| 1 | Safe loading Carriage including unloading and proper stacking of following materials from central store Barabanki to site of work. |
| 2 | 11 KV XLPE Cable 3x185 Sq.mm. |
| 3 | 11 KV 3x185 sqmm XLPE O/D Cable Box Jointing Kit |
| 4 | Earthing Set |
| 5 | GI Wire |
| 6 | PCC Pole 8.5 mtr Long |
| 7 | Top Channel |
| 8 | T-off Channel |
| 9 | ACSR Weasel Conductor |
| 10 | 250 KVA TF |
| 11 | 11 kv Composite Polymer Pin Insulator |
| 12 | 11 kv Composite Polymer Disk Insulator 45 KN T%\&C |
| 13 | 11 kv Fuse Set |
| 14 | Dropper Channel |
| 15 | Stay Set Complete |
| 16 | LV PVC Cable 3.5x240 sqmm |
| 17 | LT AB Cable (3x95+1x95+1x16) sqmm |
| 18 | LT PVC Cable 1x240 sqmm |
| 19 | Dragging of pole from Store to site |
| 20 | Grouting of Pole in depth of 1/6th the length of pole in ratio 1:4:8 in cement sand and brick ballast and construction of pole plinth 300mmx45mm above ground level in 1:2:4 in cement, coarse sand and stone grit as per respo norms. |
| 21 | Stringing and sagging of 11 KV line with ACSR Weasel Conductor including nuzzling binding and jumpering (Rabbit conductor will be provided by the department) |
| 22 | Erection of Stay set of 16x1800 mm rod duly painted with red oxide,anchor plate, thumble turn buckle and stay insulate etc. digging of pit of size of size 0.4x0.6x1.6 m for grouting 1:3:6 cement concrete, with stay of size 7/8 SWG, nuzzling & Grouting. |
| 23 | Installation of Mounting of Following capacity of Transformer including its connection between 11 KV and LT Line mounting provinding Crimping type Aluminium lugs of required size.( All the material except transformer will be arranged by the contractor) |
| 24 | Mounting of 250 KVA Tranformer |
| 25 | Errection of Substation type double pole with PCC including mounting of Top Channal Dropper Channel, base angle with clamps with nut & bolt 33/11 KV line including grouting of support and plinthing 300 mm above ground level, fitting of 33/11 KV pin & Pin insulator. 1/6 of total lenght of poles will remain under the ground and planted on stone pad of Size 300x300x75 MM. |
| 26 | Earthing by MS Earthing Rod |
| 27 | Erection of single PCC Pole for Stringing and sagging of conductor 1/6 of total length of poles will remain under the ground and planted on stone pad of size 300x300x75 mm. |
| 28 | Stringing and Sagging of LT PVC Cable (3.5x240+1x240) SQMM (Cable will be provided by the department) |
| 29 | Stringing and Sagging of LT ABC Cable (3*95+1*70+1*16) (Cable will be provided by the department) |
| 30 | Providing & Fixing of various type materials. All materials shall be supplied by the contractor. |
| 31 | GI Pipe 6'' dia |
| 32 | Nut & Bolt |
| 33 | Alum. Lug 240 sqmm |
| 34 | LT Clamp |
| 35 | Eye Hook Clamp |
| 36 | Dead End Clamp |
| 37 | Suspension Clamp |
| 38 | Laying of 11 kv XLPE Cable AL. 3x185 Sq.MM by HDD Method as per respo Norms (All the material required for laying will be supplied by the contractor except 11 kV XLPE cable) |
| 39 | Mounting of 11 kv XLPE Cable AL. 3x185Sq.MM |
| 40 | Filling of Jointing Kit |
| 41 | Hosting of 11 kv XLPE Cable AL. 3x70+3x185Sq.MM on DP with GI pipe 6\\" its Jumpring complete with clamps, nut and bolts. (All material will be Provided by the contractor except 11 kv cable & O/D J/K. as per RESPO NORMS. |
| 42 | Dismantling of 11 kV grade underground XLPE cable of any size (up to 3•185 sq.mm), including excavation of trench, removal of cable carefully without damage, coiling, loading, transportation to departmental store, unloading, stacking and accounting, complete in all respects. |
| 43 | Erection of pipe type earthng for DT with the help of B-Class G.I pipe of size 1.5 inch dia, 60 feet deep boring by providing G.I strip 50x6 MM, 6 meter long attached with clamp L-piece nut & bolt & G.I cap |
| 44 | T/F FENCING 250 KVA wir emess fencing of 11/0.4 KV substation shall be made rectangular off size as nper site requirement not exeeding 3 meter fabrication 45x45x5 mm angle material shall be supply by contracter |
| 45 | T/F PLINTH 250 KVA plinth construction 2x2x1.5 meter with brick cement etc filling wth the sand in the hollow space plastring , 2 No MS channel on the top of plinth for placement of tranceformer , |
| 46 | Construction of LT DistriBution Cum LT Protection Piller Box MS Angle in Rectangle Size 50x50x6 MM 7.5 Meter long For installation Of Henley Type Tailleness Fuse Unit 300 AMP 650 Volt For 3 nos Outgoing Circuits With 4 Nos. Copper Bus bar OF size 1000x50x6 mm Including Proper Grouting of Structure By Digging of pits Off Size 300x300x600 mm With the Help Of Cement, Coresand And Aggregate in the ratio 1:3:6 And Fabrication of structure Complete.All Material Required Will be Supplied & Fixing by the Contractor. |
| 47 | Other line work Please Enable Macros to View BoQ information |