| 1 | Providing and making steel pole collar with cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) of specified size and shape including form work, plastering if required, curing etc. as required. (Volume of pipe/pole not to be deducted)(Electrical DSR-14/Ite. No. 11.5 pg.37) |
| 2 | S/F of sintex type junction box model no. IIGSJB 2817 of size 240x130x110mm with hinges and locking arrangment & MS clamp of 50x6mm flat, complete in all respects including 2 no. G.I pipe 1.5\\" dia having 1.0 meter length each and chuck nut for cable connection etc. as per direction of E/I. (AOR) |
| 3 | Numbering of Pole/GI post / feeder pillar with combination of yellow and black colour paint etc. complte in all respects as per direction of E/I. (AOR) |
| 4 | Supplying and laying of aluminium conductor PVC insulated armoured, served, sheathed cable 1100 Volts grade at a depth of 750 mm. below ground level over a cushion of 75 mm. thick sand alround and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. Clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respects. the armouring of the cable shall be properly connected with the earth conductor by clamps etc. (KEI/Havells/ Polycab make) (PS No 501) |
| 5 | 1) 16sq mm 4 core |
| 6 | 2) 35 sq mm 3.5 core |
| 7 | S/F of Plain of pin type copper tin plated cable socket(lug) to the cable leads, insulating with tape and making connection etc. Complete in all respects as per direction for E/I (PS No. 504) |
| 8 | 1) 35 Sq.mm. |
| 9 | 2) 25 Sq.mm. |
| 10 | 4) 16 sq. mm |
| 11 | Supply and fixing of 25 Amp TPN capacity of automatic street light cubical control panel painted with anti corrosive alkali and acid proof paint crossing of time switch TSO 100 series with contractors, HRC fuse, isolating swtich metering instrument & instrument box with CTs etc. in case of TPN, Complete in all respects. as per PS No. 807E |
| 12 | Dismantling of pole/Street Light standard /strut embedded in cement concrete foundation etc. as required (DSR-2018/item no. 12.42 P-46) |
| 13 | Hiring of welding set charges running time @ 6 hrs .10.01.07 N.S.I Jal |
| 14 | Hiring of Gas cutter set with oxygen and LPG running time 6 hrs. 10.01.06 N.S.I Jal |
| 15 | Supplying and Laying of 6 sq. mm 2 core PVC Insulated Al. moued cable for street Light pole (as per RESPO-2018) annexure -3 pg. 17. |
| 16 | Supply , Installation , testing and commissioning of standard 4.0 Mtr. High (above ground) hot dip galvanized (grading of galvenisation average 70 micron or better as per IS 2629 or equivalent) Octagonal pole, with stiffener, chain, allen bolt, foundation, single arm bracket, template, nut and bolts galvanized, factory finish base plate of size 200x200x12mm etc complete as required. The pole shall be made of 3mm thickness sheet with tolerance of +/- 5%. The column shall also be provided with flush door at the bottom with proper strengthening to the cutout of the door opening, a junction/loop box with heavy duty 3 phase , 32 Amp. connector with 16A DP MCB including all accessories complete as required derected by E/I.(Make -Bajaj/Transrail/volmont) |
| 17 | S/Laying of 90 mm dia (OD 90 mm & ID 76 mm nominal) size of (DWC) HDPE Pipes ISI marked along wigh all accessories like socket, bend, couplers etc. conforming to IS 14930, Part-II complete with filling and cutting, jointing etc. direct in ground ( 75 cm below ground level) including excavation and refilling the trench pat excluding sand cushioning and protective covering etc. Complete in all respects. Rex/Duraline/Time/CPE make. as per DSR 2018 item no. 14.16.2 page no. 49 |
| 18 | S/E of overhead line with ACSR conductor on steel tubular poles incl. compression joint, laying stringing and binding etc. as PS No. 627 |
| 19 | Painting of the electric pole with 2 Coats of aluminium paint over red oxide primer complete in all respects. P.S. No. 634 |
| 20 | Supply and burying of 600 mm x 600 mm x 6.0 mm GI plate, vertically for eathing with its top at least 3 meters below ground level complete with 20 mm dia. GI Pipe and funnel for watering and one earthing lead of one no. 8 to 10 SWG GI wire in 15 mm. dia. GI Pipe up to switch board 30 cm. square CI Frame with hinged cover, masonry housing, alternate layers of charcoal/coke and salt at least 150 mm. thick alround etc. as per direction of Engineer-in-charge complete in all respects . PS No. 702 |
| 21 | Demolishing cement concrete manually/ by mechanical means including disposal of material with in 50 Mtr. Lead as per direction of E/I. Nominal concrete 1:3:6 or richer mix(i/c equivalent design mix) (AOR) P- |
| 22 | Earth work in excavation by mechanical means (Hydraulic excavator) / manual means over areas (exceeding 30cm in depth. 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth, lead upto 50m and lift upto 1.5m. The contractor has detect different utilities like sewer line, water supply line, electric cable, Telephone cable, Gas pipe line etc. using utility detecting machine before start of excavatiob and shall start excavation only after permission of Engineer in charge. All kind of soil. (136.0 + 18% GST) (AOR) |
| 23 | Filling available excavated earth( excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20 cm in depth consolidating each deposited layer by ramming & watering, lead upto 50 m and lift upto 1.5 m. (AOR) |
| 24 | Supply and making straight through joint with cast resin compound including ferrules and other joints material for following size of PVC insulated and PVC sheathed/XLPE aluminium conductor cable of 1.1 KV grade as required |
| 25 | a) 2x16 sq. mm ((Electrical DSR-18/Item. No. 9.3.2 pg.36) Please Enable Macros to View BoQ information |