| 1 | Excavating in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth for foundation etc for laying of cables, erection of poles, struts/ stays etc not exceeding 10 sqm on plan and getting out in soft loose soil complete all as specified and directed. |
| 2 | Returning, filling in, including spreading leveling watering and well ramming in layers not exceeding 25 cm in any type of soil complete all as specified and directed. |
| 3 | Removing excavated materials to a distance not exceeding 50 m and depositing where directed, at a level not exceeding 1.5 m above the starting point in soils complete all as specified and directed. |
| 4 | M & L for sand filling in trenches for cushioning of LT cables punning after filling complete as specified and as directed.Note: Punned thickness shall only be measured and paid |
| 5 | Supply and lay un-reinforced precast concrete cable cover , class , LV , Type I flat size 250 x 150 x 40 mm laid dry in treches over under ground cables complete all as specified and directed. |
| 6 | S & F GI pipe, light grade, of size 80 mm dia including necessary fittings laid in trenches/fixed on wall/pole for LT cable protection and taking down the old GI pipe for cable protection, complete all as speicifed and directed. |
| 7 | S & F GI pipe, light grade, of size 100 mm dia including necessary fittings laid in trenches/fixed on wall/pole for LT cable protection and taking down the old GI pipe, for cable protection, complete all as speicifed and directed. |
| 8 | Dismantaling of any type and size ACSR conductor complete all as specified and directed. |
| 9 | Dismantaling of stay assembly including demolation of concrete etc complete all as specified and directed. |
| 10 | Dismantaling of insulator any size and any type complete all as specified and directed by Engr-in-Charge. |
| 11 | Dismantaling of cross arm of MS chanel or angle sections any type any size etc complete all as specified and directed. |
| 12 | Disconnecting, taking out, removing old existing unserviceable LT cable overhead service cable of any size etc complete all as specified and directed. |
| 13 | Supplying ,Laying , jointing and testing XLPE insulated, armoured, heavy duty, LT aluminum conductor cable 1100 volts grade of size 4 core 16 Sqmm laid in trenches/ducts, floors, fixed to walls etc complete all as specified and directed. |
| 14 | - ditto- here in before Item 13 but of size 2C core 10 Sqmm complete all as specified and directed. |
| 15 | - ditto- here in before Item 13 but of size 4C core 25 Sqmm complete all as specified and directed. |
| 16 | - ditto- here in before Item 13 but of size 3.5C core 35 Sqmm complete all as specified and directed. |
| 17 | - ditto- here in before Item 13 but of size 3.5C core 50 Sqmm complete all as specified and directed. |
| 18 | - ditto- here in before Item 13 but of size 3.5C core 70 Sqmm complete all as specified and directed. |
| 19 | - ditto- here in before Item 13 but of size 3.5 core 95 Sqmm complete all as specified and directed. |
| 20 | - ditto- here in before Item 13 but of size 3.5 core 120 Sqmm complete all as specified and directed. |
| 21 | - ditto- here in before Item 13 but of size 3.5 core 185 Sqmm complete all as specified and directed. |
| 22 | - ditto- here in before Item 13 but of size 3.5 core 240 Sqmm complete all as specified and directed. |
