| 1 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 2 | 4 x 16 sq. mm + 2 x 6 sq. mm earth wire |
| 3 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, Ics=100% Icu and Operational Voltage 690V etc. as required. |
| 4 | 125 A, 16 KA,TPMCCB |
| 5 | 100 A,30KA,FPMCCB |
| 6 | 200 A,36KA,FPMCCB |
| 7 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 8 | Triple pole and neutral |
| 9 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) |
| 10 | 8 way (4 + 24), Double door |
| 11 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required |
| 12 | Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp) |
| 13 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 14 | 3½ X 50 sq. mm (35mm) |
| 15 | 3½ X 95 sq. mm (45mm) |
| 16 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. with charcoal/ coke and salt as required. |
| 17 | Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required |
| 18 | Supplying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following sizes. |
| 19 | 3½ X 50 sq. mm |
| 20 | 3½ X 120 sq. mm |
| 21 | Supply and drawing following sizes of FR PVC insulated copper conductor,single core cable in the existing surface/recess/pVC conduit as required make Havells/Finolex/RR Kabel or equvalent |
| 22 | i) 5X35sqmm sqmm |
| 23 | Providing, laying and fixing following dia G.I pipe(medium class) in ground complete with G.I fittings including trenching (75cm deep) and re-filling etc as required |
| 24 | 50mm dia Please Enable Macros to View BoQ information |