| 1 | Servicing of DG Set 250 KVA, checking Comprising of A , B and C checks at regular intervals for entire system as per manufacturer's catalogue such as checking all parts for serviceability, taking down defective parts such as fuel filter assembly , air cleaner assembly, lub oil hose flexible pipe , hose turbo etc and replacing the same with same size , make and capacity of parts . Cleaning all the serviceable filters with cleaning solution such as petrol and draining out the old used burnt engine oil from the oil sump and cleaning oil sump with suitable cleaning solution such as petrol and diesel or any other cleaning solution and refilling new engine oil grade 15W/40 upto required level and including testing to DG Set to the entire satisfaction of the Engr-in- Charge.Make : Kirloskar/ Cummins/ Greaves / Mahindra Note : (a) Replacement of any new items mentioned in the servicing will be measured and paid separately under items Sr No 1.10 to 1.50 (b) Servicing will carried out through authorized service engineer of OEM. Contractor has to submit the MOU with OEM or authorized service centre by OEM to accepting officer before commencement of contract.(c) Contractor has to submit all relevant documents after carrying out A, B, C Checks to Engr In Charge. (d) Contractor has to rectified the defects within 24 Hrs after getting information from the department, if he fails to do so penalty of Rs 500 per hrs after first 24 Hrs will be charged from the contractor. |
| 2 | Supply only Spinion lub oil filter for DG Set of capacity 250kVA |
| 3 | Supply only Fuel filter element primary for DG Set of capacity 250kVA |
| 4 | Supply only Fuel filter element secondary for DG Set of capacity 250kVA |
| 5 | Supply only Safety air filter element for DG Set of capacity 250kVA |
| 6 | Supply only Primary air filter element for DG Set of capacity 250kVA |
| 7 | All as per items No 1.0 above but for DG Set of capacity 200 KVA. Make : Kirloskar/ Cummins/ Mahindra/ GreavesNote : (a) Replacement of any new items mentioned in the servicing will be measured and paid separately under items Sr No 2.10 to 2.50(b) Servicing will carried out through authorized service engineer of OEM. Contractor has to submit the MOU with OEM or authorized service centre by OEM to accepting officer before commencement of contract.(c) Contractor has to submit all relevant documents after carrying out A , B , C Checks to Engr In Charge. (d) Contractor has to rectified the defects within 24 Hrs after getting information from the department, if he fails to do so penalty of Rs 500 per hrs after first 24 Hrs will be charged from the contractor. |
| 8 | Supply only Spinion lub oil filter for DG Set of capacity 200/250kVA |
| 9 | Supply only Fuel filter element primary for DG Set of capacity 200kVA |
| 10 | Supply only Fuel filter element secondary for DG Set of capacity 200kVA |
| 11 | Supply only Safety air filter element for DG Set of capacity 200kVA |
| 12 | Supply only Primary air filter element for DG Set of capacity 200kVA |
| 13 | All as per items No 1.0 above but for DG Set of capacity 160 KVA Make : Kirloskar/ Cummins/ Mahindra/ Greaves Note : (a) Replacement of any new items mentioned in the servicing will be measured and paid separately under items Sr No 3.1 to 3.5(b) Servicing will carried out through authorized service engineer of OEM. Contractor has to submit the MOU with OEM or authorized service centre by OEM to accepting officer before commencement of contract.(c) Contractor has to submit all relevant documents after carrying out A, B, C Checks to Engr In Charge. (d) Contractor has to rectified the defects within 24 Hrs after getting information from the department, if he fails to do so penalty of Rs 500 per hrs after first 24 Hrs will be charged from the contractor. |
| 14 | Supply only Spinion lub oil filter for DG Set of capacity 160kVA |
| 15 | Supply only Fuel filter element primary for DG Set of capacity 160kVA |
| 16 | Supply only Fuel filter element secondary for DG Set of capacity 160kVA |
| 17 | Supply only Safety air filter element for DG Set of capacity 160kVA |
