| 1 | Supply and Delivery of 5.0TR capacity concealed type Split Air Conditioner of rated cooling capacity of 60000 BTU/hr. with 2Nos. twin rotary compressor,2nos. IDU of rated power supply-230V-1ph-50Hz. , 1no. ODU of rated power supply-400V-3ph-50Hz. Air-flow/per IDU:- 1000CFM. ( Make: Hitachi/Daikin/O-General) [N.S] |
| 2 | Erection, Testing & Commissioning Charges for 5.0TR Air Conditioner [N.S] |
| 3 | Supply & Charging Refrigerant 410A [N.S] |
| 4 | Supply, Installation & commissioning of hard/soft copper refrigeration pipeline, complete with fittings, elbows, bends, supporting arrangement on walls (Make- Ryoku/Rajco/Mandev) For Concealed Split AC [N.S] |
| 5 | a) Suction Line (5/8\\" OD with 0.7mm thick) |
| 6 | b) Liquid Line (3/8\\" OD with 0.7 mm thick) |
| 7 | Supply & Fixing 9mm nitrile rubber tube Insulation on suction line & Liquid Line copper pipe of ductable split AC (Make-Accoflex) For Concealed Split AC [N.S] |
| 8 | a) Liquid Line |
| 9 | b) Suction Line |
| 10 | Supply and laying 1.1 KV grade flexable Control Cabling from ODU to IDU directed by EIC. [N.S] |
| 11 | a) 4 Core 2.5sq. mm. Flexable copper cable 1.1 KV Grade Make-Ploycab/Gloster/ Finilex [N.S] |
| 12 | b) 4 Core 1.5sq. mm. Flexable copper cable 1.1 KV Grade . Make- Ploycab/Gloster/ Finilex [N.S] |
| 13 | Supply and fixing flexible canvass connection for concealed split air-conditioners. [N.S] |
| 14 | Supplying, fabrication & fixing 3 Nos. M.S u-channel of 6 mm thick of size (75 mm x 40 mm x 40 mm) of 1m length for making Base Frame for installation of outdoor unit of 5.0TR Concealed split AC incl. drilling 2 nos holes in each channel including cutting holes into the wall & grouting the same with cement concrete (1:1 ½ :3) etc. fabricated with 2 Nos. horizontal angle of 50 mm x 50 mm x 6 mm of 1.2m length alongwith 2 nos. supporting Angle of 40mmx40mmx6mm of 0.7 m length vertically . [N.S] |
| 15 | Supply and fixing of Al powder coated continuous Grill [N.S] |
| 16 | Supply & laying Drain Water piping work out of PVC / HDPE hard pipes of following sizes incl. fitting, accessories, bends, elbows, tees, flanges, tappings, wall sleeves, hangers, supports, anchors.Make- Oriplast/ Supreme [N.S] |
| 17 | a) 32mm dia |
| 18 | Charges for Scaffolding arrangement including lifting for outdoor & indoor units [N.S] |
| 19 | Charges for drop ceiling to cover the Indoor Units made of Aluminium Composite Panel Board |
| 20 | Supplying,fitting & fixing in position suspended false ceiling with frame work of aluminium hollow section of size 50mm X 25mm (2.0mm thickness) combined with aluminium corners of size 38mm X 25mm, suspended by aluminium hollow tube section of size 38mm X 25mm having size of 600mm X 600mm ceiling with aluminium composit panels (ACP) - Interior grade of thickness 3.0mm comprisingof proctective film, polyester coating, primer, aluminium coil, adhesive film, polyethylene core again with one layer adhesive film, aluminium bottom coating and finally service coating as per manufacturer's specification finished with aluminium screw and silicon sealent complete in all respect including all incidental charges etc. as per direction of Engineer-in-charge.(PWD Bldg Schedule, Page No. 167, Item 22) |
| 21 | Charges for Trap Door made of Aluminium Channel frame & Aluminium Composite Board |
| 22 | SITC OF FEEDER PILLAR OUTDOOR TYPESITC of LT,Cubicle Type, double door protection cover with roof top covering for fully waterproof outdoor type on base Mounted , totally enclosed, fully compertmentalized electrical control panel suitable for operation at 415 Volt, 50 Hz,as per size, design & drawing to be approved by EIC.The panel board will be fabricated by CPRI approved panel maker as per detail specification below.The general construction of the pannel will conform to IS 8623:93 as ammended uptodate. The Degree of IP protection for the enclosure will be IP-42.It will have multi tier arrangement, having necessary cable alley at both end, with rigid and self supporting structure fabricated with sufficient no. of channels & covered by 2mm thick CRCA sheet with base structure by 75x40x4mm channel. |
| 23 | The pannel is to be properly gasketted to prevent the dust and vermin. All vertical and horizontal bus bar chamnbers are to be properly arranged and all electrical switches, busbars are to be fixed by MS nut-bolts on suitable hylam board / non - hygroscopic insulators of adequate size and dimensions. The outgoing feeder connections from respective switches are to be made at the rear side of the pannel by means of bus-bar/multicore copper cables, to be terminated on bolted type terminals for cable connections or bush insulators for bus connectionIt will be powder coated after seven tank pretreatment process.2 Nos GI strip of size as per IS shall be fixed all around the panel and will be connected to 2 nos GI earth bus bar connected to incoming earth conductor.All tests should be made for the complete panel.The following 415 / 230 Volt Open Execution Type switches with fuses & accessories will be fixed in the panel. |
