| 1 | [11.69.2]Applying priming coats with primer of approved brand and manufacture, having low VOC (Volatile Organic Compound ) content. 2. With water thinnable cement primer on wall surface having VOC content less than 50 grams/litre [Through Rate] |
| 2 | [11.78]Painting two coats excluding priming coat with synthetic enamel paint in all shades on new wood work or metallic or plastered or concrete surfaces to give an even shade. [Through Rate] |
| 3 | [13.27]Structural steel work in single section, fixed with or without connecting plate, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. [Through Rate] |
| 4 | [13.32]Providing and fixing bolts including nuts and washers complete. [Through Rate] |
| 5 | [23.26.2]SAFETY ITEMS 2. Supply and erection of High Tension Voltage caution notice plate of size 250*200 mm in three languages. [Through Rate] |
| 6 | [24.1.1]EARTHING AND LIGHTENING ARRESTOR 1. Earthing with GL earth pipe 4.5 m long and 40 mm dia with masonry enclosures on the top etc. (but without charcoal or coke and salt) as required. [Through Rate] |
| 7 | [24.1.2]EARTHING AND LIGHTENING ARRESTOR 2. Extra for using salt and char coal/coke for pipe earth electrode as required. [Through Rate] |
| 8 | [24.1.8]EARTHING AND LIGHTENING ARRESTOR 8. Providing and fixing 25 mm x 3mm G.I. strip on surface or in recess for connections etc. as required with all labour and material. [Through Rate] |
| 9 | [24.2.1]LT CABLE 1. Supply & erection of LT phase separator on LT line complete in all respect up to entire satisfaction of the Engineer-in-charge of the work. [Through Rate] |
| 10 | [24.2.8.14]LT CABLE 8.14. Supply and erection of aluminium lugs heavy duty including crimping etc. up to the entire satisfaction of the Engineer-in-charge of the work.300 sqmm [Through Rate] |
| 11 | [24.2.8.9]LT CABLE 8.9. Supply and erection of aluminium lugs heavy duty including crimping etc. up to the entire satisfaction of the Engineer-in-charge of the work. 95 sqmm [Through Rate] |
| 12 | [24.3.4.2]HT CABLE 4.2. Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required : 150 to 185 sqmm [Through Rate] |
| 13 | [34.3.2]Printing New Letter and Figures of any ShadePrinting new letter and figures of any shade with synthetic enamel paint black or any other approved colour to give an even shade 2. English and Roman (Hyphens not to be paid) [Through Rate] |
| 14 | Supply and erection of PCC pole as per IS: 1678-1960 specifications, 11Mtr. long 140mm x 200mm at top and 140mm x 400mm at bottom with working load of 400Kg buried 2.20M in ground or as per UHBVNL specification . |
| 15 | Supply and erection of PCC pole as per IS: 1678-1960 specifications, 9 Mtr. long 105mm x 115mm at top and 105mm x 315mm at bottom with working load of 200 Kg. buried 1.80m in ground or as per UHBVNL specification. |
| 16 | Supply and erection of wooden cleats of size 4” wide and 1’-6” long complete with 4 Nos. holes suitable to pass through 300/400sqmm single core cable complete in all respect up to the entire satisfaction of Engineer-in-charge |
| 17 | Supply and erection of cradle guards made of 8 S.W.G. confirming to ISS 280/1978/1973 with latest amendments complete in all respect up to the entire satisfaction of Engineer-in-Charge. For HT Line |
| 18 | Supply and Erection of shackle insulator brown glazed (90 mm x 75 mm) Tape-I suitable for 415 /240 Volt confirming to IS 1545/1977 with latest amendment thereof |
| 19 | Supply and Erection of M.S. D-strap type-I made out of M.S Flat of size 40 x 6mm suitable for LT insulator 90 x75mm with latest amendments complete in all respect up to the entire satisfaction of Engineer-In-Charge. |
| 20 | Supply and erection of 11 KV lighting arrestor as per relevant ISS specification |
