| 1 | Fabrication, supplying, Replacement I/c buyback of existing panel,Installation testing & commissioning of Electrical control panel of cubical construction, floor mounted type, fabricated out of 2mm thick CRCA sheet, compartmentalised with hinged lockable doors, dust and vermin proof, powder coated of approved shade after 7 tank treatment process, cable alley, inter-connection with suitable size copper conductor cable/solid copper strip, having switchgears and accessories, mountings and internal wiring, earth terminals, numbering etc. complete in all respect, suitable for main fire pump, pressurisation pump & diesel pump set complete as per CPWD specification with following in coming and Outgoings, suitable for operation on 415V, 3 phase, 50Hz Ac Supply with enclosure protection class IP 42 as required :Incomings630A, 50kA 4 Pole MCCB, Ics=100% Icu rating Digital Voltmeter 0-500V with selector switch Ammeter (0-630 A) with selector swtich & CTs etc. LED type RYB phase indicating lamps, ON, OFF, trip indicating lamps Set of Copper Bus Bar 800AmpsOutgoings( Note : All outgoing feeders for pumps should have digital Ammeter with selector switches, and LED type ON, OFF, trip indicating lamps)Main Fire Pump200 A, 50kA TPN MCCB, Ics=100% Icu, with fully automatic Star/Delta starter suitable for 75 hp pump with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. - 2 Sets.Jockey Pump100 A, 50kA TPN MCCB, Ics=100% Icu, with Suitable HP fully automatic Star/Delta starter with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, Auto/manual/OFF operation. - 2 Sets.Diesel Engine ControlControl for diesel engine comprising -Automatic/Manual selctor switch & 3 attempts starting device, timers and relays as required, push buttons, start/stop in manual mode Indicating lamp for high/ Low Lub. Oil pressure, High Water Temp and Engine on indicationBattery charger suitbale for 12V/24 V DC with boost and trickle selector switch, 0-30 V DC volt meter, and 0-20 A DC Ammeter All standard relays and accessories for automatic operation of diesel engine - 1 No.System ControllerDesigning, Supply, Installation, Testing and commissioning of system controller to control operation of main electric fire pump, diesel pump, Pressurization pump, Terrace pump in sequence as per specification consisting of relays, timers.Sensors, annunciation window for fault indication, complete as per specification. |
| 2 | Providing & Fixing of pressure switch in M.S. pipe line including connection etc. as required. |
| 3 | Reconditioning, overhauling, servicing, cleaning of all existing installed 150 mm dia installation control valve including repairs/replacement of internal defective parts, greasing, oiling, working parts comprising of water motor alarm, bronze seat clapper, clapper arm and hydraulically driven mechanical gong bell to sound continuous alarm when the wet riser/ sprinkler system activates, pressure gauges, emergency releases, strainer, pressure switch, cock valve complete with drain valve and bypass, test control box, ball valves,MS pipe of required size, flanges, orifice plate, gasket etc and testing, commissioning of the same complete as required : |
| 4 | Reconditioning, overhauling, servicing, cleaning, repairing of all existing installed different sizes of butterfly Valve including repairs/replacement of internal defective parts, greasing, oiling, so as to make them in proper functional condition etc. complete as required as per site location. |
| 5 | 150 mm dia |
| 6 | 100 mm dia |
| 7 | 65/80 mm dia |
| 8 | Supplying, Installation, Testing and Commissioning of dial type pressure gauge suitable for working pressure of 250 PSI including all accessories required. |
| 9 | Reconditioning, overhauling, servicing, cleaning of existing installed air vessel including repairs/replacement of internal defective parts, greasing, oiling, including flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge etc. so as to make them in proper functional condition etc. testing & commissioning of the same complete as required as per site location. |
| 10 | Supplying and fixing of MS hose cabinet of size 900 mm x 600 mm x 500 mm made of 2 mm thick with 6mm thick glazed glass doors including necessary locking arrangement suitable to accommodate external hydrants, 2 nos 63mm dia synthetic hose pipe 15 m long, 1 no branch S.S. pipe with 4 nos MS angle ( 40 x 40 x 8 ) supports grouted in floor and duly coated with post office red external and white internal paint and dismantle the exixting cabinet with buy back value complete in all respects. |
| 11 | Reconditioning, Servicing, Checking including replacement of defective internal part/washers/gaskets etc. as required of single headed landing valve etc. complete as required. The job include cost of pressure testing of the hydrant valve after repair repainting/repolishing of the same as required. |
| 12 | Reconditioning, overhauling, servicing, cleaning of all existing installed Hose Reel Drum including repairs/replacement of internal defective parts, greasing, oiling, tracing leakages and repair of pipe connection with GI Fittings, painting so as to make them in proper functional condition etc complete as required as per site requirement. |
| 13 | Providing fixing, testing & commissioning of 15mm dia quartzoid bulb type sprinklers of rating 68 0C with required accessories i/c rebate : pendent sprinkle |
| 14 | Providing, laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming to IS 1239/Class -II of IS: 3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench i/c rebate on Existing pipe etc. of following sizes complete as required. |
