| 1 | Safe carriage of oil storage tank of 20kL including loading, unloading & carriage upto the site of approx.. 75 Km. from 220 KV Sub-station, Chinhat to 132 KV Sub-station Mahamoodabad. |
| 2 | Complete safe dismantling of the accessories of 132/33 kV 20 MVA Transformer including opening of jumpers, removal of earthing, removal of bushings, conservator tank, pipe lines, cooling fans, marshalling box, radiator with oil drain from radiator, opening of control cable sand fixing of blanking plates on the radiators, pipelines, conservator tanks, turret etc. with proper stacking. All men, material, T&P including Nuts & Bolts shall be provided by contractor. |
| 3 | Dismantling of RTCC panel of 20 MVA T/F including disconnection of cables, cutting of earthing and shifting of panel to store. |
| 4 | Dismantling of following equipment’s with due opening of jumpers, earthing, cable connections, nut bolts and proper shifting to store:- |
| 5 | 145kV CT (400-200/1Amp) 0.2 accuracy class |
| 6 | 120kV LA with structure |
| 7 | 36kv CT, 400/1Amp, 3 core |
| 8 | Old C&R panel of 20 MVA T/F including opening of all cable connection, cutting of earthng and shifting from control, room to store. |
| 9 | Shifting of oil filled main tank of dismantled 132/33kV 20 MVA T/F from plinth upto 20 metre distance including turning of tank if required with all T&P, manpower to be provided by contractor to complete the job in all respect. |
| 10 | Additional shifting of dismantaled old 132/33KV 20 MVA Transformer main tank upto storage plateform 50 Meter (5 Mtr. Per job.) |
| 11 | Shifting of oil filled main tank of new 132/33kV 63MVA T/F plinth 20 metre distance to including turning of tank if required with all T&P, manpower to be provided by contractor to complete the job in all respect. |
| 12 | Additional shifting of 01 Nos. 132/33KV 63 MVA Transformer main tank upto 275 Meter (5 Mtr. Per job.) due to sharp 90 Degri turn of road. |
| 13 | Complete erection of 132/33kV 63 MVA T/F including erection of radiator, conservator tank, all bushings, turrets, bucholz relay, connecting pipes, cooling fans, motor drive mechanism of OLTC, breather, PRV, OSR etc all other associated works to complete the job in all respect. All T&P shall be provided by contractor at his own cost. |
| 14 | Centrifuging of oil in main transformer tank un-interrupted till the desired BDV and PPM of oil is achieved including recording of all the parameters hourly such as temperature, BDV, PPM , Vacuum etc. Centrifuging machine, operator, lubricant and all T&P shall be provided by the contractor. |
| 15 | Erection of following equipment’s with connection of jumpers, earthing, cable connections, nut bolts and proper shifting to store:- |
| 16 | 145kV CT (400-200/1Amp) 0.2s accuracy class with JB |
| 17 | 120kV LA with structure |
| 18 | 36kv CT,1250/1Amp, 3 core |
| 19 | Erection of new C&R panel for 63 MVA T/F including shifting from store to control room upto erection place by providing and fixing of anchor fasteners, earthing and erection of panel with all accessories as per drawing for proper function of TNC switch and all protection relays in all respect |
| 20 | Laying of control cable of following sizes from C&R panel to CB, JB , MB as per cable schedule with due opening of cable trench and proper cable dressing to complete the job in all respect. |
| 21 | 2Cx2.5sqmm |
| 22 | 4cx2.5sqmm |
| 23 | 6Cx2.5sqmm |
| 24 | Termination of control cable of various equipment’s of switchyard to C&R panel, JB, CB, MCB with proper glanding, ferruling and lugging as per drawing with all associated works to complete the job in all respect |
| 25 | Earthing of Main tank, Marshalling box, Drive mechanism, Transformer neutral etc of new 63MVA T/F, 145kv CTs, & Control Panel of 120 LV LAs along with their JB with MS flats of following sizes which includes providing, cutting, welding, strengthening and bending of MS Flat and shifting of materials from store to site to complete the job in all respect:- (All materials including MS Flat shall be provided by contractor) |
| 26 | 75x10 mm |
| 27 | 50x6 mm |
| 28 | 25x6 mm |
| 29 | Painting of MS flats by rubbing with sand paper and then painting with 1 coat of red oxide primer and 2 coats of 1st quality synthetic enamel paint of make Aisan/Berger/Nerolac in bus green colour including vertical support. (All materials including paints shall be provided by contractor to complete the job in all respect). |
| 30 | 75x10 mm |
| 31 | 50x6 mm |
| 32 | 25x6 mm |
| 33 | Jumpering of all 3 HV Bushing of Transformer with ACSR panther conductor which includes cutting and clamping of conductor. |
| 34 | Jumpering of all 3 LV Bushing of Transformer with twin ACSR panther conductor which includes cutting and clamping of conductor. |
| 35 | Erection and installation of RTCC panel of 63 MVA T/F along with shifting from storage place to control room including termination and connection of control cables at RTCC panel as well as transformer MB side as per drawing to complete the job in all respect. All cable glands, ferrules and lugs and other T&Ps to be provided by the contractor on his own cost. |
| 36 | Cable termination along with laying of new cable if required as per drawing and cable schedule of 63 MVA T/F its cooling fans, marshalling box, all relays using existing cable for proper functioning of fans in both Manual and Auto Mode. |
| 37 | Proper packing of all bushings of dismantled transformers including wrapping with polythene sheets in the wooden carrets (shall be provided by the contractor) with proper shifting and stacking in the store. |
| 38 | Obtaining NOC from office of electrical Safety Directorate Lucknow for first time energization of 63 MVA T/F (including payment of fee as per challan) |
| 39 | Providing & fixing of name plate of 2mm thick aluminium sheet with retro reflective sheet of size 300x200mm with details/name written as per prescribed colour scheme to be fixed with the help of suitable size nuts & bolts as already installed structure of equipment’s in the switchyard with all cost of plate nuts & bolts, T&P and labour as per direction of supervising engineer. |
| 40 | Retro reflective sign board of size 10 Ft. x 06 Ft. duly made of 2 mm thick aluminium sheet fully covered with 3 M. DG Cube type retro reflective sheet of yellow colour. The letters & symbols shall be computer cut & in blue colour. Board is to be provided alongwith back support frame made of M.S. angle of size 35mm x 35mm x 05 mm with provision of two legs for grouting duly painted in black colour enamel paint and the back side of the aluminium sheet shall be painted with stove enamel paint complete in all respect and to be grouted with casting of CC (1:2:4) foundation at the sub-station. |
| 41 | Supply of PG Clamp Panther/Panther |
| 42 | Supply of PG Clamp Moose/Moose |
| 43 | Supply of 33kv CT clamp for twin Moose |
| 44 | Supply of 33kv isolator clamp for twin Moose |
| 45 | Supply of Bus post clamp for 33KV LA suitable for twin Moose |
| 46 | MS Flat 75x10 MM |
| 47 | Bus Post clamp suitable for Twin Moose |
| 48 | Supply of LED Flood light, Luminaires Type FL-1, 150 Watt. (Rate has been taken from Cost Data Book 2024-25 due to not available in proposed Cost Data Book 2025-26.) Please Enable Macros to View BoQ information |