| 1 | Taking out old unserviceable under ground PVC/XLPE LT cable of any size from trenches/ wall/ roof/ road/ pipe/ pole including segregation of serviceable bricks for re-use complete all as specified and as directed. |
| 2 | Relaying/ re routing of old serviceable under ground PVC/XLPE LT cable any grade and any size in trenches/fixed to wall/pole/roof/laid in floor including necessary connections and thimbling complete all as specified and as directed. (Earth work, brick & sand cushioning shall be measured and paid for separately under appropriate item). |
| 3 | Re-laying old PCC cover for cable protection cover, laid flat and dry in trenches over the cable , perpendicular to the direction of cable complete all as specified and as directed. |
| 4 | Supply and fix or passing through pipe/wall/floor/trenches XLPE insulated PVC bedded, galvanized steel strip or wire armoured electric power cable of size 10 Sqmm 2 core, heavy duty 1100 volts grade with glanded aluminium conductor complete all as specified and as directed. |
| 5 | Supply and fix or passing through pipe/wall/floor/trenches XLPE insulated PVC bedded, galvanized steel strip or wire armoured electric power cable of size 16 Sqmm 4 core, heavy duty 1100 volts grade with glanded aluminium conductor complete all as specified and as directed. |
| 6 | Supply and fix or passing through pipe/wall/floor/trenches XLPE insulated PVC bedded, galvanized steel strip or wire armoured electric power cable of size 25 Sqmm 4 core, heavy duty 1100 volts grade with glanded aluminium conductor complete all as specified and as directed. |
| 7 | Supply and fix or passing through pipe/wall/floor/trenches XLPE insulated PVC bedded, galvanized steel strip or wire armoured electric power cable of size 35 Sqmm 3.5 core, heavy duty 1100 volts grade with glanded aluminium conductor complete all as specified and as directed. |
| 8 | Supply and fix or passing through pipe/wall/floor/trenches XLPE insulated PVC bedded, galvanized steel strip or wire armoured electric power cable of size 50 Sqmm 3.5 core, heavy duty 1100 volts grade with glanded aluminium conductor complete all as specified and as directed. |
| 9 | Supply and fix or passing through pipe/wall/floor/trenches XLPE insulated PVC bedded, galvanized steel strip or wire armoured electric power cable of size 70 Sqmm 3.5 core, heavy duty 1100 volts grade with glanded aluminium conductor complete all as specified and as directed. |
| 10 | Supply and fix or passing through pipe/wall/floor/trenches XLPE insulated PVC bedded, galvanized steel strip or wire armoured electric power cable of size 95 Sqmm 3.5 core, heavy duty 1100 volts grade with glanded aluminium conductor complete all as specified and as directed. |
| 11 | Supply and fix or passing through pipe/wall/floor/trenches XLPE insulated PVC bedded, galvanized steel strip or wire armoured electric power cable of size 120 Sqmm 3.5 core, heavy duty 1100 volts grade with glanded aluminium conductor complete all as specified and as directed. |
| 12 | Excavation in trenches not exc 1.5 Mtr wide and not exc 1.5M depth in soft/loose soil for laying of cable, pipes etc and getting out in soft/loose soil all as specified and directed. |
| 13 | Returning, filling, including spreading, levelling, watering and well ramming in layers not exc 25cms of soil complete all as specified and directed. |
| 14 | Removing the surplus excavated material/soil to a distance not exc 50mtrs and depositing, where directed at a level not exceeding 2.5 Mtr above the starting point all as specified and directed. |
| 15 | Supply and spread sand for cushioning of cables in trenches all as specified in MES Schedule Part-I and all as directed.Note: Punned thickness only will be measured and paid. |
| 16 | Supplying and laying un-reinforced precast concrete cable cover, Class LV, Type I, flat, size 250 mm x 150mm x 40mm all as directed. |
| 17 | Supply and lay GI tubing 80 mm bore, light grade, galvanised, ISI marked with all specials for cable protection on road crossing/floor etc duly sealed at both ends after drawing cable all as specified and directed. |
| 18 | Supply and lay GI tubing 50 mm bore, light grade, galvanised, ISI marked with all specials for cable protection on road crossing/floor etc duly sealed at both ends after drawing cable all as specified and directed. |
