| 1 | Taking down carefully copper/aluminium point wiring (light, fan, socket or power) complete, including fittings such as switches, bell push, holders, ceiling roses, pendants, regulators, sockets etc but excluding DBs, light fittings etc and making good disturbed surfaces of walls, floors etc. and matching with existing surface all as specified and as directed. |
| 2 | M & L for point wiring complete on surface of wall (open) type with two runs of 1.5 sqmm for phase and neutral, single core, multistranded copper conductor cable of 1100 Volts grade,conforming to IS-694 1990, PVC insulated and unsheathed, FRLS cable drawn through and including PVC casing and caping (ISI marked) and its accessories such as Tee, elbow, jointer, elbow corner etc. fixed on surface of walls, coloumns/ beams alongwith 1.5 Sqmm copper conductor cable (multistranded) PVC insulated and unsheathed FRLS cable as earth wire connected to common earth dolly at one end and metalic bodies of luminaire/ fan at other end including PVC holding boards/bakelite sheets for mounting switches, sockets, fan Regulators, accessories etc as specified and directed for one light point or one fan point controlled by one, one way switch. NOTE: 1. Proper colour coding shall be adopted for wiring (for phase-RED,YELLOW,BLUE for Earth-Green and Neutral-Black) 2. wiring shall be done as per complaints received from user only on reqired basis it is not necessary to do whole wiring of any whole bldg.3. All points shall be earthed up to fixtures i.e holders,tube lights,all lights,ceiling lights,bulkhead lights,bldg security lights etc. |
| 3 | All as per serial item No. 2 here in before but one 6 Amp 3 pin socket outlet point on same board with other switches including earth wire as specified. |
| 4 | All as per serial item No. 2 here in before but on independent board. |
| 5 | All as per serial item No. 2 here in before but for one bell/buzzer point controlled by one push button on the same board with other switches or independent. |
| 6 | All as per serial item No. 2 herein before but with 2.5 Sqmm, PVC copper stranded cable FRLS type for phase,Neutral and earth for one 15 Amp, 6 pin socket on independent board. |
| 7 | S&F switch piano, flush button, 6 Amp, single pole, one way, 230 volts, white finish, all as specified & as directed. |
| 8 | S&F socket outlet, flush type, 3 pin, 6 Amp, multipurpose, 230 volts, single pole, one way suitable for 3 pin/2pin, 5 Amp plug top white/ivory finish all as specified & as directed. |
| 9 | S&F switch socket combination, flush type, 3 pin, 6 Amp, multipurpose, 230 volts, single pole, one way, suitable for 3 pin/2pin 5 Amp plug top white/ivory finish all as specified & as directed. |
| 10 | S&F switch socket combination, multipurpose, flush type, 2 in 1 type (3 pin ) 6/16 Amps, 230V, AC. all as specified & as directed. |
| 11 | S&F lamp holder, angle/ batten type, PVC/Polycarbonate type with back plate, suitable for batten fittings all as specified & as directed. |
| 12 | S&F fancy type ceiling rose, surface PVC 50mm dia, 3 terminals including PVC mounting block white/ivory finish all as specified & as directed. |
| 13 | S&F bell push, flush type, 6 Amp, single pole, 230 volts, white finish all as specified & as directed. |
| 14 | S&F fan regulator, step type, electronic on existing phenolic laminated sheet, 5 step, socket type, 230 volts, suitable for ceiling fan 1200/1400mm sweep all as specified & as directed. |
| 15 | M&L for point wiring with two runs of 1.5 sqmm for phase and neutral, single core, multistranded copper conductor cable of 1100 Volts grade, conforming to IS-694 1990, PVC insulated and unsheathed , FRLS cable laid / fixed and including concealed in PVC rigid conduit on walls/ceiling alongwith 1.5 Sqmm copper conductor cable (multistranded) PVC insulated and unsheathed FRLS cable as earth wire connected to common earth dolly at one end and metalic bodies of luminaire/ fan at other end including including Sunken box, including PVC boards/bakelite sheets / and including factory made terminal boxes with modular cover plates and frames suitable for mounting switches, sockets, fan Regulators, accessories etc as specified and as directed for one light point or one fan point controlled by one, one way switch NOTE :- 1.Proper colour coding shall be adopted for wiring (for phase-RED,YELLOW,BLUE for Earth-Green and Neutral-Black) 2.wiring shall be done as per complaints received from user only on reqired basis it is not necessary to do whole wiring of any whole bldg. 3. All points shall be earthed up to fixtures i.e holdrs,tube lights,all lights,ceiling lights,bulkhead lights,bldg security lights etc.4. Unit rate include for cutting chases for conduits and sinking for boxes and making good to wall ,floors etc. |
