| 1 | Supply of Equipment and accessories |
| 2 | 33 kV, 31.5 kA, 2000A, Vacuum Gang operated Circuit Breaker complete with mounting structure and all accessories including Terminal connectors |
| 3 | 33 kV, 31.5 kA, 1250A motorised isolators with single Earth Switch complete with all fittings and accessories including Terminal connectors as per specification |
| 4 | 33kV, 31.5 kA, 1250A motorised isolators without Earth Switch complete with all fittings and accessories including Terminal connectors as per specification.(Bus, Bus Sectionalizer and PT) |
| 5 | 33kV, 400-200/1-1A, 2-Core Single Phase CT complete with all fittings and accessories including Terminal connectors and marshalling box as required(0.2S-5P20 Class, live tank type) as per specification |
| 6 | 30 kV, 10 kA, Class-2 station class lightning arrester and surge monitor complete with all fitting and accessories including terminal connectors and base insulator as per specification |
| 7 | 33 kV, 8 KN post insulator with all fitting including terminal connectors as per specification (creepage dist,- 31 mm/kV) |
| 8 | 33 kV PT (33/√3)/(110/√3) with all firttings and terminal connectors (accuracy class 0.2) |
| 9 | Supply of Switchyard structure |
| 10 | Column (Total 3 Nos)(Bus: 2 Nos and line: 1 Nos) |
| 11 | Beam (Total 2 Nos) (Bus: 1 Nos and line: 1 Nos) |
| 12 | Conductor, Insulator strings, Clamps & Connectors (UPG, T Etc.) |
| 13 | Tension clamp for line and twin bus |
| 14 | Double tension hardware fittings |
| 15 | Twin bus spacer |
| 16 | Twin bus to single panther T-clamp |
| 17 | ACSR Zebra Conductor |
| 18 | 90kN Insulators |
| 19 | Mounting Structures with mounting & foundation bolts as per drawing. |
| 20 | 33kV Motorised isolators without Earth Switch |
| 21 | 33kV CT |
| 22 | 33kV LA |
| 23 | 33kV PI |
| 24 | 33kV Motorised isolators with Earth Switch |
| 25 | 33kV PT |
| 26 | CRP & SAS |
| 27 | 33kV Feeder Control and Relay Panel (Simplex Type) suitable for integration to existing Substation Automation System |
| 28 | Managed Ethernet switch with OF PATCH |
| 29 | SAMAST compliant ABT energy meter including installation |
| 30 | Armoured Control Cable(Copper) |
| 31 | a) 4Cx2.5 sqmm |
| 32 | b) 7Cx1.5 sqmm |
| 33 | c)12Cx1.5 sq mm |
| 34 | Armoured Power Cable(Aluminium) |
| 35 | a)2Cx6 sqmm |
| 36 | b) 4Cx16 sqmm |
| 37 | c) 3.5 Cx 35 sqmm |
| 38 | Earthmat extension and grounding of equipments |
| 39 | 65 x 12mm GI flat Earthing conductor for earthing of indoor L.T and control panels, junction box, Marshalling boxes, cable trenches etc. |
| 40 | Earth Electrode, 100mm dia. 3m long GI pipe |
| 41 | 50 x 6 mm GI flat earthing conductor for earthing of indoor LT and control panels, junction box, marshalling box, etc. |
| 42 | switchyard illumination |
| 43 | 100W LED lights for switchyard illumination, including fitting and fixing |
| 44 | Supply of AC marshalling kiosk including construction of foundation,installation and cable foundation |
| 45 | Supply of AC marshalling kiosk including construction of foundation,installation and cable foundation 2 No 63A, 4P (incomer) 3 No 25A, 4P (Outgoing) 8 No 16A 4P (Outgoing) 8 No 10A 4P (Outgoing) 5 No 10A 2P (Outgoing) |
| 46 | Mandatory Spares |
| 47 | Operating Mechanism for 33kV VCB |
| 48 | Trip Coil for 33kV VCB |
| 49 | Closing Coil for 33kV VCB |
| 50 | Spring charging Motor for 33kV VCB |
| 51 | 33kV, 25KA , 1250A motorised Isolators without Earth Switch |
| 52 | 33kV, 31.5 kA, 1250A Isolators female/fixed contact (entire assembly) |
| 53 | 33kV, 31.5 kA, 1250A Isolators male/moving contact (entire assembly) |