| 19 | Earthing complete with galvanised steel earth plate electrode 60x60cm x 6.0mm thick burried directly in ground (earth pit not less than 2.25 mtr deep below ground level) with top edge of the plate not less than 1.5 mtr below normal ground level, connected to and including using of 25x4 GI strip as earthing lead by means of bolts, nuts, check nuts and washers of galvanised steel , connected to earthing test point, all as specified & indicated, including testing on completion including earth work and excavation in any type of soil/rock, PCC 1:3:6 type C1, earthing chamber, precast RCC slab 50mm thick in cement concrete 1:2:4 type B1 reinforced with welded steel wire fabric weight hot less than 4 Kg/Sqm, funnel with GI watering pipe of 20mm bore, medium grade wire mesh and lugs, GI protection pipe of 15mm bore light grade upto 7.50 mtr long test point etc all as specified and directed. |
| 20 | Material & labour for repairing existing earthing any type incl making & cleaning of earth pit, repair of pits, fixing of new funnel , pit cover, painting on pit with cement base white paint complete all as per direction of Engr-in-charge. Note: (i) Cost of funnel, pit cover, cement work, PCC work and painting etc incl is quoted rate. |
| 21 | Supply and fixing of Earth continuity strip or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 24x4 mm GI strip complete all as directed by Engr-in-Charge. |
| 22 | Material & labour for maintenance of APFC panel any type and size, dismantling opening and taking down of all incoming and outgoing cables, cutting burnt edge of the cable whatever is required, providing thimble lugs and glands of suitable required for different size of cable including taking out loop of the cables, including replacement of bolts nuts & washers and reconnecting the all incoming and outgoing connections, checking of serviceability of capacitors and testing of panels on full load all as specified and as directed. Note: Capacitors shall be measured under relevant items. |
| 23 | Supply only suitable capacitor 5 KVAR 440V complete on existing APFC Panel and testing all as specified and directed |
| 24 | Supply only suitable capacitor 7.5 KVAR 440V complete on existing APFC Panel and testing all as specified and directed |
| 25 | Supply only suitable capacitor 10 KVAR 440V complete on existing APFC Panel and testing all as specified and directed |
| 26 | Cutting of road to a width of 30cm and depth not exceeding 90cm for laying of protection pipe / cable including returning and filling, spreading levelling, watering and well ramming in layers and making good with PCC 1:2:4 type B1 for top 100mm thick complete all as specified and directed. |
| 27 | Material & labour for attending any breakdown in LT UG cable by excavating, identifying core fault and carry out jointing work including straight through heat shrinkable type joint of cable size 6-16 Sqmm 4 core complete all as specified and as directed. Note: Excavation, return filling , removal & taking down of the cable shall be measured under relevant items. |
| 28 | Material & labour for attending any breakdown in LT UG cable by excavating, identifying core fault and carry out jointing work including straight through heat shrinkable type joint of cable size 25-50 Sqmm 3.5 core complete all as specified and as directed. Note: Excavation, return filling , removal & taking down of the cable shall be measured under relevant items. |
| 29 | Material & labour for attending any breakdown in LT UG cable by excavating, identifying core fault and carry out jointing work including straight through heat shrinkable type joint of cable size 70-120 Sqmm 3.5 core complete all as specified and as directed. Note: Excavation, return filling , removal & taking down of the cable shall be measured under relevant items. |
| 30 | Material & labour for attending any breakdown in LT UG cable by excavating, identifying core fault and carry out jointing work including straight through heat shrinkable type joint of cable size 150-185 Sqmm 3.5 core complete all as specified and as directed. Note: Excavation, return filling , removal & taking down of the cable shall be measured under relevant items. Please Enable Macros to View BoQ information |
| 31 | Material & labour for attending any breakdown in LT UG cable by excavating, identifying core fault and carry out jointing work including straight through heat shrinkable type joint of cable size 150-185 Sqmm 3.5 core complete all as specified and as directed. Note: Excavation, return filling , removal & taking down of the cable shall be measured under relevant items. Please Enable Macros to View BoQ information |