall be measured as one unit |
| 42 | M&L Sub main wiring using two runs of FRLSH grade PVC insulated ,unsheathed ,stranded, copper conductor cable of size 4 Sqmm and one run of 4 Sqmm FRLSH grade PVC insulated, unsheathed, stranded, single core, copper wire as earth wire to be drawn in and including white/ ivory colour heavy duty PVC casing/ capping with accessories and fixing on wall/ ceiling Including wiring of suitable size including taking down old submain wiring with fittings & fixtures and all as specified.Note : Two runs of 4 Sqmm copper wire,one run of 4 Sqmm earth wire & one run PVC Conduit shall be measured as one unit |
| 43 | M&L Sub main wiring using two runs of FRLSH grade PVC insulated ,unsheathed ,stranded, copper conductor cable of size 4 Sqmm and one run of 4 Sqmm FRLSH grade PVC insulated, unsheathed, stranded, single core, copper wire as earth wire to be drawn in and including 25 mm size PVC Conduit (medium grade) in Concealed wiring of suitable size including taking down old submain wiring with fittings & fixtures and all as specified.Note : Two runs of 4 Sqmm copper wire,one run of 4 Sqmm earth wire & one run PVC Conduit shall be measured as one unit |
| 44 | M&L Sub main wiring using two runs of FRLSH grade PVC insulated ,unsheathed ,stranded, copper conductor cable of size 6 Sqmm and one run of 6 Sqmm FRLSH grade PVC insulated, unsheathed, stranded, single core, copper wire as earth wire to be drawn in and including 25 mm size PVC Conduit (medium grade) in Concealed wiring of suitable size including taking down old submain wiring with fittings & fixtures and all as specified.Note : Two runs of 6 Sqmm copper wire,one run of 6 Sqmm earth wire & one run PVC Conduit shall be measured as one unit |
| 45 | M&L Sub main wiring using two runs of FRLSH grade PVC insulated ,unsheathed ,stranded, copper conductor cable of size 6 Sqmm and one run of 6 Sqmm FRLSH grade PVC insulated, unsheathed, stranded, single core, copper wire as earth wire to be drawn in Existing PVC Conduit in Concealed wiring of suitable size including taking down old submain wiring with fittings & fixtures and all as specified.Note : Two runs of 6 Sqmm copper wire,one run of 6 Sqmm earth wire shall be measured as one unit |
| 46 | M&L Sheet metal enclosures for single pole and neutral enclosure with a two pin and earth plug and socket complete with single pole mcb 20 Amp 240 Volt complete all as specified and as directed. |
| 47 | S & F for Sheet Metal Enclosure MCB DB SPN 4 Way, IP 43,IK 09, with 100 Amps rated bus bar 240 Volts double door with magnetic locking system including necessary provision for inserting the DBs in Wall by cutting the brick/stone masonary etc & taking down of unsv DB and making good of disturbed surface to match with existing colour of wall complete all as specified and directed.Note:- The space left after inserting MCB should be properly filled with blanking plate |
| 48 | S & F for Sheet Metal Enclosure MCB DB SPN 6 Way, IP 43,IK 09, with 100 Amps rated bus bar 240 Volts double door with magnetic locking system including necessary provision for inserting the DBs in Wall by cutting the brick/stone masonary etc & taking down of unsv DB and making good of disturbed surface to match with existing colour of wall complete all as specified and directed.Note:- The space left after inserting MCB should be properly filled with blanking plate |
| 49 | S & F for Sheet Metal Enclosure MCB DB SPN 8 Way, IP 43,IK 09, with 200 Amps rated bus bar 240 Volts double door with magnetic locking system including necessary provision for inserting the DBs in Wall by cutting the brick/stone masonary etc & taking down of unsv DB and making good of disturbed surface to match with existing colour of wall complete all as specified and directed.Note:- The space left after inserting MCB should be properly filled with blanking plate |
| 50 | S & F for Sheet Metal Enclosure MCB DB SPN 12 Way, IP 43,IK 09, with 200 Amps rated bus bar 240 Volts double door with magnetic locking system including necessary provision for inserting the DBs in Wall by cutting the brick/stone masonary etc & taking down of unsv DB and making good of disturbed surface to match with existing colour of wall complete all as specified and directed.Note:- The space left after inserting MCB should be properly filled with blanking plate |