| 21 | Supply and erection of stay set for LT/HT Line complete in all respect with G.I. stay wire( rope of 7 wires of 8 SWG G.I. Wire), egg/Disc insulator , G.I. rod of 20mm dia 8’ long threaded up-to 250mm long with nut (weight 6.224 kg) with cross plate of 460mm of angle 65x65x6 mm(weight 5.33 kg), elbow (weight 2.24 kg ) complete with clamps , nuts and bolts complete in all respect up-to the entire satisfaction to Engineer-in-Charge of the work.LT Stay |
| 22 | Supply and erection of stay set for LT/HT Line complete in all respect with G.I. stay wire( rope of 7 wires of 8 SWG G.I. Wire), egg/Disc insulator , G.I. rod of 20mm dia 8’ long threaded up-to 250mm long with nut (weight 6.224 kg) with cross plate of 460mm of angle 65x65x6 mm(weight 5.33 kg), elbow (weight 2.24 kg ) complete with clamps , nuts and bolts complete in all respect up-to the entire satisfaction to Engineer-in-Charge of the work.HT Stay |
| 23 | Supply and erection of 11 KV brown glazed 10 KN pin insulator with GI pin/ silicon type as per specification and approved make by DHBVN. |
| 24 | Supply and erection of V-shape X-arm suitable for 11KV system made of out of 1650mm long MS channel of size 100x50x50x6mm as per design and drawing 2 Nos. 18mm dia holes provided in the base for fixing of half clamp made of MS flat of size 50x6mm and 2 Nos. holes 22mm dia for GI Pin on the flange plate of MS Flat of size 50x6mm shall be provided on the top and bottom flanges of both end of V-shape X-arm with 22mm hole in the plate complete in all respect including primer and aluminum paint. |
| 25 | Supply and erection of top hamper suitable for 11 Mtr. long PCC pole and 11KV system made out of MS flat size 50x6mm (A shapes) having approx weight 2.5 kg as per approved design and drawing including primer and alum paint complete all respect. |
| 26 | Supply and erection of fuse unit of L.T. side suitable for 200 KVA transformer complete with wooden board cleats, aluminum strips MS clamps and MS nut and bolts including all petty material required up-to the entire satisfaction of Engineer-in-Charge. |
| 27 | Supply and erection of ACSR conductor conforming to IS 398 (Part-II) 1976/1996, IS 4826-1976 IS 1521-1972 and IS 1778-1980 with latest amendments and erection of the same with accessories including stringing and sagging of conductor of various sizes i.e. 100mm2/80mm2/50mm2/30mm2/30mm2 PVC insulated as well as jointing and binding with insulator at supports in all respect up to the entire satisfaction of Engineer-in-Charge.100sqmm ACSR |
| 28 | Supply and erection of ACSR conductor conforming to IS 398 (Part-II) 1976/1996, IS 4826-1976 IS 1521-1972 and IS 1778-1980 with latest amendments and erection of the same with accessories including stringing and sagging of conductor of various sizes i.e. 100mm2/80mm2/50mm2/30mm2/30mm2 PVC insulated as well as jointing and binding with insulator at supports in all respect up to the entire satisfaction of Engineer-in-Charge.80 Sqmm ACSR |
| 29 | Supply and erection of ACSR conductor conforming to IS 398 (Part-II) 1976/1996, IS 4826-1976 IS 1521-1972 and IS 1778-1980 with latest amendments and erection of the same with accessories including stringing and sagging of conductor of various sizes i.e. 100mm2/80mm2/50mm2/30mm2/30mm2 PVC insulated as well as jointing and binding with insulator at supports in all respect up to the entire satisfaction of Engineer-in-Charge.30 Sqmm PVC Insulated ACSR Condt. |
| 30 | Supply and erection of anti climbing barbed wire of size 12x12 gauge (6.33 Mtr. = 1.00 kg) for 11 KV/33KV Poles complete in all respect |
