| 1 | Supply of Electrical panel kiosk- Explosion proof with 63A MCB - 4P, 63A RCCB - 4P , 32A MCB - 3P , 6A MCB - 1P (3Nos)As installed |
| 2 | Installation of Electrical panel kiosk- Explosion proof with 63A MCB - 4P, 63A RCCB - 4P , 32A MCB - 3P , 6A MCB - 1P (3Nos)As installed |
| 3 | Supply of cable - 5C x 10 sq.mm , FRLSH armoured copper |
| 4 | Laying of cable - 3C x 10 sq.mm , FRLSH armoured copper (25 M - Underground and remaining through open duct) |
| 5 | Supply of Termination of Cable -4C x 10 sq.mm , Arrmoured copperArmoured cable glanding with heavy duty single compressionbrass cable gland and end termination with heavy duty longbarrel Aluminium lugs |
| 6 | Termination of Cable -4C x 10 sq.mm , Arrmoured copperArmoured cable glanding with heavy duty single compressionbrass cable gland and end termination with heavy duty longbarrel Aluminium lugs |
| 7 | Supply of 3C x 2.5 sq.mm Cable for light,FRLSH arrmoured copper |
| 8 | Laying of 3C x 2.5 sq.mm Cable for light, FRLSH arrmoured copper |
| 9 | Supply of Termination of 3C x 2.5 sq.mm Cable for light,FRLSH arrmoured copperArmoured cable glanding with heavy duty single compressionbrass cable gland and end termination with heavy duty longbarrel Aluminium lugs |
| 10 | Termination of 3C x 2.5 sq.mm Cable for light,FRLSH arrmoured copperArmoured cable glanding with heavy duty single compressionbrass cable gland and end termination with heavy duty longbarrel Aluminium lugs |
| 11 | GI conduit for cable laying |
| 12 | Supply of flame proof cable gland brass - M20 |
| 13 | Installation of flame proof cable gland brass - M20 |
| 14 | Supply of flame proof cable gland brass - M25 |
| 15 | Installation of flame proof cable gland brass - M25 |
| 16 | Supply of Flame proof Light (60 W) |
| 17 | Installation of Flame proof light(60 W) |
| 18 | Supply of Flame proof wether proof junction box |
| 19 | Installtion of Flame proof wether proof junction box |
| 20 | Supply of Flame proof wether proof rotory switch |
| 21 | Installtion of Flame proof wether proof rotory switch |
| 22 | Supply of Multifuction meter |
| 23 | Installation of multifunction meter |
| 24 | Supply of Current transformer |
| 25 | Installation of current transformer |
| 26 | Supply of GI pole 6 meter |
| 27 | Installation of GI pole 6 meter |
| 28 | Supply of FRLSH (Armoured Aluminium) Conductor: Aluminium No. of Core:3 and 4sq mm Insulation: XLPE Inner Sheath: PVC Armouring: Flate/Round G.I. Strip Outer Sheath: PVC Voltage Grade: 650/1100V |
| 29 | Laying of FRLSH (Armoured Aluminium) Conductor: Aluminium No. of Core:3 and 4sq mm Insulation: XLPE Inner Sheath: PVC Armouring: Flate/Round G.I. Strip Outer Sheath: PVC Voltage Grade: 650/1100V |
| 30 | Supply of of LT cable end termination compression gland and Heavy duty Aluminium long barrel lugs for 3x4 sq. mm size of PVC insulated and PVC sheathed/ XLPE aluminium conductor cable of 1.1 kV grade as required.( Including supply of gland and lugs as required ) |
| 31 | Making end termination with compression gland and Heavy duty Aluminium long barrel lugs for 3x4 sq. mm size of PVC insulated and PVC sheathed/ XLPE aluminium conductor cable of 1.1 kV grade as required.( Including supply of gland and lugs as required ) |
| 32 | Supply of flame proof 24 inch wall fan with aluminium body , variable speed with ocsillation complete accessories as required. |
| 33 | Installation of flame proof 24 inch wall fan with aluminium body , variable speed with ocsillation complete accessories as required. |
| 34 | Supply of flame proof surface mounted 20W, 1700-2100 lumen output, 230V AC, single phase, 50 Hz, 1200mm length, T5 LED tube integral light fittings with metal body complete accessories including inbuilt LEDdrive, LED tube etc. as required. |