| 16 | All as per serial item No. 15 here-in-before but for one 6 Amp, 3 pin socket outlet point on same board with other switches including earth wire as specified. |
| 17 | All as per serial item No. 15 here-in-before but on independent board. |
| 18 | All as per serial item No. 15 here-in-before but for one bell/buzzer point controlled by one push button on the same board with other switches or independent. |
| 19 | All as per serial item No. 15 here-in-before but with 2.5 Sqmm, PVC copper stranded cable FRLS type for phase, neutral and earth for one 16 Amp, 6 pin socket on independent board. |
| 20 | S&F modular switch one way, 6 Amp, one module, 230V all as specified and directed. |
| 21 | S&F modular bell push, 6 Amp, one module, 230V all as specified and directed. |
| 22 | S&F modular socket, 6A, 3 pin 2 module, 230V all as specified and directed. |
| 23 | S&F modular switch one way, 16 Amp, one module, 230V all as specified and directed. |
| 24 | S&F modular socket, 6A/16A, 3 pin combined 2 module, 230V all as specified and directed. |
| 25 | S&F modular fan Regulator, 2 module complete all as specifed and as directed. |
| 26 | S&F bell, AC, 230 volts, single phase complete all as specified and as directed. |
| 27 | S&F repairs socket outlet, flush type, 3 pin, 6 Amp, multipurpose, 230 volts, single pole, one way suitable for 3 pin/2pin, 5 Amp plug top white/ivory finish all as specified & as directed. |
| 28 | S&F in repairs, switch socket combination with box type outlet, 3 pin, 6 Amps, flush type (Multi purpose), piano type, AC 230 Volts. all as specified and as directed. |
| 29 | S&F in repairs, switch socket combination with box type outlet, 2 in 1, 3 pin, 6 Amps and 16 Amp, flush type (Multi purpose), piano type, AC 230 Volts all as specified and as directed. |
| 30 | S&F in repairs, switch piano, flush button, 6 Amp, single pole, one way, 230 volts, white finish all as specified & as directed. |
| 31 | S&F in repairs, and connecting up fan regulator, electronic on existing phenolic laminated sheet, 5 step socket type, 230 volts, suitable for ceiling fan 1200/1400mm sweep all as specified & as directed. |
| 32 | S&F in repairs fancy type ceiling rose, surface PVC 50mm dia, 3 terminals including PVC mounting block white/ivory finish all as specified & as directed. |
| 33 | S&F in repairs bell, AC, 230 volts, single phase complete all as specified and as directed. |
| 34 | S&F in repairs lamp holder, angle/ batten type, PVC/Polycarbonate type with back plate, suitable for batten fittings all as specified & as directed. |
| 35 | S&F modular cover plate frame, 3 module complete all as specifed and as directed. |
| 36 | S&F modular cover plate frame, 4 module complete all as specifed and as directed. |
| 37 | S&F modular cover plate frame, 6 module complete all as specifed and as directed. |
| 38 | S&F modular cover plate frame, 8 module complete all as specifed and as directed.Notes for Item Nos 27 to 38 : (i) Item shall be executed to attend day to day complaints. (ii) Burnt/damaged fitting only shall be replaced.(iii) Wiring is not included in these item. |
| 39 | M & L for sub main wiring with 4 runs of 10 sqmm, single core, PVC insulated & unsheathed FRLS cable conforming to IS-694, 1100 volts with copper conductor, multi stranded drawn in and including suitable size heavy grade casing caping (ISI marked) with all accessories such as Tees, Elbows, junction box, reducers etc as requied alongwith one run of 10 sqmm single core PVC insulated & unsheathed FRLS copper conductor as continuos earth wire dolly and connecting to existing main switch board / distribution board of each building / qtr as ordered and testing on completion including taking down old submain wiring and any type of conduit complete all as specified and as directed. NOTE: 1. Proper colour coding shall adopted for wiring (for phase-RED,YELLOW,BLUE for Earth-Green and Neutral-Black)2. Five runs of 10 sq.mm cable and one run of PVC casing & caping shall be measured as one unit. |
