| 1 | Supplying and fixing 415V, 100A TPN SFU with sheet steel enclosure on flat iron/angle iron frame on wall with nuts bolts etc incl. S & F 3 nos. DIN type HRC fuse as per rating |
| 2 | Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Brand approved by EIC) of the following sizes in the prelaid polythene pipe and by the prelaid GI fish wire and making necy. connection as required |
| 3 | (a) 3 x 22/0.3 (1.5 sqmm) |
| 4 | (b) 2x84/0.3 (6 sqmm) + 1x56/0.3 (4 sqmm) as ECC (for SPN DB) |
| 5 | (c) 4x126/0.4 (10 sqmm) + 2x80/0.4 (6 sqmm) as ECC) for AC |
| 6 | Cutting Channel of size (40 mm x 40 mm) on masonry wall by Electric operated cutting machine incl. supplying & fixing heavy gauge 19 mm, 3 mm thick Polythene pipe by means of anchoring chemical (Hilti/Sika) and GI 'U' hooks of 8 SWG incl. supplying and drawing 18 SWG GI wire as Fish wire and mending good damages to original finish by using own tools and tackles |
| 7 | (a)19 mm dia 3 mm thick polythene pipe without earth continuity wire |
| 8 | Supplying and fixing PVC Rigid Conduit 'FR' [Precision Make] on wall, ceiling with saddles and other accessories as required and mending good damages to building works |
| 9 | (b) 25 mm dia 3 mm thick polythene pipe without earth continuity wire |
| 10 | Supply & Fixing 240 V, 6 A, 3 pin Modular type plug socket (Brand approved by EIC) with 6A Modular type switch, without plug top on 4 Module GI Modular type switch board with 3 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc |
| 11 | Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes. |
| 12 | (a) 1.5 sqmm |
| 13 | (b) 4 sqmm |
| 14 | ( c ) 6 sqmm |
| 15 | (d) 10sqmm |
| 16 | Supply of 2/4 Core XLPE Insulated & Sheathed Armoured stranded Aluminium Conductor cables for Working Voltage up to 1100 Volts of following sizes [Make Polycab / RR / Havells/ Gloster as approved by E.I.C] 4 Core 35 Sqmm |
| 17 | Laying of cable from 3/3½ core 35 sqmm to 50 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making holes etc. as necy., mending good damages and painting |
| 18 | Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below: 4 Core 35 Sqmm |
| 19 | Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials :4 Core 35 Sqmm |
| 20 | Supplying and fixing 4 way double door Vertical TPN MCB Distribution board for MCCB incomer with IP-42/43 protection on wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment (Legrand/ABB/Siemens), 4way, with S&F 4 pole 100A MCCB of breaking capacity 25kA/35kA as incoming and 4 nos. 415V 63A TP MCB of breaking capacity 10kA and C characteristics as outgoing. |
| 21 | Supplying and fixing 2+10 Way double-door SPN MCB Distribution Board with IP-42/43 protection, with DP isolators as incomer and SPMCB('C' Curve,10A) as outgoing,fixing at flat iron frame on wall &mending good the damages to original finish; inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. (Make: Legrand/ABB/ Siemens) --i) with S&F 240V 40Amps DPMCB isolator as incomer and 240V 6-32A SPMCB of Breaking capacity 10KA & C characteristics 10 nos as outgoing, |
| 22 | Supplying and delivery of LED Industrial Batten light made of CRCA Sheet Body (Thickness ≥ 0.50 mm) and construction as per relevant IS, along with LED lamp (Opal finish polycarbonate housing with Aluminium end-cap) voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range 0o to 40o C, internal surge protection of 2.5 KV(internal) with Short & Open circuit protection , THD < 10% , P.F.≥0.9, IP20, CRI >80, and minimum 40000 Burning Hours (Life projection shall be calculated as per TM-21 methodology), CCT 5700°K /6500°K, and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.). |
| 23 | Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing, with Minimum 5 year OEM warranty. All test report except L80 should be from 3rd party NABL accredited Lab as per BIS shall be submitted. (System lumen efficacy ≥115 lm/Watt) (Make - Philips / Crompton / Wipro) -- Single fittings along with S/F of 1 no. 18-20 W LED lamp as per specification |
| 24 | Fixing only lamp on existing fittings |
| 25 | Supply & delivery of 230 V, 50 Hz, single phase, 52 watts, 48\\" (1200 mm) Sweep, speed 320 rpm (minimum), A.C. Ceiling Fan and class of insulation: B, 3 nos. metal (Aluminium alloy) blades, 30 cm long down rod (14 SWG & higher thickness), 2 nos. canopies, safety rope, copperwinding, steel/Al body. Power Factor not less than 0.9 and minimum air delivery 210 cu.m/min (minimum), without Regulator including capacitor with safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for compliant to IS 374:2019 and external connections with 1.5 sq.mm FR, PVC insulated copper conductor single core cable and earthing etc. as required (Make - Crompton / Usha / Orient ) [ BEE star rated] |
