| 1 | STADIUM FLOOD LIGHT WORK |
| 2 | Laying of one number PVC insulated sheathed / XLPE LT cable of 1.1 KV grade of following size 4Cx16sqmm sqmm direct in ground including excavation, sand cushioning, protective covering /HDMI PIPE and refilling the trench etc as per specification required. |
| 3 | Trench size: 600mtrx.450mtrsx.750mtrs |
| 4 | Supplying and fixing cable route marker with 10 cm X 10 cm X 5mm thick G.I. plate with inscription there on, bolted /welded to35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing thesame in ground as required |
| 5 | Supply ,Testing & commissioning of LT XLPE insulated Aluminium conductor steel armoured 1.1kv grade cable size of 4 Cx 16 sqmm with requisite no's of lugs for connection of cable at both ends of LT panels etc |
| 6 | Supply and fixing of GI Horizontal bracket on top of the poles for the instalation of integral flood lighting luminarie at 9 mtrs long pole for 02Nos Of flood lights. The length and dia of adustable bracket is such that it should be well fixed on top of the pole of mast give on aesthetic look to the mast with suitable holes for mounting of flood light and supported by hollow pipe to routing of connecting cable its as required. |
| 7 | Supply ,eraction , testing and commissioning of integral flood lighting luminaire with pressure dia cast aluminium housing (IP66)LED 300 W FLOOD LIGHT including assembling and making connection as reqd |
| 8 | Supply & fixing of dust and water proof box of size 250mm X 200mm X 150mm of SWG 16mm sheet cables looping box with the suitable clamps,nuts,bolts and locking arrangments including providing and fixing of 1No. 6A MCB with carrier/ base and 4 Way 60A terminal block to receive PVC armoured cable ,complets as required. |
| 9 | Supply anf fixing of GI pipes ( Class B) 40mm dia 1.5mtr length (vertical) along the poles for protection of UG cable |
| 10 | Supply Installation Testing and commisssioning of Low Voltage Outdoor Panel ( feeder pillar) IP55 suitable for operation on 415V 50Hz supply fabricated out of 1.6mm thick CRCA sheet in double door construction having base framw made of 40x40x5mm MS angle of 600mm height. The panel shall have following components : |
| 11 | Incomer : 1 No. 63A 4P MCCB 25kA with Icu=100%Ics with set of spreaders and extended rotary handle |
| 12 | 1 Set LED Indication for 3 phases with control MCBs and wiring |
| 13 | Busbar : EC Grade Aluminium of 120A TPN on DMC insualtors |
| 14 | Outgoings : 32A 4P MCB 10kA - 4 Nos with terminal blocks of 25sqmm for cable connections. |
| 15 | Earthing terminals shall be provided on the panel. |
| 16 | Supply and drawing following size of FRLS PVC insulated copper conductor , single core cable in the existing surface/recessed steel /PVC conduit as reqd. |
| 17 | 3x2.5 sqmm (From tubular pole to LED light for providing supply to flood lights) |
| 18 | STREET LIGHT FROM AUDITORIUM TO GATE NO.2 |
| 19 | Supply , installation, testing and commissioning of 2 core LT, AB Cable of size 16 mm2 with 25 mm2 messenger wire for supporting the AB Cable. |
| 20 | Supply , testing and installation of streetlight IPC Suitable for 16 mm2 cable as per IS-NFC-33-020 AND TESTING as per NFC-33-004.(coplete box with suitable busbar and MCB) |
| 21 | Supply and installation of allied clamps for holding the cable (suspension type and tension type) |
| 22 | Supply and drawing following size of FRLS PVC insulated copper conductor , single core cable in the existing surface/recessed steel /PVC conduit as reqd. |
| 23 | 3x1.5 sqmm (From tubular pole to LED light for providing supply to flood lights) |
| 24 | Supply Installation Testing and commisssioning of Low Voltage Outdoor Panel ( feeder pillar) IP55 suitable for operation on 415V 50Hz supply fabricated out of 1.6mm thick CRCA sheet in double door construction having base frame made of 40x40x5mm MS angle of 600mm height. The panel shall have following components : |
| 25 | Incomer : 1 No. 63A 4P MCCB 25kA with Icu=100%Ics with set of spreaders and extended rotary handle |
| 26 | 1 Set LED Indication for 3 phases with control MCBs and wiring |
| 27 | 1 Set Astronomical Based Time Switch with 60A 4P Contactor and provision for Auto manual operation of the circuit with control wiring push button, auto manual switch control MCBs terminal blocks. Provision for Manual operation through remote shall be kept in the incomer circuit.Over voltage protection voltage and TPN surge voltage protector shall be provided. |
| 28 | Busbar : EC Grade Aluminium of 120A TPN on DMC insualtors |
| 29 | Outgoings : 32A 2P MCB 10kA - 6 Nos with terminal blocks of 25sqmm for 2 core cable connections. |
| 30 | Earthing terminals shall be provided on the panel. |
| 31 | Supply Installation Testing and commisssioning of Low Voltage Outdoor Enclosure as cut point enclosures for pole mounting, suitable for operation on 415V 50Hz supply fabricated out of 1.6mm thick CRCA sheet. The panel shall have following components : |
| 32 | 3 sets Loop in Loop out Terminal Blocks of suitable size to terminate 3nos 2 core cable at the cut points. |
| 33 | Outgoings : 16A DP MCB 10kA - 2 Nos |
| 34 | Earthing terminals shall be provided on the panel. |
| 35 | SITC OF CHEMICAL EARTHING: GI Electrode of 50 mm Dia 3 Mtr length with 50 KG BFG along with PVC /FrP pit cover and 40x6 mm GI bus bar for connection ; CPRI approved and with NABL certification including providing and fixing of GI STRIP (25X4)MM AS required. Make JMV/GMAX/SHOBIT (Complete job) |
| 36 | Supply of LED based 30-35W Street light fitting, housing made up of pressure die cast LM 6 Alloy/ Antidust exposed Lens, minimum system efficacy of 100 lumen/Watt and a minimum system lumen output of 3500 lumens, CRI of minimum 70; Color temparaure should be of 5700K, Ingress Protection of IP66 (lamp and gear Compartment both), mechanical impact resistance of IK-08. The fixture driver should have an operating voltage range of 140-270 V, surge protection of >=4KV, PF >0.9 and THD<10%. The LED driver should have Fixed output, High Cut @325V , capable to withstand 440V for 8 Hrs and and Auto Restart function should also be available within the fixture. |
| 37 | Branch cutting of trees all along the circular street light road whereever required |
| 38 | SHIFTING and installation of 30 w solor street lights from MAC - AUDITORIUM (28 NOS)TO GATE no. 1- Guest house park . And vice versa(shifting of 35 w street light from Gate no. 1 - guest house park to MAC - Auditorium) Please Enable Macros to View BoQ information |