| 40 | M & L for sub main wiring with 2 runs of 6 sqmm, single core, PVC insulated & unsheathed FRLS cable conforming to IS-694, 1100 volts with copper conductor, multi stranded drawn in and including suitable size heavy grade casing caping (ISI marked) with all accessories such as Tees, Elbows, junction box, reducers etc as requied alongwith one run of 6 sqmm single core PVC insulated & unsheathed FRLS copper conductor as continuos earth wire dolly and connecting to existing main switch board / distribution board of each building / qtr as ordered and testing on completion including taking down old submain wiring and any type of conduit complete all as specified and as directed. NOTE: 1. Proper colour coding shall adopted for wiring (for phase-RED,YELLOW,BLUE for Earth-Green and Neutral-Black) 2. Three runs of 6 sq.mm cable and one run of PVC casing & caping shall be measured as one unit. |
| 41 | M & L for sub main wiring with 2 runs of 4 sqmm, single core, PVC insulated & unsheathed FRLS cable conforming to IS-694, 1100 volts with copper conductor, multi stranded drawn in and including suitable size heavy grade casing caping (ISI marked) with all accessories such as Tees, Elbows, junction box, reducers etc as requied alongwith one run of 4 sqmm single core PVC insulated & unsheathed FRLS copper conductor as continuos earth wire dolly and connecting to existing main switch board / distribution board of each building / qtr as ordered and testing on completion including taking down old submain wiring and any type of conduit complete all as specified and as directed. NOTE: 1. Proper colour coding shall adopted for wiring (for phase-RED,YELLOW,BLUE for Earth-Green and Neutral-Black)2. Three runs of 4 sq.mm cable and one run of PVC casing & caping shall be measured as one unit. |
| 42 | S&F metal base plastic enclosure with plug socket, single pole and neutral with two pin and earth plug with one MCB of 20 Amps (SP) complete all as specified and as directed. Make : Havells DBOX Plug and socket or equivalent approved make |
| 43 | S&F in repairs, MCB SP, AC 240 V, 6 to 32 Amps, 10 KA capacity ,'c' series, making connection with suitable size of copper lugs etc complete all as specified and as directed. |
| 44 | S&F in repairs, MCB SPN, AC 240 V, 6 to 32 Amps, 10 KA capacity ,'c' series, making connection with suitable size of copper lugs etc complete all as specified and as directed. |
| 45 | S&F in repairs double door shutter type for distribution board (when MCBs are to be used), single pole and neutral, 240 volts, 8 way, protection class IP-42, suitable for fixing MCBs, Isolators etc, confirming As per IEC 61439-3, suitable for flush mounting and surface mounting, with 100 Amps rated copper busbar, with Neutral bar, Earthbar and cable alley for cable managment, fully shrouded, Neutral bars, prefittes masking sheet complete all as specified and as directed. |
| 46 | S&F in repairs, double door shutter type for distribution board (when MCBs are to be used), single pole and neutral, 240 volts, 4 way, protection class IP-42, suitable for fixing MCBs, Isolators etc, confirming As per IEC 61439-3, suitable for flush mounting and surface mounting, with 100 Amps rated copper busbar, with Neutral bar, Earthbar and cable alley for cable managment, fully shrouded, Neutral bars, prefittes masking sheet complete all as specified and as directed. |
| 47 | S&F in repairs, double door shutter type for distribution board (when MCBs are to be used), Tripple pole and neutral, 415 volts, 4 way, protection class IP-42, suitable for fixing MCBs, Isolators etc, confirming As per IEC 61439-3, suitable for flush mounting and surface mounting, with 100 Amps rated copper busbar, with Neutral bar, Earthbar and cable alley for cable managment, fully shrouded, Neutral bars, prefittes masking sheet complete all as specified and as directed. |
| 48 | S&F in repairs ISOLATOR TPN, AC 415 V, 63 amps, 10 KA capacity ,'C' series, making connection with suitabl size of copper lugs etc complete all as specified and as directed. |