| 23 | Supply, installation, testing and commissioning weather and vermin proof L.T. feeder pillar box CPRI approved factory fabricated out door,double door cubicle/KIOSK type totally enclosed outer cage made out of 3.15 mm thick sheet metal and inner compartments of 2.0 mm thick sheet metal enclosure with angle iron frame of M.S. angle 50x50x6 mm with height not less than 0.8 meter, suitable for operation on 3 phase 4 wire, 440 volts 50 HZ system, IP 65 , Gasket insulators, fasteners etc with hinged panel doors (covers) on two sides with handles , bottom gland plate and locking arrangement with latch door mechanism, consisting of sufficient Nos of circular cable entry holes at bottom only with suitable PVC/rubber /wooden bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper busbar or conductor PVC insulated cables of adequate size, duly powder coated internally/ externally of approved colour with PCC foundation and suitable capacity busbar , Air vent , PCC foundation 1:2:4 for foundation etc comprising for the following :-Location: MLI pump house main LT panel |
| 24 | (a) Copper Bus bar, 750amps of size 40x10mm complete all as specified and directed. |
| 25 | (b) MCCB 4 Pole thermal magnetic release 415 volts 500 A 36 KA,Ics=100%Icu -01(incoming), complete all as specified and directed. |
| 26 | (c)MCCB 4 pole thermal magnetic release 400 A, 36 KA,Ics=100%Icu -02 Nos ( LT Panel 2 +spare ) complete all as specified and directed. |
| 27 | (c)MCCB 4 pole thermal magnetic release 250 A, 36 KA,Ics=100%Icu , -01 nos ( LT Panel 1 ) complete all as specified and directed. |
| 28 | (d) MCCB 4 pole thermal magnetic release 160 A, 36 KA ,Ics=100%Icu -01 (MLI pump house) complete all as specified and directed. |
| 29 | (e) MCCB 4 pole thermal magnetic release 63 A, 16 KA ,Ics=100%Icu ,-02 nos (MI room, mandir, store-2 nos,LT Panel 5) complete all as specified and directed. |
| 30 | (f) Digital street light timer with TPN MCB of 32A , 40A contactor, and all connected items all as specfied and directed. |
| 31 | (g) Voltmeter digital type 0-500 V with inbuilt selector switch-01 No complete all as specified and directed. |
| 32 | (h) Ammeter digital type 0-500 A with in built selector switch and CTs-01 No complete all as specified and directed. |
| 33 | (i) 3 Line multifunctional meter-01(Nos) complete all as specified and directed. |
| 34 | All as per item no 23 here in before but LT Panel consisting of following items (MLI pump house to LT Panel 1 near Adm block) complete all as specified and directed. |
| 35 | (a) copper Bus bar,400amps of size 40x5mm complete all as specified and directed. |
| 36 | (b) MCCB 4 Pole thermal magnetic release 415 volts 250 A 36 KA,Ics=100%Icu ,Adjustable overload settings:0.8-1×In, Adjustable shortcircuit settings: 6-10×In -01(incoming), complete all as specified and directed. |
| 37 | (c)MCCB 4 pole thermal magnetic release 415 Volts 160 A, 36 KA, Ics=100%Icu ,Adjustable overload settings:0.8-1×In, Adjustable shortcircuit settings: 6-10×In -02 (Adm bldg +Spare) complete all as specified and directed. |
| 38 | (e)MCCB 4 pole thermal magnetic release 415 Volts 63 A, 16 KA, Ics=100%Icu ,Adjustable overload settings:0.8-1×In, Adjustable shortcircuit settings: 6-10×In -03( OR line,1,2 &3) complete all as specified and directed. |
| 39 | (f)MCCB 4 pole thermal magnetic release 415 Volts 40A, 16 KA, Ics=100%Icu ,Adjustable overload settings:0.8-1×In, Adjustable shortcircuit settings: 6-10×In -02( samll store, sentry) complete all as specified and directed. |
| 40 | (g) Indicating lamps ( LED type) ( R-Y-B) -01 (Set of three) complete all as specified and directed. |
| 41 | (h) Voltmeter ammeter digital type 0-500 V with inbuilt selector switch-01 No complete all as specified and directed. |
| 42 | (j) 3 Line multifunctional meter-01(Nos) complete all as specified and directed. |
| 43 | All as per item no 23 here in before but LT Panel consisting of following items (LT Panel 2 near OR Line HQ) complete all as specified and directed. |
| 44 | (a) Copper Bus bar 600 amps of size 40x8mm complete all as specified and directed. |
| 45 | (b) MCCB 4 Pole thermal magnetic release 415 volts 400 A 36 KA,Ics=100%Icu ,Adjustable overload settings:0.8-1×In, Adjustable shortcircuit settings: 6-10×In -01(incoming), complete all as specified and directed. |