| 35 | Installation of flame proof surface mounted 20W, 1700-2100 lumen output, 230V AC, single phase, 50 Hz, 1200mm length, T5 LED tube integral light fittings with metal body complete accessories including inbuilt LEDdrive, LED tube etc. as required. |
| 36 | Supplying of 10 SWG Copper wire at 0.50 meter below ground level / surface for conductor earth electrode, including connection/ termination with Cu. Lug etc. as required. |
| 37 | Laying of 10 SWG Copper wire at 0.50 meter below ground level / surface for conductor earth electrode, including connection/ termination with Cu. Lug etc. as required. |
| 38 | Maintenance free Earthing -Providing of maintenance free Earthing system comprises of molecularly bonded copper of 99.9% purity on low carbon steel of 3m length , having a diameter of 20mm with copper bonding thickness of 250 microns with with fault current withstand capability of 20 KA rms value for 1 second and I peak of 50 KA. Universal Clamp should be exothermic moulded alongwith earth rod. Earth enhancing mineral compound is used for improving the soil conductivity. The material shall be mineral inert to sub soil and shall not pollute the environment and non corrosive to earth rod. The material should have a resistivity less than 0.2 Ωm. It should be free from hazardous substances The mineral compound is required to have minimum 20 Kg of the total composite. If using chemical compound min 37.5 Kg is required. Polypropylene &Polyethylene Earth electrode inspection chamber with heavy duty cover should be used to cover the Earth Rod. The dimension shall be 170mmx 170mmx 170mm with a weight bearing capacity of 50KN. |
| 39 | Maintenance free Earthing - fixing of maintenance free Earthing system comprises of molecularly bonded copper of 99.9% purity on low carbon steel of 3m length , having a diameter of 20mm with copper bonding thickness of 250 microns with with fault current withstand capability of 20 KA rms value for 1 second and I peak of 50 KA. Universal Clamp should be exothermic moulded alongwith earth rod. Earth enhancing mineral compound is used for improving the soil conductivity. The material shall be mineral inert to sub soil and shall not pollute the environment and non corrosive to earth rod. The material should have a resistivity less than 0.2 Ωm. It should be free from hazardous substances The mineral compound is required to have minimum 20 Kg of the total composite. If using chemical compound min 37.5 Kg is required. Polypropylene &Polyethylene Earth electrode inspection chamber with heavy duty cover should be used to cover the Earth Rod. The dimension shall be 170mmx 170mmx 170mm with a weight bearing capacity of 50KN. |
| 40 | Supply of wiring for light point/ fan point/ exhaust fan point/call bell point with 1.5 sq. mm FRLS PVC insulated, 650V, copper conductor single core cable in surface / recessed with 20mm medium class, ISI marked PVC conduit / casing and capping, with one way modular switch, modular plate, suitable size modular PVC/GI box and earthing the point with 1.5 sq. mm FRLS PVC insulated, 650V, copper conductor single core cable (Green) etc. as required. Note: Upto 5Mtr length from Switch board to point |
| 41 | Wiring for light point/ fan point/ exhaust fan point/call bell point with 1.5 sq. mm FRLS PVC insulated, 650V, copper conductor single core cable in surface / recessedwith 20mm medium class, ISI marked PVC conduit / casing and capping, with one way modular switch, modular plate, suitable size modular PVC/GI box and earthing the point with 1.5 sq. mm FRLS PVC insulated, 650V, copper conductor single core cable (Green) etc. as required. Note: Upto 5Mtr length from Switch board to point Please Enable Macros to View BoQ information |