| 26 | Fixing only ceiling fan complete with blades, canopy, fork, rubber bush etc. incl. S&F connecting wire for down rod upto 30 cm incl. painting the rod with approved paint and making necessary connection as required by 2x1.5 sqmm flexible copper wire |
| 27 | SITC OF RAC MACHINE |
| 28 | SITC of air-cooled Hi-Wall SAC of following capacities comprising Indoor and Outdoor Units with factory-charged Rotary/Scroll compressors (R-32/R-410A) incl surface / concealed copper refrigerant piping insulated with closed-cell elastomeric nitrile rubber insulation and wrapping tape (up to 3 m), FRLS type copper power cable (up to 3.5 m) with suitable plug top, 3 meters of drain pipe, and wireless remote control with suitable battery. |
| 29 | The system shall operate on 230V, 50Hz (±tolerance as per applicable standard), single-phase AC supply, providing cooling, dehumidification, and air circulation functions conforming to IS-1391 (Part-II ) with all amendments, and shall be capable of efficient performance at outdoor ambient temperatures up to 50°C, with a minimum 5- year OEM warranty on both the compressor and PCB. The system shall be installed with S&F appropriate fixing arrangements as per OEM recommendations, including wall openings, mending well the damages and making necessary connections including T&P & labour etc as required complete in all respect as per the direction of EIC.(Make- O- General/Mitsubishi electric /Mitsubishi Heavy/Daikin) |
| 30 | A) Cooling Capacity- 5.2 kW (Minimum) , Air Flow Rate:600 CFM (Minimum) Minimum ISEER - 5.0, BEE level - 4-Star(min) |
| 31 | B) Cooling Capacity- 6.1 kW (Minimum) , Air Flow Rate:800 CFM (Minimum) Minimum ISEER - 5.0, BEE level - 4-Star(min) |
| 32 | S&D of Concealed type split AC machines (a set of full metal 4 body indoor and outdoor unit) having Cooling Capacity range (26.4 KW 27.2 KW), with fixed speed rotary compressor, refrigerant gas R32/R410,minium Air flow range CFM (2800-3000) or better, both condenser and cooling coils made of copper tube connecting chord with plug top confirming to IS 1391 (Part-I & Part-II) with all amendments.(Make Mitsubishi Electric/ Daikin/ OGeneral/ Carrier/ LG/Panasonic/Johnson Controls (Hitachi) / Toshiba/ Sharp/Mitsubishi Heavy/Voltas) [ Librery Hall ] |
| 33 | S&D of Concealed type split AC machines (a set of full metal body indoor and outdoor unit) having Cooling Capacity range (17.5 KW 18.0 KW), with fixed speed rotary compressor, refrigerant gas R32/R410,minium Air flow range CFM (2800-3000) or better, both condenser and cooling coils made of copper tube connecting chord with plug top confirming to IS 21391 (Part-I & Part-II) with all amendments. (Make Mitsubishi Electric/ Daikin/ OGeneral/ Carrier/ LG/Panasonic/Johnson Controls (Hitachi) / Toshiba/ Sharp/Mitsubishi Heavy/Voltas)[ Librery Hall ] |
| 34 | Installation Testing & Commissioning of Indoor & Outdoor unit of above Hi wall split AC Machine after making hole in wall etc as per direction of EIC including making arrangement for outdoor unit by suitable size angle iron frame as per direction of E.I.C |
| 35 | Supply & laying Drain Water piping work out of PVC / HDPE hard pipes of 25 mm dia. incl. fitting, accessories, bends, elbows, tees, flanges, tapings, wall sleeves, hangers, supports, anchors. |
| 36 | Supply, installation & Commissioning of hard/soft copper refrigerent pipe line with 9mm nitral rubber insulation and Al foil tape complete with fittings,elbows bends, supporting arrangements on wall (Make- Uniflow /Rajco/Nippon/Venum ) |
| 37 | Liquid Line(3/8\\" OD with 0.6mm thick) [ for 5 TR7.5 TR/7.5 TR] |
| 38 | Liquid Line(1/4\\" OD with 0.6mm thick) [ for 1.5 TR/2 TR] |
| 39 | Suction Line(5/8\\" OD with 0.7mm thick) [ for 1.5TR/2TR/3TR/ 5 TR/7.5 TR ] |
| 40 | Suppying , Fabricating & Fixing 3 nos. MS u- Channel of 6mm thick of Size (75mm x 40mm x 40mm) for making platform for Installation of outdoor unit of 7.5 TR Concealed split Incl. drilling 2 nos holes in each channel incl. cutting holes into the wall & grouting the same with cement concreate(1:1 1/2:3) etc. fabricated with horizontal angle of 25mm x25mm x 6mm incl. supporting angle 50mm x50mm x 6mm in each platform., for transmitting the load centrally through 2Nos. (50mm x 50mm x 6mm) Angle inserted into the exiting wall. . Area of the platform is 4 mtr x 1.2 Mtr x 1 Mtr or as per Machine configuration & load with adequate service access as per direction of EIC. |