| 54 | 33kV, 400-200/1-1A, 2-Core Single Phase CT (0.2S-5P20 class, live tank type) as per specification |
| 55 | 33kV Lightning Arrester |
| 56 | Numerical Backup Relay as per the required specifications |
| 57 | Master trip Relay as per the required specifications |
| 58 | Bay control unit as per the required specifications |
| 59 | OFC Patch Cord: ST-ST |
| 60 | OFC Patch Cord: ST-LC |
| 61 | Clamps & Terminal connectors |
| 62 | Tension Clamps |
| 63 | Supply of Equipment and accessories |
| 64 | 33 kV, 31.5 kA, 2000A, Vacuum Gang operated Circuit Breaker complete with mounting structure and all accessories including Terminal connectors |
| 65 | 33 kV, 31.5 kA, 1250A motorised isolators with single Earth Switch complete with all fittings and accessories including Terminal connectors as per specification |
| 66 | 33kV, 31.5 kA, 1250A motorised isolators without Earth Switch complete with all fittings and accessories including Terminal connectors as per specification.(Bus, Bus Sectionalizer and PT) |
| 67 | 33kV, 400-200/1-1A, 2-Core Single Phase CT complete with all fittings and accessories including Terminal connectors and marshalling box as required(0.2S-5P20 Class, live tank type) as per specification |
| 68 | 30 kV, 10 kA, Class-2 station class lightning arrester and surge monitor complete with all fitting and accessories including terminal connectors and base insulator as per specification |
| 69 | 33 kV, 8 KN post insulator with all fitting including terminal connectors as per specification (creepage dist,- 31 mm/kV) |
| 70 | 33 kV PT (33/√3)/(110/√3) with all firttings and terminal connectors (accuracy class 0.2) |
| 71 | Supply of Switchyard structure |
| 72 | Column (Total 3 Nos)(Bus: 2 Nos and line: 1 Nos) |
| 73 | Beam (Total 2 Nos) (Bus: 1 Nos and line: 1 Nos) |
| 74 | Conductor, Insulator strings, Clamps & Connectors (UPG, T Etc.) |
| 75 | Tension clamp for line and twin bus |
| 76 | Double tension hardware fittings |
| 77 | Twin bus spacer |
| 78 | Twin bus to single panther T-clamp |
| 79 | ACSR Zebra Conductor |
| 80 | 90kN Insulators |
| 81 | Mounting Structures with mounting & foundation bolts as per drawing. |
| 82 | 33kV Motorised isolators without Earth Switch |
| 83 | 33kV CT |
| 84 | 33kV LA |
| 85 | 33kV PI |
| 86 | 33kV Motorised isolators with Earth Switch |
| 87 | 33kV PT |
| 88 | CRP & SAS |
| 89 | 33kV Feeder Control and Relay Panel (Simplex Type) suitable for integration to existing Substation Automation System |
| 90 | Managed Ethernet switch with OF PATCH |
| 91 | SAMAST compliant ABT energy meter including installation |
| 92 | Armoured Control Cable(Copper) |
| 93 | a) 4Cx2.5 sqmm |
| 94 | b) 7Cx1.5 sqmm |
| 95 | c)12Cx1.5 sq mm |
| 96 | Armoured Power Cable(Aluminium) |
| 97 | a)2Cx6 sqmm |
| 98 | b) 4Cx16 sqmm |
| 99 | c) 3.5 Cx 35 sqmm |
| 100 | Earthmat extension and grounding of equipments |
| 101 | 65 x 12mm GI flat Earthing conductor for earthing of indoor L.T and control panels, junction box, Marshalling boxes, cable trenches etc. |
| 102 | Earth Electrode, 100mm dia. 3m long GI pipe |
| 103 | 50 x 6 mm GI flat earthing conductor for earthing of indoor LT and control panels, junction box, marshalling box, etc. |
| 104 | switchyard illumination |
| 105 | 100W LED lights for switchyard illumination, including fitting and fixing |
| 106 | Supply of AC marshalling kiosk including construction of foundation,installation and cable foundation |
| 107 | Supply of AC marshalling kiosk including construction of foundation,installation and cable foundation 2 No 63A, 4P (incomer) 3 No 25A, 4P (Outgoing) 8 No 16A 4P (Outgoing) 8 No 10A 4P (Outgoing) 5 No 10A 2P (Outgoing) |