| 51 | S & F for Sheet Metal Enclosure MCB DB TPN 4 Way, IP 43,IK 09, Vertical Type with 200 Amps rated bus bar 240 Volts double door with magnetic locking system including necessary provision for inserting the DBs in Wall by cutting the brick/stone masonary etc & taking down of unsv DB and making good of disturbed surface to match with existing colour of wall complete all as specified and directed.Note:- The space left after inserting MCB should be properly filled with blanking plate |
| 52 | Supply and fix sheet metal enclosure double door, vertical type for DB’s when MCCB’s to be used as incomer including MCCB 100 Amp triple pole and neutral 4 ways IP 43,IK 09, 415 volts with 200amps rated bus bar fixed sunk/ flush to wall by cutting the brick/stone masonary etc & taking down of unsv DB and making good of disturbed surface to match with existing colour of wall complete all as specified and directed.Note:- The space left after inserting MCB should be properly filled with blanking plate |
| 53 | Supply and fix for MCB Single Pole rated capacity 6 to 32Amp,240 Volts10KA breaking capacity 10 KA , 'C' curve connected with suitable lugs complete all as specified and as directed. |
| 54 | Supply and fix for MCB Single Pole & neutral rated capacity 16 to 32Amp,240 Volts10KA breaking capacity 10 KA , 'C' curve connected with suitable lugs complete all as specified and as directed. |
| 55 | Supply and fix for MCB Triple Pole & neutral rated capacity 40 to 63Amp,415 Volts10KA breaking capacity 10 KA , 'C' curve connected with suitable lugs complete all as specified and as directed. |
| 56 | Supply and fixing in replacement, MCB SPN 40-63 Amp, 240V, 10KA, 'C' curve complete with connection testing and commissioning all as specified and directed by Engr-in-charge. |
| 57 | Supply and fix in repairs of MCCB 3P 25 to 100 Amps /415Volts ,having breaking capacity Ics=100%Icu with complete accessories as per existing suitable size complete all as specified and as directed |
| 58 | Supply and fix in repairs of MCCB 3P 160 Amps /415Volts ,having breaking capacity Ics=100%Icu with Complete accessories as per existing suitable size complete all as specified and as directed |
| 59 | Supply and fix in repairs of MCCB 4P 63 Amps /415Volts ,having breaking capacity Ics=100%Icu with complete accessories as per existing suitable size complete all as specified and as directed |
| 60 | Supply and fix in repairs of MCCB 4P 100 Amps /415Volts ,having breaking capacity Ics=100%Icu with Complete accessories as per existing suitable size complete all as specified and as directed |
| 61 | Supply and fixing High-quality design LED Tube light fittings in extruded with high quality PC diffuser 1x20 watt with enhances safety and relible ,robust housing structure with efficiency of 100 lm/W ,decorative end caps complete with all accessories internally pre-wired and including connecting up with twin core twisted flexible copper conductor cable including taking down old light fittings complete all as specified and directed. |
| 62 | S&F LED Batten Tube Light light fittings 10 Watt and fixed with wall surface with anodized extruded aluminium housing, high transmissitivity diffuser and high lumen output and connecting with 3 core flexible copper cable PVC insulated complete all as specified and directed. |
| 63 | Supply and fixing for LED luminaire 600 mm x 600 mm, square LED Panel 36 Watt ,lumen output >= 110 lumen/watt , 220 V AC Ceiling mounted type with high effeciency PMMA diffuser soft glare free light complete with driver holder, LED lamp suitable for roof/false ceiling ,including connecting up with driver three core flexible copper conductor cases of suitable size complete all as directed by Eng-in- Charge |
| 64 | Supply and fix Ceiling rose, 3 phase/PVC polycarbonate, isolated body, white finish complete all as specified |
| 65 | Supply ans fixing 18 watt surface led panel round 6500k trimless ,lumen 1440 lm complete all as specified and as directed |
| 66 | Supply and fix energy efficient exhaust fan, 300m sweep made of metal body Ventil air -DS type complete with louvers with bolts nuts and washer size of the bolt 15 cm long 12 mm dia embedded in the wall including provision of PVC flexible copper cable of size 23/0.0076 two core from ceiling rose to exhaust fan connection and making suitable size of hole to existing brick wall for fan base including writing the MES Number with synthetic enamel paint complete all as specified and directed .(Note: Cost of suitable opening wall for fixing exhaust fan is deemed to be included in overall rate quoted. |
