| 1 | Taking down,dismantling and removal of Existing PCC street light pole of any size, height including breaking of PCC foundation upto ground level,and removal of debris from site ,Disconnection and removal of power cables, LED Light fittings AND FRP junction boxes without any damage for refixing the LED light fittings if serviceable complete all as specified and directed. |
| 2 | Excavation in trenches n.exc 1.5 m wide and n. exc 1.5 m in depth and getting out in soft/loose soil for removing/laying of cables complete all as specified and as directed by Engineer-in-charge. |
| 3 | Returning, filling in including spreading , leveling , watering and well ramming in layers n.exc 25 cm with soil complete all as specified and as directed by the Engineer-in- Charge. |
| 4 | Removing excavated material to a distance n.exc 50 m and depositing where directed at a level n.exc 1.5 mtr above the starting point complete all as specified and as directed by Engineer-in-Charge. |
| 5 | Supply,Laying,Testing & commissioning of LT XLPE insulated,Screened,PVC bedded galvanised steel strip or wire armoured,electric power cables with aluminium stranded conductor,1100 volts,grade cross sectional area 4 x 10 sqmm confirming to IS : 7098(part-I) -1988 including taking down old LT UG cables of any size all as specified and directed by the Engr-in-Charge. |
| 6 | Supply and laying of DWC (Double Wall corrugated) HDPE pipe ISI marked confirming to IS-16205 Part-24, of inner dia of 32 mm(OD 40mm) polythylene with smooth internal and profiled external surface for non pressure under ground cable complete including couplers and fittings and taking down old DWC pipes complete all as specified.Make: Telerex/Supreme/Gemini |
| 7 | M&L for reinforced cement concrete foundation of size 0.4x0.4x1.0m for 4m tubular Poles 1:2:4, type B-1 (using 20mm graded stone aggregate) including necessary reinforcement as directed by Engineer in Charge, complete all as specified and directed.(For Pole Foundation)Note: The rate quoted shall be inclusive of formwork, reinforcement bars etc.Earth work and excavation shall be mesaured and paid seperately |
| 8 | Supply and drawing through the pole for making connections to the light fittings,three core,PVC insulated and sheated, Heavy duty,1100 volts grade,multistranded copper conductor(FRLS) cable 3Cx1.5 sqmm, complete all as specified and directed |
| 9 | Supply and fix swaged type tubular pole decorative type made of MS(mild steel) material of thickness not less 3mm made with PU (polyutherene) coated coloured paint Miami Type decorated suitable for pathway/street light pole having height 4 mtr having dia size minimum 3\\" and inbuild junction box metal door open Provision with 4 way connector bolt and MCB SP 6A complete all as specified and directed by the Engineer-in-Charge. Make : Luker/Suncity/ Havells. Note: (a) The above pole cost Including of J bracket bolt of 04 Nos, with base plate of size 200x200x16 mm Thick inluding GI Nut bolts, washers & fixtures etc.(b) The rate quoted shall also be deemed to be included the cost for provision of 50mm bore PVC pipe from cable trench to centre of the pole concrete.(c) The cost of earth work & excavation , RCC foundation will measured and paid seperately. |
| 10 | Supply and fix Decorative LED Street lantern/Luminar set 30 watt warm white colour multi LED lamp of Sphere shape IP 65 trasperent acrylic with reflectors protection provision along with inverted U shape arm with decorative design as per below cat part mentioned made up of die cast polycarbonate body complete all as specified and directed. Make :-Luker Catpart No LPL30H BK or equivalent specifications of Suncity/Havells /Crompton, complete all as specified and directed by the Engr-in-Charge. |
| 11 | Supply, install, test & commissioning of LT Feeder pillar box double door, outdoor type made out of 3.15 mm thick CRCA sheet and fixed by means of suitable nut bolts and clamps cubical type as per is rules with IP 54 protection suitable for 3 phase 4 wire 50 Htz 500V weather proof vermin proof, internal connection with copper cable ,chromium plated brass cable gland duly painted with 2 coats synthetic enamel paint over a coat of red oxide primer, LT danger notice plate 200 mm x 150 mm made of mild steel at least 1.6mm thick & vitreous enamelled white on both sides and with inscription in signal red colour with skull & bone on front side, 440 V grade, suitable for and consisting of following including taking down old LT pillar box:Location : Near Porta Cabins Bldg. Make : C.P.R.I Approved( INCOMER) (a) MCCB,100Amps, 16 KA 4 pole, - 1 NoBUS BAR CHAMBER(b) Bus bar aluminium of suitable size,of current rating upto 200 Amps with color coded(R,Y,B,N) heat shrinkable sleave and shall be mounted on non hygroscopic, non combustible, track resistant, high strength DMC material, interconnection of all incomings & outgoings. INSTRUMENT CHAMBER :- (i) Digital Multifunction Meter- 01 Set. (ii) Red,Yellow,Blue Phase indicating Lights LED type 220V AC- 1 Set. (Set of three).(iii) Protection MCB 6 A SP C Series- 1 Set. (Set of three).(iv) CT 100/5A Set of -03Make of Metering Accessories :-L&T/ AE/ Trinity/ Schneider.OUTGOINGS:(a) MCCB, 63 Amps, 16 KA 4 pole, - 4 No,(b) MCB, TPN 20 Amps, 16 KA 4 pole, - 1 No, (c) MCB SPN 32 amp,10KA B series - 01 No. |
| 12 | Supply, installing ,testing and commissioing factory made and tested LT Outdoor Street Light Timer Panel with having platform mounted,suitable for 415 Volts 3 Phase and neutral 4 wire,50 HZ AC supply system shall be dust and vermin proof,protection class(IP-54) and made of 3.15 mm thick stainless steel sheet 316 grade & suitable framework/Support made out of 40x40x5 mm MS Iron angle frame ,front opening type with aprons for cable entry,with proper ferrul and cable gland,internal wiring with PVC insulated multistranded copper conductor FRLS Cable of adequate size but not less than 4 sqmm complete. The scope of work also comprising of the following including taking down old timer panel:-(i) RYB Phase indicating LED type -01 set. (ii) MCB TPN 40Amps 4 polez,10 KA,50 HZ,415 Volts-01 No (iii) Power contactor 3 Pole,40 Amps.50 Hz,415 Volts-01 No. (iv) Time switch Digital Type,one dial daily,240/415 Volts,50 Hz-01 No. (v) Auto/Manual selector switch 6A-01 No.(vi) RED Phase indicating light LED Type -01 NoLocation : B Zone S/S and High Mast LightMake : Universal Switchgear or CPRI approved confirming to IS specifications |
| 13 | M& L Earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6 mm thick , buried directly in ground (earth pit not less than 2.25 mtrs deep below ground with the top edge of the earth plate at depth not less than 1.5 mtr below normal ground level, connected using galvanized iron strip 32 x 6mm as earthing lead by means of bolts, Nuts, check nuts, and washer of galvanized iron or steel provision of 15 mm dia GI pipe light grade for protection of GI wire & 20mm dia. GI pipe medium grade for watering arrangement and PCC (1:3:6) , type C1 chamber, MS funnel ,wire gauge, 50mm thick RCC 1:2:4 TMT bars on both ways including necessary excavation in any type of soil returning filling in removal of surplus soil to distance n.exc. 50m complete all as shown in electrical plate no 5 of schedule part-1 2009 all as specified and directed. all as shown in electrical plate no-5 connected to earthing test point incl excavation all as specified or indicated including testing on completion,complete all as directed. Please Enable Macros to View BoQ information |