| 108 | Mandatory Spares |
| 109 | Operating Mechanism for 33kV VCB |
| 110 | Trip Coil for 33kV VCB |
| 111 | Closing Coil for 33kV VCB |
| 112 | Spring charging Motor for 33kV VCB |
| 113 | 33kV, 25KA , 1250A motorised Isolators without Earth Switch |
| 114 | 33kV, 31.5 kA, 1250A Isolators female/fixed contact (entire assembly) |
| 115 | 33kV, 31.5 kA, 1250A Isolators male/moving contact (entire assembly) |
| 116 | 33kV, 400-200/1-1A, 2-Core Single Phase CT (0.2S-5P20 class, live tank type) as per specification |
| 117 | 33kV Lightning Arrester |
| 118 | Numerical Backup Relay as per the required specifications |
| 119 | Master trip Relay as per the required specifications |
| 120 | Bay control unit as per the required specifications |
| 121 | OFC Patch Cord: ST-ST |
| 122 | OFC Patch Cord: ST-LC |
| 123 | Clamps & Terminal connectors |
| 124 | Tension Clamps |
| 125 | Erection of mounting structure as required, including construction of foundation and supply of all foundation materials and structure earthing |
| 126 | 33kV Vacuum Circuit breaker |
| 127 | 33kV CT |
| 128 | 33kV PT |
| 129 | 33kV isolator |
| 130 | 33kV LA |
| 131 | 33kV Post insulator |
| 132 | Erection of switchyard lattice tower structures (Column) including construction of foundation and supply of all foundation materials including labor cost, etc. |
| 133 | Column (Total 3 Nos)(Bus: 2 Nos and line: 1 Nos) |
| 134 | Erection of Beam |
| 135 | Beam (Total 2 Nos) (Bus: 1 Nos and line: 1 Nos) |
| 136 | Erection, Testing and commissioning including laying of control cables and equipment earthing as required |
| 137 | 33kV Vacuum Circuit breaker |
| 138 | 33kV CT |
| 139 | 33kV PT |
| 140 | 33kV isolator |
| 141 | 33kV LA |
| 142 | 33kV Post insulator |
| 143 | Instalation of earthing system |
| 144 | Construction of extended Main Earth mat (65 x 12 mm GI Flat) and connection to riser for equipment earthing as directed including painting of welded joints with bitumen paint |
| 145 | Installation of 50 x 6 mm GI flatearthing conductor for earthing of indoor LT & Control Panels, junction box, marshalling box, etc. |
| 146 | 100 mm dia earth electrode, 3mtr. Long GI pipe with test link including construction of covered earth pit |
| 147 | Installation and commissioning of the C&R panel |
| 148 | Erection, testing and commissioning of C&R panel and integration with existing Substation Automation System |
| 149 | Stringing of conductors |
| 150 | Stringing of conductors including hanging of disc insulator along with fitting and fixings of all clamps and hardware fittings , all jumpering works as required and as directed |
| 151 | Construction of cable trench including supply of all foundation materials and labour as required |
| 152 | C-Type |
| 153 | D-type |
| 154 | Construction of Fencing and Earthwork |
| 155 | Reconstruction of fencing covering the switchyard |
| 156 | Earthwork in excavation by mechanical means ( Hydraulic excavator/ manual means over areas exceeding 30cm in depth, 1.5m in width as 10Sqm on plan) including getting out and disposal of excavated earth, lead upto 50m and lift upto 1.5m, as directed by engineer in charge, ordinary rock |
| 157 | Civil Works (Details as per annexure attached with BID) |
| 158 | Construction of proposed rain water drain (Annexure-I) |
| 159 | Construction of retaining wall including supply of all materials and labour as required as per specifications(Annexure-II) |
| 160 | Switchyard PCC and Gravelling (Annexure-III) |
| 161 | Survey |
| 162 | Detailed Survey along with all reports like SLD, Section diagram and Layout Diagram etc Please Enable Macros to View BoQ information |