| 46 | (c) MCCB 4 Pole thermal magnetic release 415 volts 250 A 36 KA,Ics=100%Icu ,Adjustable overload settings:0.8-1×In, Adjustable shortcircuit settings: 6-10×In -02(LT Panel 3&4), complete all as specified and directed. |
| 47 | (d)MCCB 4 pole thermal magnetic release 415 Volts 100 A, 16 KA, Ics=100%Icu ,Adjustable overload settings:0.8-1×In, Adjustable shortcircuit settings: 6-10×In -01 (Qtr Guard ) complete all as specified and directed. |
| 48 | (e)MCCB 4 pole thermal magnetic release 415 Volts 63 A, 16 KA, Ics=100%Icu ,Adjustable overload settings:0.8-1×In, Adjustable shortcircuit settings: 6-10×In -04 (OR LINE HQ,SP,JCO Living & Shelter ) complete all as specified and directed. |
| 49 | (g) Indicating lamps ( LED type) ( R-Y-B) -01 (Set of three) complete all as specified and directed. |
| 50 | (h) Voltmeter digital type 0-500 V with inbuilt selector switch-01 No complete all as specified and directed. |
| 51 | (i) Ammeter digital type 0-400 A with in built selector switch and CTs-01 No complete all as specified and directed. |
| 52 | (j) 3 Line multifunctional meter-01(Nos) complete all as specified and directed. |
| 53 | All as per item no 23 here in before but LT Panel consisting of following items (LT Panel 3 near cook house) complete all as specified and directed. |
| 54 | (a) Copper Bus bar 240amps of size 20x6mm complete all as specified and directed. |
| 55 | (b) MCCB 4 Pole thermal magnetic release 415 volts 160 A 36 KA,Ics=100%Icu ,Adjustable overload settings:0.8-1×In, Adjustable shortcircuit settings: 6-10×In -01(incoming), complete all as specified and directed. |
| 56 | (c)MCCB 4 pole thermal magnetic release 415 Volts 125 A, 16 KA, Ics=100%Icu ,Adjustable overload settings:0.8-1×In, Adjustable shortcircuit settings: 6-10×In -01 (Existing panel at MT Area) complete all as specified and directed. |
| 57 | (c)MCCB 4 pole thermal magnetic release 415 Volts 63 A, 16 KA, Ics=100%Icu ,Adjustable overload settings:0.8-1×In, Adjustable shortcircuit settings: 6-10×In -06 (Cook House 06 Nos) complete all as specified and directed. |
| 58 | (d)MCB 2 pole SPN 32A-6 complete all as specified and directed. |
| 59 | (f) Indicating lamps ( LED type) ( R-Y-B) -01 (Set of three) complete all as specified and directed. |
| 60 | (g) Voltmeter digital type 0-500 V with inbuilt selector switch-01 No complete all as specified and directed. |
| 61 | (h) Ammeter digital type 0-400 A with in built selector switch and CTs-01 No complete all as specified and directed. |
| 62 | (i) 3 Line multifunctional meter-01(Nos) complete all as specified and directed. |
| 63 | All as per item no 23 here in before but LT Panel consisting of following items (LT Panel 4 near TRG Area) complete all as specified and directed. |
| 64 | (a) Copper Bus bar 240amps of size 20x6mm complete all as specified and directed. |
| 65 | (b) MCCB 4 Pole thermal magnetic release 415 volts 160 A 36 KA,Ics=100%Icu ,Adjustable overload settings:0.8-1×In, Adjustable shortcircuit settings: 6-10×In -01(incoming), complete all as specified and directed. |
| 66 | (c)MCCB 4 pole thermal magnetic release 415 Volts 125 A, 16 KA, Ics=100%Icu ,Adjustable overload settings:0.8-1×In, Adjustable shortcircuit settings: 6-10×In -01 (Library And BOC Gate) complete all as specified and directed. |
| 67 | (c)MCCB 4 pole thermal magnetic release 415 Volts 63 A, 16 KA, Ics=100%Icu ,Adjustable overload settings:0.8-1×In, Adjustable shortcircuit settings: 6-10×In -04 (MES Store 04 Nos, Class ROOM 04 nos ) complete all as specified and directed. |
| 68 | (d)MCB 2 pole SPN 32A-6 complete all as specified and directed. |
| 69 | (f) Indicating lamps ( LED type) ( R-Y-B) -01 (Set of three) complete all as specified and directed. |
| 70 | (g) Voltmeter digital type 0-500 V with inbuilt selector switch-01 No complete all as specified and directed. |
