| 1 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.(Drain pipes for IDU of AC) |
| 2 | 25 mm |
| 3 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 4 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 5 | 4 X 4 sq. mm + 2 X 4 sq. mm earth wire |
| 6 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 7 | 6 way , Double door |
| 8 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 9 | Single pole |
| 10 | Triple pole and neutral |
| 11 | Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 A, “C” curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 12 | Supply, installation, testing and commissioning of following capacity and rating wall mounted split Air conditioner, inverter type fitted with rotary compressor operating on 230v ± 10%, 50Hz single phase AC supply with evaporator and condensing unit made of copper tubes , cordless remote control, copper piping for both suction and discharge of upto five (05) meters length with protection covering for piping , power and control cabling as per site requirement, outdoor stand duly painted, comprising of following etc. complete as per requirement including first charge of refrigerant. a) Insulated copper pipe lines liquid and suction lines as per manufacturer recommendation.b) Flexible copper cable between indoor & outdoor unit of suitable size as per manufacturer recommendation. c) Drain pipe. |
| 13 | 1.5 TR capacity, 5 star rating |
| 14 | 2 TR capacity, 5 star rating |
| 15 | Supplying, Installation, Testing and Commissioning of Air Cooled Floor standing Tower type split Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), R-32/R-410/R-407C Green Refrigerant, wireless Remote control, suitable for working between 180-260V with low & high voltage cutoff and 50 hz ,1 phase/3 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary with min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). as specified. The system shall be able to deliver 100% of the rated capacity as per relevant IS Code. The lab testing reports as per IS: 1391 shall be submitted from National Accreditation Board for Testing and Calibration Laboratories (NABL) accredited as per International Electrotechnical Commission (IEC) 17025 standards / Central Power Research Institute (CPRI)/ Electrical Research and Development Association (ERDA)with Original Equipment Manufacturer (OEM) etc. complete as per CPWD specification and as per IS: 1391 as required.Cooling Only |
| 16 | 04 Ton BEE 5 Star rating |
| 17 | SITC of wall mounting type of following capacity automatic line voltage stabilizer having range of 180V to 275V (minimum) single phase, 50Hz with steady single phase output voltage with built in time delay, high and low voltage cut-off with connecting 3 core cable of 1 meter length complete etc. as per site requirement. Make: V Guard or equivalent. |
| 18 | 4 KVA single phase |
| 19 | 5 KVA single phase |
| 20 | Providing & Fixing of pre-fabricated stand for keeping outdoor units of 1 Ton/1.5 Ton / 2 Ton Capacity split type AC as required. |
| 21 | Fabrication of stand/Pedestal for keeping the indoor/out door unit of split type AC of various capacity made of suitable size of M S Angle and painting with one coat of red oxide and paint as required. |
| 22 | Providing and fixing of refrigerant copper pipes of following sizes (Suction & delivery) of split type AC i/c providing electrical cables, insulation, extra gas charging , cutting, drilling holes on the wall for passing gas pipes , fixing suitable size PVC pipe on the wall through the holes and cementing, painting to give an even look and smooth finish and covering with PVC non adhessive tape over the insulation of refrigerant pipes and as per the direction of E-in-C. |
| 23 | Refrigerant pipes of Sizes 3/4\\" & 1/2\\" Please Enable Macros to View BoQ information |