| 18 | Supply only Primary air filter element for DG Set of capacity 160kVA |
| 19 | All as per items No 1 above but for DG Set of capacity 125 KVA Make : Kirloskar/CimminsNote : (a) Replacement of any new items mentioned in the servicing will be measured and paid separately under items Sr No 4.1 to 4.5 (b) Servicing will carried out through authorized service engineer of OEM. Contractor has to submit the MOU with OEM or authorized service centre by OEM to accepting officer before commencement of contract. (c) Contractor has to submit all relevant documents after carrying out A, B, C Checks to Engr In Charge. (d) Contractor has to rectified the defects within 24 Hrs after getting information from the department, if he fails to do so penalty of Rs 500 per hrs after first 24 Hrs will be charged from the contractor. |
| 20 | Supply only Spinion lub oil filter for DG Set of capacity 125 kVA |
| 21 | Supply only Fuel filter element primary for DG Set of capacity 125 kVA |
| 22 | Supply only Fuel filter element secondary for DG Set of capacity 125 kVA |
| 23 | Supply only Safety air filter element for DG Set of capacity 125 kVA |
| 24 | Supply only Primary air filter element for DG Set of capacity 125 kVA |
| 25 | All as per items No 1.0 above but for DG Set of capacity 100 KVA Note : (a) Replacement of any new items mentioned in the servicing will be measured and paid separately under items Sr No 5.1 to 5.5. (b) Servicing will carried out through authorized service engineer of OEM. Contractor has to submit the MOU with OEM or authorized service centre by OEM to accepting officer before commencement of contract.(c) Contractor has to submit all relevant documents after carrying out A, B, C Checks to Engr In Charge. (d) Contractor has to rectified the defects within 24 Hrs after getting information from the department, if he fails to do so penalty of Rs 500 per hrs after first 24 Hrs will be charged from the contractor. |
| 26 | Supply only Spinion lub oil filter for DG Set of capacity 100 kVA |
| 27 | Supply only Fuel filter element primary for DG Set of capacity 100 kVA |
| 28 | Supply only Fuel filter element secondary for DG Set of capacity 100 kVA |
| 29 | Supply only Safety air filter element for DG Set of capacity 100 kVA |
| 30 | Supply only Primary air filter element for DG Set of capacity 100 kVA |
| 31 | All as per item No 1.0 above but for DG Set of capacity 62.5 KVA Note : (a) Replacement of any new items mentioned in the servicing will be measured and paid separately under items Sr No 6.1 to 6.5. (a) Servicing will carried out through authorized service engineer of OEM. Contractor has to submit the MOU with OEM or authorized service centre by OEM to accepting officer before commencement of contract.b) Contractor has to submit all relevant documents after carrying out A, B, C Checks to Engr In Charge. (c) Contractor has to rectified the defects within 24 Hrs after getting information from the department, if he fails to do so penalty of Rs 500 per hrs after first 24 Hrs will be charged from the contractor. |
| 32 | Supply only Spinion lub oil filter for DG Set of capacity 62.5 KVA |
| 33 | Supply only Fuel filter element primary for DG Set of capacity 62.5 KVA |
| 34 | Supply only Fuel filter element secondary for DG Set of capacity 62.5 KVA |
| 35 | Supply only Safety air filter element for DG Set of capacity 62.5 kVA |
| 36 | Supply only Primary air filter element for DG Set of capacity 62.5 kVA |
| 37 | All as per items No 1.0 above hence before but for f DG Set 50 KVANote : (a) Replacement of any new items mentioned in the servicing will be measured and paid separately under items Sr No 7.1 to 7.5.(b) Servicing will carried out through authorized service engineer of OEM. Contractor has to submit the MOU with OEM or authorized service centre by OEM to accepting officer before commencement of contract.(c) Contractor has to submit all relevant documents after carrying out A, B, C Checks to Engr In Charge. (d) Contractor has to rectified the defects within 24 Hrs after getting information from the department, if he fails to do so penalty of Rs 500 per hrs after first 24 Hrs will be charged from the contractor. |