| 71 | (h) Ammeter digital type 0-400 A with in built selector switch and CTs-01 No complete all as specified and directed. |
| 72 | (J) 3 Line multifunctional meter-01(Nos) complete all as specified and directed. |
| 73 | All as per item no 23 here in before but LT Panel consisting of following items (LT Panel 5 near CSD canteen ) complete all as specified and directed. |
| 74 | (a) Copper Bus bar 240amps of size 20x6mm complete all as specified and directed. |
| 75 | (b) MCCB 4 Pole thermal magnetic release 415 volts 160 A 36 KA,Ics=100%Icu ,Adjustable overload settings:0.8-1×In, Adjustable shortcircuit settings: 6-10×In -01(incoming), complete all as specified and directed. |
| 76 | (c)MCCB 4 pole thermal magnetic release 415 Volts 63 A, 16 KA, Ics=100%Icu ,Adjustable overload settings:0.8-1×In, Adjustable shortcircuit settings: 6-10×In -04 (CSD, Store,Guard Room,Spare) complete all as specified and directed. |
| 77 | (d)MCB 2 pole SPN 32A-6 complete all as specified and directed. |
| 78 | (f) Indicating lamps ( LED type) ( R-Y-B) -01 (Set of three) complete all as specified and directed. |
| 79 | (g) Voltmeter digital type 0-500 V with inbuilt selector switch-01 No complete all as specified and directed. |
| 80 | (h) Ammeter digital type 0-400 A with in built selector switch and CTs-01 No complete all as specified and directed. |
| 81 | (i) 3 Line multifunctional meter-01(Nos) complete all as specified and directed. |
| 82 | Supply and fix feeder pillar box made out of 3.15 mm thickness CRCA heavy internal compartment thickness of 2mm including MS angle iron frame of size 40 x 40 x 5 mm including Incomer as MCCB 25A and 5 Nos outgoing as MCB TPN 32 Amp complete all as specified and directed. |
| 83 | M&L , earthing complete for machinary / Equipment installed at power house / sub station with galavanised steel earth plate electrode of size 60 cmx 60 cmx 6 mm thick buried directly in ground ( earth pit not less then 2.25 m deep below the normal ground level ) with top edge of the earth plate not less then 1.5m below normal Ground level connected galvanised earth strip 32X6 mm by means of bolts, nuts, washerws and check nuts all shown in electrical plate No.5 of SSR Part- I connected to main board / disribution board complete .Earthing GI lead and GI protection pipe 15 mm dia light grade upto 7.5 m from earth pit connecting to machinary/ equipment, testing point, all as specified and testing on complete all as specified and directed. |
| 84 | Note :- (i) The unit rate shall also included for earth work in hard /dense soil , PCC type C-I (1:3:6) chamber , PCC 1:2:4 type B-I cover 50 mm thick reinforced with 8 mm dia TMT bars,150 mm c/c both ways, funnel with watering pipe 20 mm dia medium graded , GI protection pipe light grade 15 mm dia and wire mesh complete in addition to items No. 1(a) to (e) of preamble (notes) under sub heading earthing specified on SI page No. 389 of SSR Part - II. |
| 85 | (ii) Earthing strip and GI protection pipe beyond 7.5 mtrs will be measured and paid separatelly if required under appropriate Schedule. |
| 86 | Note :- (i) Earthing shall be tested as specified in casul 19.137 of SSP PART - I 2009 , to the entire satisfication of Engr-in-Charge. (ii) On teting after complataion of earthing , if the desired earth resistance is not obatined the earthing wiil be re done by the contractor at his on risk and cost to the entire satisfaction of the Engr - in - charge. |
| 87 | M&L for road cutting of any thickness with depth of 0.6m depth and 0.1m width and laying of pipe and drawing cable and PCC 1:3:6 for road cutting all as per specfied and dirrected. |
| 88 | NOTE APPLICABLE FOR ALL ITEMS :- If rate quoted for similar/identical items in same part of Sch ‘A’ is at variance, the lowest rate quoted shall only be considered for payment to the contractor. Please Enable Macros to View BoQ information |