| 31 | Supply and erection of L.T. Aerial bunched cable of size 120 Sqmm, 4 core plus 95 Sqmm including making of necessary connection of make Polycab, Havell’s Grandlay, complete in all respect up to the entire satisfaction of Engineer-in-charge |
| 32 | Supply and erection of Disc insulator with fitting on PCC pole of approved make of State Electricity Nigam requirement to complete in all respect to confirming to ISS 731/1971 latest amendment thereto. |
| 33 | Supply and erection of PVC insulated sheathed 50 Sqmm aluminum conductor cable single core 1100 volts grade in existing pipe, complete in all respect up to entire satisfaction of the Engineer-in-Charge of the work. |
| 34 | Supply and erection of P.G clamp Al cast 2 bolt suitable for 50/80/100 Sqmm ACSR conductor complete in all respect up to entire satisfaction of the Engineer-in-Charge of the work. |
| 35 | Supply, installation, testing, commissioning of 3 Phase 11KV/0.433 KV-250V, 200 KVA Oil immersed, naturally cooled, Aluminum Wound Outdoor type Distribution Transformers with CSP (Completely self protected) features with external micro-processor based four pole MCCB 300Amp. To 400 Amp, 50kA strictly conforming to Nigam’s technical specification No. CSC-V/R-I/DH/UH/P and D/2010-2011 read with amendment thereof and as per relevant ISS as amended from time to time and losses conforming to 4 stars rating of BEE as per Approved Specification of DHBVN/UHBVN including installation of transformer on existing platform up-to the entire satisfaction of Engineer-in-Charge.Voltage Rated Frequency Permitted at 75ºCi) Maximum load looses at 50% load at 75ºC = 780 Watt ii) Maximum losses at 100% load at 75ºC = 2300 Wattiii) Warranty = 78/72 Months shall be one time The above losses are maximum allowable and there would not be any positive tolerance. |
| 36 | Supply, stringing and sagging of 8 SWG G.I. earth wire as per complete in all respect to the entire satisfaction of Engineer-in-Charge conforming to IS 298/1978 and 7807/1973 and with latest amendment thereof. (Excluding GST) |
| 37 | Supply and erection of guards reel for LT line made of 8 S.W.G. G.I. wire complete in all respect up to the entire satisfaction of Engineer-in-Charge. |
| 38 | Supply and Erection of 11 kV G.O. Switch vertical mounted with heavy duty 9 Nos. post insulators suitable copper male and female contacts fixed on GI angle frame with G.I. Nut and Bolts including G.I. pipe and operating handle complete in all respect (Excluding GST). |
| 39 | Supply and erection of PVC insulated 300 Sqmm single core un-armoured power cable with aluminum conductor 650/1100V confirming to ISS 1554(Part-I) of 1988 IS: 7098/Part-1/1988 with latest amendments with necessary connections and complete in all respect up-to the entire satisfaction of Engineer-in-Charge of the Work. Make: Grandlay/Polycab/Havell`s. (Excluding GST). |
| 40 | S/E of cable holding clamp made out with two pieces of best quality of wood, suitable for HT 11 KV XLPE cable of size 95 sqmm to 240 sqmm x 3 core complete with cutting of wood of suitable size i.e size of one half clamp should be 100 mm width x300mm long x 100 mm high, complete with making grove of suitable size of cable i.e. 95 sqmm to 240 sqmm x 3 core, complete with suitable size nut and bolt, and applying primer and paint complete in all respect upto entire satisfaction of Engineer-in-charge of the work. (EXCLUDING GST) |
| 41 | Rate without GST for Supply and erection of 185 sqmm 3 core XLPE (E) 11 KV HT aluminum conductor armored cable armored cable ISI make laid in existing pipe/ trenchers/ surface with all labour and material required to complete the job in all respect upto the entire satisfaction of the Engineer in charge of the work.Make:- Havell`s, Polycab, Grandly. (Excluding G.S.T.) Please Enable Macros to View BoQ information |