| 49 | M&L in repairs/replacement earthing complete with galvanized steel earth plate electrode 60 cm X 60 cm X 6.3 mm thick, buried directly in ground (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of plate not less than 1.5 mtr below ground level, connecting to the GI wire 4 mm dia, by means of nut bolts, check nuts and washer of the GI . Earth wire connected upto main earth point/DBs alongwith 15mm dia GI pipe, medium grade, including provision of concrete pit in PCC (1:2:4) type B-1 using 20 mm graded stone aggregates with 40 mm thick RCC (1:2:4) cover with reinforced with XPM (weight not less than 4 Kg / Sqm) and frame of angle iron 25mm X 25 mm X 3mm with lugs 2 Nos and with 6 mm dia MS bar handle made to shape, GI light grade 20 mm bore pipe for watering perforated at bottom 1.75 mtr long placed on top edge of earth plate, common salt and charcoal filling, test point made out of phosphorus bronze with fixing arrangement, funnel, wire mesh and earth work in hard/dense soil, returning filling in and removal of surplus soil to a distance not exceeding than 50 mtr, all as per electric plate No 3 of SSR Part I 2009 and connection to earth test point all as specified including testing on completion. |
| 50 | Supply and fix in repairs electronic meters temper proof LCD display with polycarbonate cover 230 V, 10-60Amp, accuracy class-I 50Hz, conforming to IS 13779, IP-54, with parameters to show data, time, current reading, load, PF, voltage and KWH complete all as specified and directed by Engr in Charge.Note : The meters shall be taken on charge by the Engr in Charge and RV No. shall be mentioned in the MB. |
| 51 | S&F in replacement LED flood light fitting 70 Watts, having pressure die cast housing with IP 65 efficient high outout emitter LED for better distribution, protection with heat resistant toughned glass with individual LED lenses complete including making connection with flood light box or OH line using PVC insulated and sheathed single core multi stranded alumn conductor cable of size 1.5 sq mm including MS clamps nuts, bolts and washers of required size complete all as specified and directed by Engr in Charge.Make : Havells Cat No. JETAADORNFLS70WLED757SSYMTOTGV2 or equivalent of makes specified. |
| 52 | S&F in replacement LED flood light fitting 100 Watts, having pressure die cast housing with IP 65 efficient high outout emitter LED for better distribution, protection with heat resistant toughned glass with individual LED lenses complete including making connection with flood light box or OH line using PVC insulated and sheathed single core multi stranded alumn conductor cable of size 1.5 sq mm including MS clamps nuts, bolts and washers of required size complete all as specified and directed by Engr in Charge.Make : Havells Cat No. JETALEGANZAFLS100WLED757P60DTOTG or equivalent of makes specified. |
| 53 | Supply & Fix in repair Capacitor 2.5 mfd, 240 Volt suitable all as specified and as directed. |
| 54 | S&F in replacement decorative ultra slim square profile LED lighting fixture with extruded polycarbonate, environmental friendly, energy efficient of capacity 10 Watt, 6500 K with inbuilt driver complete fitting and all other accessories fitting arrangements including connecting up with two core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and as directed.Make : Cat No.LHEXACP7IN1W010 of Havells or equivalent of makes specified in PS |
| 55 | S&F in replacement decorative ultra slim batten square profile LED lighting fixture with extruded polycarbonate, environmental friendly, energy efficient of capacity 20 Watt , 6500 K with inbuilt driver complete fitting and all other accessories fitting arrangements including connecting up with two core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and as directed.Make : Cat No.LHEXAWP7UN1W020 of Havells or equivalent of makes specified in PS |
| 56 | S & F Inverter LED batten 20W 6500K with square profile and polycarbonate channel, lithium-Ion battery with charging time 8hours-10 hours, back up time up to 4 hours and surge protection up to 4KV.Make : HAVELLS PRIDE PLUS INVERTER BATTEN Cat No. LHEXASP7IN1W020 or equivalent model of makes specified. |
| 57 | S&F in repairs, 600 mm x 600 mm size, recess mounted LED luminaire of capacity 36 watt, with driver, for soft glare free light, AC 230 volt complete with all acessories and connections, complete all as specified & as directed.Make:HAVELLS OCTANE PLUS LED 2 X 2 PANEL Cat No LHEBAEP7IW1W036 or equivalent model of makes specified. |
| 58 | S&F in replacement LED street light fitting 70 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant acrylic covers with driver, lamp, impact and corrosion resistant with IP 66 protection complete including PVC copper wire 1.5 sqmm of suitable length for connection of street light from Overhead conductor /junction box complete all as specified and directed by Engr in Charge.Make : Havells Cat No LHEXBCP7IN7K070 or equivalent of makes specified. |