| 15 | 150 mm dia |
| 16 | 80 mm dia |
| 17 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 1239/Class -II of IS: 3589 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade i/c dismantling of existing pipe with rebate etc complete as required : |
| 18 | 150 mm dia |
| 19 | 100 mm dia |
| 20 | 80 mm dia |
| 21 | 65 mm dia |
| 22 | 50 mm dia |
| 23 | 40 mm dia |
| 24 | 32 mm dia |
| 25 | 25 mm dia |
| 26 | Providing & fixing 100 mm flow switch in following sizes M.S. pipe including connection etc as required. |
| 27 | Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete with mounting base complete as required. |
| 28 | Supplying, replacement, installation, testing & commissioning of addressable manual call point complete as required. |
| 29 | Supplying, replacing, installation, testing & commissioning of addressable horn cum strobe ABS body complete as required. |
| 30 | Supplying, replacing, installation, testing & commissioning of 1.5/3/6W ceiling speaker complete as required. |
| 31 | Overhauling, checking, reconditioning, servicing, greasing of the Electric driven Main pump 60 HP including necessary repairs/replacement of internal defective all parts, alignment of pump as required and re-testing & commissioning of the same complete as required. The Job also includes putting the same in automatic operation mode of the Main pump set to make it functional as per Delhi Fire Service requirements. |
| 32 | Overhauling, checking, reconditioning, servicing, greasing of the deisel engine driven pump set including necessary repairs/ replacement of all internal defective parts including alignment of pump as required and re-testing & commissioning of the same complete as required. The Job also includes putting the same in automatic operation mode to make it functional as per Delhi Fire Service requirements. |
| 33 | Overhauling, checking, reconditioning, servicing, greasing of the including necessary repairs/ replacement of all internal defective parts alignment of 12.5 HP Jockey pump as required and re-testing & commissioning of the same complete as required. The Job also includes putting the same in automatic operation mode to make it functional as per Delhi Fire Service requirements. |
| 34 | Dismantling, Checking, Overhauling, servicing, repairing as required, refixing testing & commissioning of following size existing sluice valves including repairs of internal defective parts as required, greasing, oiling, changing gasket so as to make them in proper working condition etc. complete as required. |
| 35 | 150 mm |
| 36 | 100 mm |
| 37 | Dismantling, Checking, Overhauling, servicing, repairing as required, refixing, testing & commissioning of following size existing Cast iron double flanged non return valves including repairs of internal defective parts as required, greasing, oiling, changing gasket so as to make them in proper working condition etc. complete as required. |
| 38 | 150 mm dia |
| 39 | 80/100 mm dia |
| 40 | Dismantling, checking, Overhauling, servicing, reinstallation, testing & commissioning of Ventilation Fans including repair of worn out and defective parts, greasing, alignment and balancing, painting of supporting structures wherever required and reassembling of machine in original shape and design to deliver/discharge the capacity of air flow etc. as required of existing various capacity ceiling suspended type double skinned following size of Tube Axial Fresh Air Fans from ceiling, existing centrifugal forward curved DIDW Blowers, TEFC weather proof motor of IP-55 class F insulation, EFF 2, Direct drive and pulley mounted on motor and fan shaft, belt guard, motor & fan mounted on common base plate for extensive repair/renovation of units. The job includes testing commissioning of the centrifugal fan after carrying out the necessary repairs/replacement of parts as required and making the same functional complete in all respects.. |
| 41 | Dismantling, checking, overhauling, servicing, reinstalling, testing & commissioning of the existing Automatic Tripping cum Actuator Unit and integration of the same after carrying out necessary servicing, overhauling, repair/replacement of worn out and defective parts for mechanical Exhaust fan with the existing panel complete as per the directions of the Engineer-in-Charge |
| 42 | Reconditioning, servicing, repair of existing micro processor based three loop main fire alarm control panel of Essar make fully networkable upto 6 loops/ Zone i/c overhauling checking, servicing, testing & commissioning of the same after effecting necessary repairs/replacement of internal defective parts viz power supply card, zone card, re-wiring i/c re-testing & commissioning etc. complete as required, operating at 24 VDC comprising of audio & visual alarm indication of Fire, continuous status indications of Health/Fire/Faulty Zones, Fire/Fault test switches, zone isolation switch with indicators and also test switch for system test, sounder alarm. Silence alarm and a switch for resetting the whole system with audio-visual indications etc as required. The Job i/c's checking the entire system tracing and removing the faults in system, denting & painting the Fire Alarm control panel complete, i/c credit for defective/unserviceable spare parts etc as reqd. |
| 43 | Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS/HFFR outer sheath complete as required. |
| 44 | Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS/HFFR outer sheath complete as required. Please Enable Macros to View BoQ information |