| 1 | Taking down existing defective LT under ground cable of any size from trenches complete all as directed |
| 2 | S&F 80 mm bore tubing 'light grade' galvanised iron with all fittings and fixed to poles, walls etc. with flat iron clamps/ bolts/ nuts/ washers or laid in floors/under roads complete all as specified and directed. |
| 3 | All as item No-2 above but 50 mm bore |
| 4 | All as item No-2 above but 40 mm bore |
| 5 | Supply, Laying, jointing and testing in replacement of LT underground cable, heavy duty, 1100 Volts, XLPE insulated and sheathed, armoured with multi-stranded aluminium conductor cable, laid in trenches/ducts or fixed to poles / walls or laid under roads/ paths/ drains/ culverts duly encased in galvanised steel pipe of suitable sizes including cable gland of suitable sizes and aluminium lugs for connection complete all as specified and directed of following size:- |
| 6 | 3.5 core120 sqmm |
| 7 | 3.5 core 70 sqmm |
| 8 | 3.5 core 50 sqmm |
| 9 | 3.5 core 25 sqmm |
| 10 | 4 core 25 sqmm |
| 11 | 4 core 16 sqmm |
| 12 | Excavation in trenches n. exc. 1.5 mtr in wide and n. exc. 1.5 mtr in depth for laying of underground cable and getting out in soft/loose soil complete all as specified and directed. |
| 13 | Supply & lay in trenches double walled corugated HDPE pipe 75 mm dia high density for protection of under ground cables( Note: pipe couplers with seal, bends, end covers etc are deemed to be included in rate quoted) |
| 14 | Supply & lay in trenches double walled corugated HDPE pipe 50 mm dia high density for protection of under ground cables( Note: pipe couplers with seal, bends, end covers etc are deemed to be included in rate quoted) |
| 15 | Returning, filling in excavated soil in trenches including spreading, leveling, watering and well ramming in layers n. exc. 25 cm thick complete all as specified and directed |
| 16 | Removing of excavted soil to a distance n. exc. 50 mtr and deposited where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed. |
| 17 | Supply and fix , test , commissioning of LT weather proof panel board powder coated out door type double door shutter type made out of CRCA 3.15 mm thick outer and 1.6 mm thick for inner door confirming to IS 8623 with angle iron 50x50x6 mm outdoor, floor mounting type with closed bus bar, chamber and with aluminium bus bar with necessary insulator suitable for 3 phase, 4 wire 50 Hz AC supply as per CPRI approved including provn of digital ammeter 0-500A, digital voltmeter 0-500Volts, CT's of suitable ratio, indicator lamps R-Y-B,selector switches and internal wiring including making PCC block type 0.6 Mtr above ground level grouting etc all as specified and directed with the following Work also includes provision of suitable size of cable glands, cable lugs, nut, bolts, washers etc (The bottom portion of enclosure shall be minimum 40 cm above ground level. legs & depth of the panel should not be less than 45cm).Legs of angle iron should be 100 cm lenth (60 cm below ground and 40 cm above the eground) a) Aluminium bus bar of capacity 400 Amps for Phase-R-Y-B & 200 Amps for neutral -1 No b) MCCB 4 Pole 36 KA , 250 Amp - 1 No (I/C) c) MCCB 4 Pole 25 KA, 125 Amp - 4 Nos (O/G) |
| 18 | All as item No 11 above but with following accessories:- a) Aluminium bus bar of capacity 600 Amps for Phase-R-Y-B & 200 Amps for neutral -1 No b) MCCB 4 Pole 36 KA 400 Amp - 1 No (I/C)c) MCCB 4 Pole 25 KA 250 Amp - 2 Nos (O/G)d) MCCB 4 Pole 25 KA 125 Amp - 1 Nos (O/G) |
| 19 | All as item No 11 above but with following accessories:- a) Aluminium bus bar of capacity 300 Amps for Phase-R-Y-B & 200 Amps for neutral -1 No b) MCCB 4 Pole 36 KA 160 Amp - 1 No (I/C)c) MCCB 4 Pole 18 KA 63 Amp - 3 Nos (O/G) |
| 20 | All as item No 11 above but with following accessories:- a) Aluminium bus bar of capacity 400 Amps for Phase-R-Y-B & 200 Amps for neutral -1 No b) MCCB 4 Pole 36 KA 250 Amp - 1 No (I/C)c) MCCB 4 Pole 25 KA 160 Amp - 2 No (O/G) d)MCCB 4 pole 25 KA 125 Amp -1 No (O/G)e) MCCB 4 Pole 18 KA 63 Amp - 3 Nos (O/G) |