| 59 | S & F in repairs new generation IP 65 LED post top lantern 15 watt, energy saving, enviorment friendly, long life aesthetically designed with symmetrical light distribution, spun aluminium landscape lumainarie with high power LEDs as light source. clear cover complete as specified and as directed by Engr-in-Charge. Make: HAVELLS Cat No RUBYNXTPT15WLED730PSYMTOPC or equivalent approved make |
| 60 | S&F in repairs 8 Watt decorative type garden/ path lights bollard light fitting made up of high grade unbreakable polycarbonate material IP65 and including necessary excavation and concrete 1:3:6 foundation and fixed by 3 Nos bolts complete as specified and directed by Engr-in-Charge.Make : Havells Cat No. CONEBLS8WLED830PSYMTOPC or equivalent model of makes specified. |
| 61 | S&F in repairs, 300 mm x 300 mm size, recess mounted LED luminaire 15 watt, with driver, for soft glare free light, AC 230 volt complete with all acessories and connections, complete all as specified & as directed.Make : Cat No PLUTO1X1PLR15WLED840SG2 or equivalent model of makes specified. |
| 62 | Supply & fix exhaust fans PVC body, AC single phase 230/ 240 V of size 150 mm sweep, with louver, and connecting up including provision of three core flexible copper wire of size 1.5 sqmm from ceiling rose to exhaust fan complete and fixing with necessary bolts, nuts , washers,etc complete all as specified and as directed by Engineer in Charge. |
| 63 | Supply & fix exhaust fans PVC body, AC single phase 230/ 240 V of size 200 mm sweep, with louver, and connecting up including provision of three core flexible copper wire of size 1.5 sqmm from ceiling rose to exhaust fan complete and fixing with necessary bolts, nuts , washers,etc complete all as specified and as directed by Engineer in Charge. |
| 64 | M&L in repairs,for copper flexible submersible cable, flat, 3 core, 1100 volts grade, PVC Insulated, 2.5 Sq mm including water proof joint all as specified and as directed. |
| 65 | S&F in repairs, bakelite sheet board of 100 mm x 100mm size, not less than 3mm thick for mounting of switch, sockets, fan regulators, etc.complete with screws and washers, etc. all as specified and as directed. |
| 66 | S&F in repairs, bakelite sheet board of 175 mm x 100mm size, not less than 3mm thick for mounting of switch, sockets, fan regulators, etc.complete with screws and washers, etc. all as specified and as directed. |
| 67 | S&F in repairs, bakelite sheet board of 200 mm x 150mm size, not less than 3mm thick for mounting of switch, sockets, fan regulators, etc.complete with screws and washers, etc. all as specified and as directed. |
| 68 | S&F in repairs, bakelite sheet board of 250 mm x 200mm size, not less than 3mm thick for mounting of switch, sockets, fan regulators, etc.complete with screws and washers, etc. all as specified and as directed. |
| 69 | S&F in repairs, bakelite sheet board of 350 mm x 300mm size, not less than 3mm thick for mounting of switch, sockets, fan regulators, etc.complete with screws and washers, etc. all as specified and as directed. Note for item Nos 65 to 69 : Cutting of backelite sheet board for mounting switch,sockets, fan regulators etc. shall be as per site requirement. |
| 70 | Taking down unserviceable ceiling fan, 1200/ 1400 mm sweep, any make, opening, taking out burnt copper winding, cleaning all parts, rewinding with new super enamelled copper wire of matching size and gauge and number of turns as required, varnishing and heating the winding including providing paper insulation including replacement of ball bearings, greasing re-assembling the fan as a one unit and re-fixing ceiling fan at the existing site / rooms and connected with 23/0.0076 three core PVC flexible cable from ceiling rose to fan etc complete all as specified. |
| 71 | Taking down unserviceable ceiling fan, 1200/ 1400 mm sweep, any make, with blades, opening, cleaning all parts, including replacement of ball bearings, greasing re-assembling the fan as a one unit and re-fixing ceiling fan at the existing site / rooms and connected with 23/0.0076 three core PVC flexible cable from ceiling rose to fan etc complete all as specified. |