| 67 | Supply and fix energy efficient exhaust fan, Engineering plastic complete with louvers shutter ,voltage230,50 hz,rpm1200,copper winding 250 mm sweep with bolts nuts and washer size of the bolt 15 cm long 12 mm dia embedded in the wall including provision of PVC flexible copper cable of size 23/0.0076 two core from ceiling rose to exhaust fan connection and making suitable size of hole to existing brick wall for fan base including writing the MES Number with synthetic enamel paint complete all as specified and directed .(Note: Cost of suitable opening wall for fixing exhaust fan is deemed to be included in overall rate quoted. |
| 68 | Supply and fixing of PVC Exhaust Fan 150 mm sweep with lovour complete all as specified and as directed |
| 69 | Supply and fixing of PVC Exhaust Fan 200 mm with lovour complete all as specified and as directed. |
| 70 | Supply and fix PCB Circuit Controller board for BLDC Ceiling fans of 1200 mm sweep speed not less than 380 RPM Suitable for existing make complete all as specified and directed including dismantling, fault diagnosis, replacement of PCB k, cleaning, functional testing, refitting, trial run restoration of all associated indications/alarms complete as per site requirement |
| 71 | Taking out burnt/damaged copper winding wire of 1200/1400mm Sweep ceiling fan motor of any make and M&L for rewinding of ceiling fans motor of any make with super enameled copper winding wire of appropriate size/same gauge as original including ,soldering, varnishing , ball bearing, push, locking pin and certain minor repair along with minor repair/replacement work-as-such Rubber rill,louring pin,flexible wire from ceiling rose to ceiling fan etc and assembling and testing and refixing of same places complete all as specified. |
| 72 | Taking out burnt/damaged copper winding of Exhaust fan 400mm motor of any make and M&L for rewinding of wall mounted fans motor of any make with super enameled copper winding wire of appropriate size/same gauge as original, including packing insulating material, soldering, varnishing, including painting etc and certain minor repair such as such as flexible wire/cord oiling greasing etc complete all as specified. |
| 73 | Taking out burnt/damaged copper winding of Wall mounted fan 400/600 mm motor of any make and M&L for rewinding of wall mounted fans motor of any make with super enameled copper winding wire of appropriate size/same gauge as original including insulating, soldering, varnishing, etc such as flexible wire /cord/oiling greasing etc certain complete all as specified. |
| 74 | Taking out taking down refixing burnt/damaged wire of pedestal fan any size motor of any make and M&L for rewinding of fans motor of any make with super enameled copper winding wire of appropriate size/same gauge as original including packing insulating , soldering, varnishing, assembling and testing and refixing of same places complete all as specified. |
| 75 | Taking out burnt/damaged wire of exhaust fan 200 to300 mm motor of any make and M&L for rewinding of fans motor of any make with super enameled copper winding wire of appropriate size/same gauge as original including insulating , soldering, varnishing, assembling and testing including taking down and refixing using etc of same places complete all as specified. all as specified. |
| 76 | Taking out burnt/damaged wire from exhaust fan motor of 400 to 450 and M&L for rewinding of with super enameled copper winding wire of same size, gauge & weight including packing insulating material, soldering, varnishing, including painting and certain minor repair such as flexible wire/cord oiling, greasing etc assembling and testing including refixing using fastener etc. complete all as specified varnishing & insulating complete and refixing of same places complete all as specified and directed. |
| 77 | Taking down dismantling UNSV/Rusted fatal/damaged Exhaust Fan MS / iron body of any size and any make and repairing the following items of existing sizes. |
| 78 | Exhaust Fan motor suitable for 400 to 450 mm |
| 79 | Exhaust fan frame with nut bolts etc size 400to 450 mm sweep |
| 80 | Exhaust fan Louver iron shutter for size 400 to 450mm sweep along with fixing arrangement |
| 81 | Exhaust Fan motor suitable for 250 to 300 mm |
| 82 | Exhaust fan frame with nut bolts etc size 200to 300 mm sweep |