| 38 | Supply only Spinion lub oil filter for DG Set of capacity 50 kVA |
| 39 | Supply only Fuel filter element primary for DG Set of capacity 50 kVA |
| 40 | Supply only Fuel filter element secondary for DG Set of capacity 50 kVA |
| 41 | Supply only Safety air filter element for DG Set of capacity 50 kVA |
| 42 | Supply only Primary air filter element for DG Set of capacity 50 kVA |
| 43 | All as per Item No 1.0 above but for DG Set of capacity 30/25/20/15KVA Note : (a) Replacement of any new items mentioned in the servicing will be measured and paid separately under items Sr No 8.1 to 8.5.(b) Servicing will carried out through authorized service engineer of OEM. Contractor has to submit the MOU with OEM or authorized service centre by OEM to accepting officer before commencement of contract. (c) Contractor has to submit all relevant documents after carrying out A , B , C Checks to Engr In Charge. (d) Contractor has to rectified the defects within 24 Hrs after getting information from the department, if he fails to do so penalty of Rs 500 per hrs after first 24 Hrs will be charged from the contractor. |
| 44 | Supply only Spinion lub oil filter for DG Set of capacity 30/25/20/15KVA |
| 45 | Supply only Fuel filter element primary for DG Set of capacity 30/25/20/15KVA |
| 46 | Supply only Fuel filter element secondary for DG Set of capacity 30/25/20/15KVA |
| 47 | Supply only Safety air filter element for DG Set of capacity 30/25/20/15KVA |
| 48 | Supply only Primary air filter element for DG Set of capacity 30/25/20/15KVA |
| 49 | M&L for changing / topping up of best quality engine oil 15W40 for various DG sets held on charge of GE (AF) Yelahanka including removing of old burnt engine oil from DG Sets complete all as specified and directed. Make : Castrol/ Veedol/ KOEL / Servo |
| 50 | M&L for changing / topping up of best quality anti-freezing, inhabitator corrosion (Coolant) liquid for DG sets of various capacity held on charge of GE (AF) Yelahanka including removing of old burnt engine oil from DG Sets complete all as specified and directed. Make : Castrol/ Veedol/ KOEL / Servo |
| 51 | Supplying, fixing and installation of 63 Amp, 415 V, 50 Hz, 3 phase 4 wire system Controller Based ATS Panel with short circuit withstand capacity min 10 KA for 1 second, IP-54, Short circuit protection overload protection and single phase protection, phase reversal protection including wiring connection and taking down existing old unserviceable one complete all as specified and directed. Make : Kirloskar/ Cummins/ Greaves |
| 52 | Supplying, fixing and installation of 100 Amp, 415 V, 50 Hz, 3 Phase 4 wire system Controller Based ATS panel with short circuit withstand capacity min 10 KA for 1 second, IP-54, short circuit protection, overload protection and single phase protection, phase reversal protection including wiring connection and taking down existing old unserviceable one complete all as specified and directed. |
| 53 | Supplying, fixing and installation of 40 Amp, 415 V, 50 Hz, 3 Phase 4 wire system Controller Based ATS panel with short circuit withstand capacity min 10 KA for 1 second, IP-54, short circuit protection, overload protection and single phase protection, phase reversal protection including wiring connection and taking down existing old unserviceable one complete all as specified and directed. |
| 54 | S&F in repairs of fuel pipe set for engine of DG Set of capacity 250/200/160 kVA complete all as specified and directed. |
| 55 | S&F in repairs of fuel pipe set for engine of DG Set of capacity 125/100/62.5 kVA complete all as specified and directed. |
| 56 | S&F in repairs of fuel pipe set for engine of DG Set of capacity 50/25/20/15 kVA complete all as specified and directed. |
| 57 | S&F in repairs of radiator hose pipe set for engine of DG Set of capacity 200/160/125kVA complete all as specified and directed. |
| 58 | S&F in repairs of radiator hose pipe set for engine of DG Set of capacity 100/62.5 kVA complete all as specified and directed. |