| 72 | Taking down unserviceable Exhaust fan any sweep and make, opening, taking out burnt copper winding, cleaning all parts, rewinding with new super enamelled copper wire of matching size and gauge and number of turns as required, varnishing and heating the winding including providing paper insulation including replacement of ball bearings, greasing re-assembling the fan as a one unit and re-fixing ceiling fan at the existing site / rooms and connected with 23/0.0076 three core PVC flexible cable from ceiling rose to fan etc complete all as specified. |
| 73 | Taking down carefully water Geyser 25/50 ltrs capacity by unscrewiring nuts bolts, water inlet/outlet pipes from walls/foundation complete repair of base assembly of geyser made out of copper base plate with gasket and proper size of nuts, bolts & washers, with replacement of inlet and outlet pipe, connection of geyser with flexible copper cable 3 core of size 23/0.0076 including refixing in position after carrying out repair including making connectin to the water inlet, outlet pipe, electric connection and testing complete all as specified and as directed. |
| 74 | M&L in repairs for down rod with clamps etc of ceiling fan with down rod of 15mm bore medium grade GI pipe 0.45 metre long with clamps, bolts, nuts, split pins washers of suitable size of approved quality all as per specified and as directed. |
| 75 | M&L in repairs for down rod with clamps etc of ceiling fan with down rod of 15mm bore medium grade GI pipe 0.60 metre long with clamps, bolts, nuts, split pins washers of suitable size of approved quality all as per specified and as directed. |
| 76 | M&L in repairs for down rod with clamps etc of ceiling fan with down rod of 15mm bore medium grade GI pipe 1.50 metre long with clamps, bolts, nuts, split pins washers of suitable size of approved quality all as per specified and as directed. |
| 77 | S&F in replacement heating element, triangular or square type, 1500watts, 230 volts, suitable for geyser and as per approved sample all as specified and as directed. |
| 78 | S&F in replacement heating element, triangular or square type, 2000watts, 230 volts, suitable for geyser and as per approved sample all as specified and as directed. |
| 79 | Supply only of geyser safety valve (Pressure release valve) complete suitable for vertical type geyser all as specified and as directed. |
| 80 | Supply only non return valve made out of brass fixed in vertical position of size 15mm dia all as specified and as directed. |
| 81 | Supply only outer tank sheet cover made out of mild steel sheet of suitable size for geyser of size 25 ltrs capacity vertical type complete all as specified and as directed. |
| 82 | S&F in replacement inner tank of 25 ltr capacity geyser as per existing at site all as specified and as directed. |
| 83 | S&F in repairs, indicator lamp, 220 Volts, AC, suitable for 25/50 ltrs capacity of geyser all as sepecified and as directed. |
| 84 | S&F in repairs, PVC connection pipe (ISI marked) complete with brass end terminal 300mm long all as specified and as directed. |
| 85 | S&F in repairs, PVC connection pipe (ISI marked) complete with brass end terminal 450mm long all as specified and as directed. |
| 86 | S&F in repairs thermostate switch pointer type suitable for 25/50 ltrs capacity geyser with adjustment knob complete all as specified and as directed. |
| 87 | Supply and fix in replacement 25 mm size PVC casing caping with all accessories of adequate size complete all as specified and directed by Engineer in charge. |
| 88 | Supply and fix in replacement 32 mm size PVC casing caping with all accessories of adequate size complete all as specified and directed by Engineer in charge. |
| 89 | S&F in replacement 1100 Volt grade, heavy duty cable PVC insulated aluminium stranded conductor served with inner sheathing of PVC tape and over all PVC sheathed in service connection suspended by insulating hangers not more than 1 mtr apart including 4 mm suspension wire one twin core cable flat of stranded multistranded conductor of size 4 Sqmm complete all as specified and as directed. |
| 90 | S&F in replecement 1100 Volt grade, heavy duty cable PVC insulated aluminium stranded conductor served with inner sheathing of PVC tape and over all pvc sheathed in service connection suspended by insulating hangers not more than 1 mtr apart including 4 mm suspension wire one twin core cable flat of stranded multistranded conductor of size 6 sqmm complete all as specified and as directed. Please Enable Macros to View BoQ information |