| 83 | Exhaust fan Louver iron shutter for size 250 to 300mm sweep along with fixing arrangement |
| 84 | Taking down dismantling UNSV/Rusted fatal/damaged Wall mounted Fan from of any size and any make and repairing the following items of existing sizes. |
| 85 | Wall mounted Fan motor suitable for 450 mm |
| 86 | Wall mounted Fan winds (sweep) for 450 mm set etc size |
| 87 | Wall mounted fan canopy set of one suitable for existing fan. |
| 88 | Wall mounted fan stand( base) suitable 450mm fan. |
| 89 | Wall mounted fan fixing arrangement/hook with nuts bolts /locking pin system |
| 90 | Taking down dismantling UNSV/Rusted fatal/damaged Ceiling Fan from of any size and any make and repairing the following items of existing sizes. |
| 91 | Ceiling Fan motor suitable for 1200 mm |
| 92 | Ceiling fan winds(sweep)1200mm set etc size |
| 93 | Ceiling fan canopy set of two suitable for existing fan. |
| 94 | Ceiling fan down rod suitable 1200mm ceiling fan. |
| 95 | Ceiling fan fixing arrangement/hook with nuts bolts /locking pin system |
| 96 | Supply and fixing of Standard ball bearing for suitable 1200/1400 mm ceiling fan suitable for different makes of fans of approved quality including necessary |
| 97 | S&F in repairs down rod 30 cms long made out of heavy grade M.S pipe with necessary threading at both ends, holes as required matching with existing & painting for size of ceiling fan 1200mm/1400 mm as all directed by Engineer-in-Charge.Make :- As per Site |
| 98 | S&F in repairs down rod 60 cms long made out of heavy grade M.S pipe with necessary threading at both ends, holes as required matching with existing & painting for size of ceiling fan 1200mm/1400 mm as all directed by Engineer-in-Charge.Make :- As per site |
| 99 | S&F in repairs rubber bushes and real synthetic rubber with 14.5 mm hole suitable for fan hooks for hanging of ceiling fans all directed by Engineer-in-Charge. |
| 100 | S&F in replacement condenser/capacitor suitable for 230 volts single phase for ceiling fan/exhaust fan/cabin fan/pedestal fan of capacity 2.5 mfd ISI mark including necessary connection complete all as specified. |
| 101 | S&F in replacement condenser/capacitor suitable for 230 volts single phase for ceiling fan/exhaust fan/cabin fan/pedestal fan of capacity 3.15 mfd ISI mark including necessary connection complete all as specified. |
| 102 | S&F in replacement condenser/capacitor suitable for 230 volts single phase for ceiling fan/exhaust fan/cabin fan/pedestal fan of capacity 4 mfd ISI mark including necessary connection complete all as specified. |
| 103 | Cutting of existing wall and fixing of Exhaust fan total making good plaster and white wash and suitable size of 04 Number fastener and fixing of any type exhaust fan complete all as specified and as directed . |
| 104 | Taking down geysers of any type and any capacity due to rusting of bolts/seepage of wall and re-installation at any location including S&F in repairs of heavy duty pin type fastener 4” long and making necessary inlet/outlet electric & water supply connections from existing source to geyser complete all as specified and as directed. |
| 105 | S&F in repairs heating element, cup (round) type, 1.5 KW 230 volts, ISI marked suitable for 25/50 ltrs geysers of any make complete all as specified and as directed. Make : As per Site |
| 106 | Description all as per serial item No.62 here-in-before but in tikona typeMake :As per Site |
| 107 | S&F in repairs heating element, cup (round) type, 2.00 KW 230 volts, ISI marked suitable for 25/50 ltrs geysers of any make complete all as specified and as directed. Make :As per site |
| 108 | Description all as per serial item No.64 here-in-before but in tikona typeMake : As per Site |
| 109 | S&F in repairs 7 \\" thermostat switch for geysers of 25/50 ltrs capacity (ISI marked) complete all as specified and as directed. |
| 110 | S&F in repairs 11\\" thermostat switch for geysers of 25/50 ltrs capacity (ISI marked) complete all as specified and as directed. |
| 111 | S&F in repairs inner stainless-steel inner tank of 20 gauge sheet rated pressure not less than 8kg/sqcm suitable for 25 ltrs capacity geysers complete all as specified and as directed. |
| 112 | S&F in repairs plug top 3 pin 15 Amp ISI marked complete all as specified and as directed. Make :As per site . |