| 24 | INCOMING1. 415 V, 125 A TPN Switch disconnector fuse with 3 Nos. HRC fuse - 1 Nos.( Make- L&T/ABB/Siemens)BUSBAR415 V, 200 A electrolyte grade tinned copper bus bar with vertical section of size 40 mm x10 mm +/-5% for phase & Nutral Bars.The Bus Bar shall be fixed with FRP chair & the entire bars are insulated with PVC heat Shrinkable sleeve of suitable size & color as per direction of EIC |
| 25 | OUTGOING415 V TPN Switch disconnector fuse with 3 Nos. HRC fuse Make- L&T/ABB/Siemens) with necessarynuts bolts and connectioni) 415 V, 63 A - 4 Nos.( Make- L&T/ABB/Siemens) |
| 26 | ACCESSORIESA.S&F 3Ph multifunction metering (KWH, KW, KVA, V,I,F,PF) Class 1 accuracy with RS485,screw terminals AC/DC wide Voltage power supply 110- 240V, AC ±10% ,50/60 Hz,110-250V DC ±10%(Make-L&T-WL440511OOOO)-1 Set200/5A ,10VA,CL.1 CT (Kappa/AE)- 3 no.415V, 63A, 4 Pole AC operated (L&T, Type-MCX-12, Cat. No. CS97015).( Make- L&T/ABB/Siemens) - 4 No.R-Y-B LED Indicator Lamp [Legrand/L&T] - 11 Set 6A\\"C\\" curve 10KA MCB (MK-Legrand)-01 Nos40A FP MCB -4 NosSelector switch Three step 10 Amp --Auto/ Manual/ OFF--4 No'sDigital time switch (L&T, Cat no. 67DDT0- 4 NosDanger Board |
| 27 | Inter Connection : Interconnection for power to be done by 4 bar solid copper bar by colored PVC Sleeve with insulation of following sizes:i) Incoming terminal to to Bus Bar by 20 X 5 mmii) Bus bar to Outgoing terminal 15 x 3 mm iii) Power contractor interconnection wiring 6 sqmm copper wireiv) A hylam sheet of 10mm thick of suitable size will be fitted for installation of Power contractor, Time Switch, SPMCB etcAll interconnection of metering panel to be done by 2.5 sq.mm multistranded copper wire finish with Copper socket by crimping method having marked ferrule for indication |
| 28 | Earthing-A separate earth bolt/Bars-2 Nos will be provided in panel board in both sides as per drawing.Cable alley:Cable entry arrangement will be provided in both side of the cubical panel in vertical possition with appropriate size FRP insulator to support outgoing copper bars indicating phae & Neutral for each outgoing main switches & gland plate must be placed at the bottom of the panel with detechable type as per direction of E.I.C |
| 29 | Painting:The Complete panel board shall be painted by two coats of powder coated paint over two coats of RO primer of approved make and brand and color as per direction of EIC. |
| 30 | Ordinary reinforced Cement concrete (mix 1:2:4) with graded stone chips (20 mm nominal size) and 8 mm rod excluding shuttering and reinforcement,if any, in ground floor as per relevant IS codes. (7 X 8 X 0.10) =5.6 cumRfe:- page-24 Items-4. of PWD SOR Vol-I w. e. f. 1.11.2017 |
| 31 | a) Pakur Variety. For Mechine Foundation (For four No's IDU and One No Feeder Piler Box) |
| 32 | Supply & Delivery 1.1KV grade XLPE insulated Armoured Aluminium conductor cable (Finolex/Polycab/ Gloster) [N.S] |
| 33 | 4 Core 16 sqmm (From Timer to outdoor unit) |
| 34 | 4 Core 50 sqmm (From Ground Floor panel to Timer ) |
| 35 | Laying of cable upto 4 core 25 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 10 SWG GI (Hot Dip) Wire, making holes etc. as necy. mending good damages and painting. [Page No. F-1, Item No. 2(b)] |
| 36 | Laying of cable from 3/3½ core 35 sqmm to 50 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making holes etc. as necy., mending good damages and painting [Page No. F-01, Item No.2(c)] |
| 37 | Laying of one No. cable above 35 sqmm and upto 185 sqmm in underground trench 460mm wide x 760mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per Mtr. including filling the space between the bricks and cable and also the trenchwith shifted soil, leveling up and restoring surface duly rammed.[Page No. F-02, Item No.1(b)] |
| 38 | Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below :[Page No. F-4, Item No. 7] |
| 39 | 4 Core 16 sqmm |
| 40 | 4 Core 50 sqmm |
| 41 | Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials [Page No. F-5, Item No. 8] |
| 42 | 4 Core 16 sqmm |
| 43 | 4 Core 50 sqmm |
| 44 | Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes [Page No. F-5, Item No. 9] |
| 45 | 2.5 sqmm (copper) |
| 46 | 1.5 sqmm (copper) |
| 47 | Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level By TATA-Medium GI pipe[Page No. G-1, Item No. 2(a)] |
| 48 | Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos. 12 mm dia holes on the GI pipe [Page No. G-2, Item No. 3(a)] |
| 49 | Excavation of soil for installation of Earth Electrode and filling & ramming. For Soft Soil Page No. G-1, Item No. 1(a) |
| 50 | Extra for treatment of soil by using salt and charcoal for earth electrod . [ Page No. G-2, Item No. 3(a)] |
| 51 | Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 65 mm x 8 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required [Page No. G-2, Item No. 4(d)] |
| 52 | Connecting the equipments body to earth busbar incl. S & F 25 mm x 6 mm Galvanized (Hot Dip) MS flat on wall/floor with GI saddle as required and connection to equipments with incl. drilling holes, bolts, nuts,washers etc [Page No. G-3, Item No. 5(d)] |
| 53 | N.B- The Rate to be quoted by all the bidders should be inclusive of all taxes, duties including GST & CESS etc. Please Enable Macros to View BoQ information |