| 21 | All as item No 11 above but with following accessories:- a) Aluminium bus bar of capacity 400 Amps for Phase-R-Y-B & 200 Amps for neutral -1 No b) MCCB 4 Pole 36 KA 250 Amp - 1 No (I/C)c) MCCB 4 Pole 25 KA 125 Amp - 3 No (O/G)d) MCCB 4 Pole 18 KA 63 Amp - 2 Nos (O/G) |
| 22 | All as item No 11 above but with following accessories:- a) Aluminium bus bar of capacity 300 Amps for Phase-R-Y-B & 200 Amps for neutral -1 No b) MCCB 4 Pole 36 KA 200 Amp - 1 No (I/C)c) MCCB 4 Pole 25 KA 125 Amp - 1 No (O/G)d) MCCB 4 Pole 18 KA 63 Amp - 3 Nos (O/G) |
| 23 | All as item No 11 above but with following accessories:- a) Aluminium bus bar of capacity 600 Amps for Phase-R-Y-B & 200 Amps for neutral -1 No b) MCCB 4 Pole 36 KA 400 Amp - 1 No (I/C)c) MCCB 4 Pole 25 KA 125 Amp - 3 No (O/G)d) MCCB 4 Pole 36 KA 125 Amp - 3 Nos (O/G) |
| 24 | All as item No 11 above but with following accessories:- a) Aluminium bus bar of capacity 600 Amps for Phase-R-Y-B & 200 Amps for neutral -1 No b) MCCB 4 Pole 36 KA 400 Amp - 1 No (I/C)c) MCCB 4 Pole 25 KA 250 Amp - 2 Nos (O/G)d) MCCB 4 Pole 25 KA 200 Amp - 1 Nos (O/G) |
| 25 | All as item No 11 above but with following accessories:- a) Aluminium bus bar of capacity 400 Amps for Phase-R-Y-B & 200 Amps for neutral -1 No b) MCCB 4 Pole 36 KA 250 Amp - 1 No (I/C)c) MCCB 4 Pole 25 KA 125 Amp - 6 Nos (O/G) |
| 26 | All as item No 11 above but with following accessories:- a) Aluminium bus bar of capacity 400 Amps for Phase-R-Y-B & 200 Amps for neutral -1 No b) MCCB 4 Pole 36 KA 250 Amp - 1 No (I/C)c) MCCB 4 Pole 18 KA 100 Amp - 7 Nos (O/G) |
| 27 | All as item No 11 above but with following accessories:- a) Aluminium bus bar of capacity 300 Amps for Phase-R-Y-B & 200 Amps for neutral -1 No b) MCCB 4 Pole 36 KA 200 Amp - 1 No (I/C)c) MCCB 4 Pole 25 KA 125 Amp - 4 Nos (O/G)d) MCCB 4 Pole 18 KA 100 Amp - 2 Nos (O/G) |
| 28 | All as item No 11 above but with following accessories:- a) Aluminium bus bar of capacity 300 Amps for Phase-R-Y-B & 200 Amps for neutral -1 No b) MCCB 4 Pole 36 KA 200 Amp - 1 No (I/C)c) MCCB 4 Pole 25 KA 125 Amp - 3 Nos (O/G)d) MCCB 4 Pole 18 KA 100 Amp - 1 Nos (O/G) |
| 29 | All as item No 11 above but with following accessories:- a) Aluminium bus bar of capacity 300 Amps for Phase-R-Y-B & 200 Amps for neutral -1 No b) MCCB 4 Pole 36 KA 200 Amp - 1 No (I/C)c) MCCB 4 Pole 18 KA 63 Amp - 3 Nos (O/G) |
| 30 | All as item No 66 above but with following accessories:- a) Aluminium bus bar of capacity 200 Amps for Phase-R-Y-B & 100 Amps for neutral -1 Nob) MCCB 4 Pole 25 KA , 160 Amp - 1 No (I/C)c) MCCB TPN 63 Amp ,10 KA - 1 Nosd) MCB TPN 63 Amps-04 e) Astro time switch ( AUTS02AST00 of L&T) suitable for street light control and with 40 Amps ,440 volt coil voltage MNX- 40 contactor ( L&T) 3Ph phase- 0 1 Set |
| 31 | Cutting through existing bituminous road / PCC / floor/ approx size width 50cm X 60cm depth along cross section of the road for laying of GI tubing/RCC pipe for encasing of cable and repairing the road to match with the original finish complete all as specified. |
| 32 | \\"M&L earthing GI Strip complete with galvanized steel plate electrode 600 mm x 600 mm x 6.0 mm thick, burried directly in ground vertically in pit of depth not less than 2.25 metre below normal ground level with top edge of the earth plate at a depth not less than 1.5 metre below normal ground level surrounded from all sides with mixture of charcoal and common salt in alternate layers and electrode connected to galvanized iron strip 32 x 6 mm size by means of GI bolts, nuts, check nuts and washers, earth strip protected by galvanized steel pipe 40 mm bore (light grade) connected to main switch board or any other electrical equipment all as shown in electrical plate No. 3 of SSR-2009 Part I and including necessary excavation and earth work in any type of strata, 20 mm bore medium grade GI pipe for watering, funnel with wire mesh, PCC (1:3:6), type C-1 chamber, RCC (1:2:4), type B-1, reinforced with 6 mm dia MS round bars @ 15 cm c/c both way for cover and MS frame etc., complete all as specified. |
| 33 | M&L for making underground boaring (Manually/Mech) through existing bituminous road/PCC/Floor along cross section approx 10 mtr of the road at a depth approx 1.0 mtr for laying of GI tubing of dia 80/100 mm for encasing of cable all as specified and directed at site. |