| 113 | Taking down UNSV/ Rushed / fatal hot water geyser capacity 25 Ltrs / 50 Ltrs from OTM / Mess / Accn etc of any make and repairing / Installation at same location: replacement of spare parts will be paid separately |
| 114 | Base plate with indicator red and green suitable for cap-50 Ltrs |
| 115 | Base plate with indicator red and green suitable for Cap-25 Ltrs |
| 116 | S&F in repair base 09/06 Nuts assembly, compatible to existing geyser, with inlet and thermostat pipe with drain plug inclusive of clamps for holding the element with nuts, bolts and gasket complete all as specified and as directed. |
| 117 | S&F in repairs brass non-return valve 15 mm bore ISI marked screwed both ends and connecting to iron pipe in repairs complete all as specified and as directed. |
| 118 | S&F in repairs pressure safety value confirming to relevant IS with washer suitable for 15 mm GI pipe suitable for 25/50 ltrs geysers complete all as specified and as directed. |
| 119 | S&F in repair of GI tubing medium grade of size 25mm bore ISI marked galvanized with all fittings such as bends, elbows, tees, check nuts, unions nipples etc for cold water pipe line complete all as specified and as directed. |
| 120 | Description all as per item No 76 here-in-before but 20mm bore. |
| 121 | Description all as per item No 76 here-in-before but 15mm bore. |
| 122 | Supply only PVC connection pipes inner wiremesh type 15mm size of length 450mm hot and cold with both ended brass flare nuts for geyser connection. |
| 123 | Supply and fixing of Plug type bib taps, cast iron, screwed for iron pipe and fixed of size 15/20 mm bore dia |
| 124 | Stop valves/angle vale 15mm , cast copper alloy, screwed down, high pressure,with crutch or butterfly handle, screwed both ends for iron pipe or for unions and fixed |
| 125 | M&L in repair plastic type DBs SPN 2 way flush mounted including accessories therein and disposing off complete all as specified and directed. |
| 126 | Supply and fix in repair of 15 Amps switch socket combination including Box complete all as specified and as directed |
| 127 | Supply and fix in repairs of MCCB 3P 25 to 100 Amps /415Volts ,having breaking capacity with complete accessories as per existing suitable size complete all as specified and as directed |
| 128 | Supply and fix in repairs of MCCB 3P 160 Amps /415Volts ,having breaking capacity with Complete accessories as per existing suitable size complete all as specified and as directed |
| 129 | Supply and fix in repairs of MCCB 4P 63 Amps /415Volts ,having breaking capacity with complete accessories as per existing suitable size complete all as specified and as directed |
| 130 | Supply and fix in repairs of MCCB 4P 100 Amps /415Volts ,having breaking capacity with Complete accessories as per existing suitable size complete all as specified and as directed |
| 131 | Material and labour for earthing complete with galvanised steel earth plate electrode 600mm x 600mm x 6mm thick buried directly in ground (earth pit not less than 2.25metre deep below natural ground level) with top edge of the plate not less than 1.5metre below normal ground level, connected to galvanised earth lead wire 4mm dia by means of bolts, nuts, check nuts and washers of galvanized iron or steel connected to main switch board/ main DB’s/ earth test point with and including necessary excavation and earth work in any type of strata, PCC 1:3:6, type C1 in chamber wall with 50mm thick, RCC cover 1:2:4, type B0 duly reinforced with 6 mm dia bar, @100mm both way with suitable lifting handle, charcoal dust and common salt mixed and packed in 150mm thick layer all around the earth plate, watering pipe of size 20mm dia medium grade, 0.63mm thick GI sheet funnel with wire mesh, GI protection pipe 15mm dia light grade up to 7.5m from electrode and engraving of earth marking on nearby structure/ building with cement motor 1:4 plate of size 200mm x 150mm x 15mm thick and writing of earth results with paint complete all as shown in electrical plate No. 5 of SSR Part-I complete all as specified and as directed. Note: - On testing if desired earth resistance is not obtained, the earthing will be redone at no extra cost. |
| 132 | Material and labour for earth continuity conductor or main earthing lead 4 mm dia GI or steel wire fixed to wall on batten or recessed or buried in ground or drawn in conduit/ pipe all as required at site complete all as specified and as directed. Please Enable Macros to View BoQ information |