| 41 | Supply and Fixing Al powder coated Grill (Make-Primer/Air kolkata) |
| 42 | Charges for Trap door made of Aluminiun channel & ACP sheet ( Make Audecor or PWD approved)for IDU maintenance as per direction of the E.I.C |
| 43 | Charges for drop ceiling to cover the Indoor units made of ACP 3 mm thick. ( Make Audecor or PWD approved) as per direction of The E.I.C |
| 44 | Supply & Laying of 1.1 KV. Grade 4 core 6 Sq.mm XLPE Insulated & Sheathed Armoured stranded Copper cable of following on existing cable tray or necessary saddles on wall as required as per direction of E.I.C [Make: POLYCAB / Havells / RR Kable ] |
| 45 | Supply & Laying of 1.1 KV. Grade 2 core 4 Sq.mm XLPE Insulated & Sheathed Armoured stranded Copper cable of following on existing cable tray or necessary saddles on wall as required as per direction of E.I.C [Make: POLYCAB / Havells / RR Kable] |
| 46 | Supply of XLPE Insulated & unarmoured stranded Copper Conductor control cables having following numbers of core for Working Voltage up to 1100 Volts of following sizes [Make Polycab / RR / Havells as approved by E.I.C] for IDU to ODU connection etc -- 4core 4sqmm |
| 47 | Laying of cable upto 3/4 core 25 sqmm on wall / surface incl. S & F MS saddles with earthing attachment in 10 SWG GI (Hot Dip) Wire, making holes etc. as necy. mending good damages andpainting |
| 48 | Supply and Fixing of 6 Module watherproof cabinets IP-65 -IK 09- Class II , reversible door consisting 2 position rail PVC box with supplying and fixing 32 A FP MCB Isolator on din rail of existing DBs and necessary connection.( Make- Legrand/ Hensel or Equivalant as per EIC) |
| 49 | Supply & Fixing of perforated GI cable tray with perforation not more than 17.5% suspended from ceiling incl. S&F GI connector, 6mm dia MS suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl. Al painting of MS support--- With out angle iron support [150x50x1.25mm (18SWG)] |
| 50 | Supplying and fixing 240/415 V MCB Isolator on din rail of existing DBs and necessary connection.--40 A FP [ Make- Legrand / Schneider/ABB/C&S ] |
| 51 | Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., incl supplying sockets, tapes. |
| 52 | 6 sq.mm |
| 53 | 4 sq.mm |
| 54 | S & F 415V 40A Timer controller for Three phase single control AC machine in SS double door in suitable SS enclosure with S&F following electrical accessories & front door locking arrangement with all connection by finishing the ends of 4x4 & 1x2.5 copper wire dowells solderless socket by crimping method as to GS earthing attachment on wall incl necessary connections as per direction of EIC :- |
| 55 | i) 10kA, C-Curve, 415V, 40A ,FPMCB (LT/Schnider/ABB Elegance) as incomer --- 1 No.ii) 24 Hr programmable Digital/Analog Timer (LT make cat no 67DDT0) ---- 1 Noiii) 415V, 40A, 3 pole power contractor (LT make cat no MNX 32/230V/415V) with 1 NO +1 NC additional contact block ---- 1 set.iv) ON & OFF push button switch ---- 2 Nos.v) Overload (Range 9-14A) & SPP protection --- 1Set. |
| 56 | vi) 20A Auto-Off-Bipass SPDT toggle switch (Approved/reputed make) ---- 1No. & 6A MCB for control circuit --- 3 Nos.vii) 10A SPST Moduler type switch (Make :- Legrand/Myrius) - 1 No.viii) 70V-250V, LED Indicating Lamp (Make (Siemens) -------- 5 Nosix) Outgoing connector make ELMAX (Approved/reputed make) - 1 No |
| 57 | S & F 250V 25A Timer controller for single phase single control AC machine in SS double door 2+10-way DB enclosure (Make: LK, encloser cat no DBSPN012DD) or equvalant) with S&F following electrical accessories & front door locking arrangement with all connection by finishing the ends of 2x4 & 1x2.5 copper wire dowells solderless socket by crimping method as to GS earthing attachment on wall incl necessary connections as per direction of EIC :- |
| 58 | i) 10kA, C-Curve, 240V, 25A,DPMCB (LT/Schnider/ABB Elegance) --- 1 Noii) 24 Hr programmable Digital/Analog Timer (LT make cat no 67DDT0) ----1 Noiii) 3 pole power contractor (LT make cat no MNX 22/230V) with 1 NO +1 NC additional contact block - Isetiv) 2 Moduler AC motor stater (Make:- Legrand/Myrius) ---- 1 No.v) 3Module plate with cover(Make:-Legrand/Myrius) -1 No |
| 59 | vi) 20A Auto-Off-Bipass SPDT toggle switch (Approved/reputed make) ---- INo.vii) 10A SPST Moduler type switch (Make:-Legrand/Myrius) 1 No.viii) 70V-250V, LED Indicating Lamp (Make (Siemens) 1 No.ix) Outgoing connector make ELMAX (Approved/reputed make) - 1 No.. Please Enable Macros to View BoQ information |