| 59 | S&F in repairs of radiator hose pipe set for engine of DG Set of capacity 50/25/20/15 kVA complete all as specified and directed. |
| 60 | S&F in repairs Battery Lead of size 35 Sqmm copper single core flexible wire FR PVC insulated with thimble providing complete all as specified and directed. |
| 61 | S&F in repairs Asbestos rope (heat protectable) of existing size for exhaust hose/fume circulate pipe including taking down existing complete all as specified and directed. |
| 62 | M&L for Servicing of self-starter after taking down the same from DG Sets of capacity 250/200/160/125 kVA, transporting to workshop, opening the same and replacing the defective parts/winding including testing after repair/ servicing and refixing in original position complete all as specified and directed. |
| 63 | M&L for Servicing of self-starter after taking down the same from DG Sets of capacity 100/100/50 kVA, transporting to workshop, opening the same and replacing the defective parts/winding including testing after repair/ servicing and refixing in original position complete all as specified and directed. |
| 64 | M&L for Servicing of self-starter after taking down the same from DG Sets of capacity 15/20/25/30 kVA , transporting to workshop, opening the same and replacing the defective parts/winding including testing after repair/ servicing and refixing in original position complete all as specified and directed. |
| 65 | Supply and fixing in repairs of V belt set (for fan & alternator) for 100/125/160/200/250 KVA DG set of make Kirloskar/CG/Cummins etc all as per existing complete all as specified and directed |
| 66 | Supply and fixing in repairs of V belt set (for fan & alternator) for 15/20/25/30/50 KVA DG set of make Kirloskar/CG/Cummins etc all as per existing complete all as specified and directed |
| 67 | S & F including wiring connection and taking down existing old unserviceable one complete all as specified and directed maintenance free lead acid sealed lead accumulator (SMF) 12 volts 180 AH (battery) and deposit to MES Store Yard complete all as specified and as directed. Make : Exide/ TATA GREEN/AMARON |
| 68 | S & F in repairs maintenance free lead acid sealed lead accumulator (SMF) 12 volts 150 AH (battery) and deposit to MES Store Yard complete all as specified and as directed. Make : Exide/ TATA GREEN/AMARON |
| 69 | S & F in repairs maintenance free lead acid sealed lead accumulator (SMF) 12 volts 100 AH (battery) and deposit to MES Store Yard complete all as specified and as directed. Make : Exide/ TATA GREEN/AMARON |
| 70 | M & L in repairs of locks for sound proof canopy of any make as per recommendation of OEM. |
| 71 | Supply and fix in repairs of electronic sensor suitable for DG Set of capacity 250/200/160 KVA complete all as specified and directed. |
| 72 | Supply and fix in repairs of electronic sensor suitable for DG Set of capacity 125/100 KVA complete all as specified and directed |
| 73 | Supply and fix in repair electronic sensor suitable for DG Set of capacity 62.5/50/30/25 KVA complete all as specified and directed |
| 74 | Taking down carefully/alternator for DG Set of capacity 250kVA/200KVA/160KVA , 415 V , 3 Phase , 4 wire system and designed on 0.8 Power factor and 1500 rpm by unscrewing and disconnecting coupling shaft from prime move side , opening winding shell cleaning removing burnt field and starter winding , cleaning removing burnt field and starter winding with supper enamelled copper strip/ conductor of existing gauge , varnishing , heating / baking including reassembling all the dismantled component to its original position with testing alternator to its optimum efficiency ie 415 Volts output at 1500 rpm at 0.8 PF to the satisfaction of engineer In charge. Make : Kirloskar/ Greaves/ Mahindra |
| 75 | All as per Items No 34 above but DG Set of capacity 125/100KVA |
| 76 | All as per Items No 34 above but DG Set of capacity 62.5/50/30/25/20/15KVA Please Enable Macros to View BoQ information |
| 77 | All as per Items No 34 above but DG Set of capacity 62.5/50/30/25/20/15KVA Please Enable Macros to View BoQ information |