| 34 | Supply and install Air conditioner 2.0 ton hi wall split units indoor/outdoor complete with cordless remote control unit and with in built air ioniser and Plasma filter for better indoor air quality with minimum 3 star rating |
| 35 | M & L for sub main wiring with 2 single core, 4 Sq. mm, PVC insulated unsheathed, multi stranded copper conductor FRLS cable 1100 Volts grade incl 2.5 Sqmm PVC insulated unsheathed multi stranded copper conductor FRLS as continuous earth wire and connecting to common earth terminals complete all as specified and directed in conduits/ PVC capping- casing. Note :-(i) Two run of copper cable and one run of earth wire shall be measured as one length. (ii)Rate of casing-capping/ conduit deemed to be included in rate quoted. |
| 36 | S & F Plug & socket enclosure in sheet metal enclosure with 20A SP MCB complete all as specified and as directed. |
| 37 | Supply and fix in repair sheet metal enclosure DBs SPN, 4 Ways, 240V with 200 Amps rated bus bars double door complete all as specified and as directed. |
| 38 | Supply and fix in replacement MCB SP 6 to 32 Amps, 240 volts complete all as specified and as directed. |
| 39 | Supply and fix in replacement MCB SPN 32 Amps, 240 volts complete all as specified and as directed. |
| 40 | Supply and fixing in repair PVC insulated flexible cable 3 core with multistranded copper conductors round shaped sheathed for 1100 volts grade of size 4.00 Sqmm |
| 41 | Supply and fix in repair Air Conditioner Copper Pipe of Size: 2\\"-3\\" suitable for 1.5/2.0 Ton split Air conditioner |
| 42 | Supply and fix stand/ mounting bracket metal body fully poweder coated factory made for outer unit of split AC of capacity 2.0 TR |
| 43 | Supply & installation 15 meter high galvanized mast light suitable for 6 to 9 lanternsymmetrically fitted alongwith their control gear and having two point suspension system with stainless steel wire rope of 6 mm dia 97/19 guage and double drum winch with luminaire mounting arm, pully assembly, aviation obstruction light, lightning arrester spike, flexible copper wire including RCC foundation as per height |
| 44 | Supply and fixing LED flood light 200/210 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp |
| 45 | Earthing complete with galvanised steel earth plate electrode 60cm×60cmx. 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below groundlevel) with top edge of the plate not less'than 1.5 metres below normal ground level, connected to galvanised earth lead wire 4.0mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion |
| 46 | Supply and fix, test, commissioning of LT weather proof panel board powder coated in door type double door shutter, out door type made out of CRCA 3 mm thick outer and 1.6 mm thick for inner door confirming to IS 8623 with angle iron 50x50x6 mm outoor, floor mounting type with closed bus bar, chamber and with Copper bus bar of cap 200 Amp with necessary insulator suitable for 3 phase, 4 wire 50 Hz AC supply as per CPRI approved including provn of digitalammeter 0-500A, digital voltemeter 0-500Volts, CT's of suitable ratio, indicator lamps R-Y- B.selector switches and internal wiring including making PCC block type 0.6 Mtr above ground level grouting etc all as specified and directed with the following Work also includes provision of suitable minimum 60 cm above ground level of legs of angle iron) size of cable glands, cable lugs,nut, bolts, washers etc. The bottom portion of enclosure shall beshall be minimum 60 cm above ground level of legs of angle iron a) Copper bus bar capacity 200 Amps for Phase-R-Y-B-3 Nos & 100 Amps for neutral -1 Nob) MCCB 4 Pole 100 Amps 25 KA - 1 No (I/C) c) MCB TPN 63 Amp, 10 KA-01 No(O/G)d)MCB TPN 32 Amp, 10 KA-01 No(O/G)e)TIME Swith daily dial type FM 1/ Quartz daily 240 V din mounting Make L&Tf) Contactor 40 A, 3 pole, MNX 40 make L&T |
| 47 | Note: Amount of sch of credit of Rs.42320/-will be deducted from total amount of BOQ. Please Enable Macros to View BoQ information |