| 1 | Installation of Fire check door & pressurization System in stair case at Academic Block Building at Dr. Ram Manohar Lohia Institute of Medical Sciences, Vibhuti Khand, Gomti Nagar, Lucknow (U.P.) |
| 2 | VENTILATION SYSTEM-ANIMAL HOUSE A & B BLOCK |
| 3 | Axial Fan for \\"Exhaust Air (Emergency)\\" |
| 4 | Supply installation, testing and commissioning of single piece long casing (Motor should completely be accommodated inside the fan casing) Vane Axial Fan (multi piece casing are not acceptable) in GSS/MS with powder coated, Al impeller with adjustable blade angles (Manually Adjustable at Site), bird screen ,gravity louvers, fire retardent flexible connection, necessary nut bolts and directly coupled TEFC Sq.cage induction motor (IE2) H Class insulation for Smoke Exhaust) suitable for 415V±10%, 50 Hz. 3 phase electric supply complete with required hardware etc. All offered fans pitch angle shall be AMCA Certified & Listed on AMCA website (Interpolation of pitch angle shall not be acceptable) and Fan Efficiency Grade ( Min FEG 71, lesser is not acceptable).Thickness of the casing shall not be less than: For Dia (300 to 650) mm – 2mm, Dia (700 to 1140) mm – 3 mm, Dia (1200 to 1400) mm – 4mm & Dia 1600 – 5 mm.All fans after assembly shall be dynamically trim-balanced to ISO1940 and AMCA 204/3 - G2.5 quality grade.Fan Casing should be provided with Special Designed Integral Straightening Vanes (Vanes should be integral part of casing, it should not be provided separately as an accessory) to reduced turbulence provide high performance & low noise level. |
| 5 | Fans for emergency application Tube axial are to be used.Sound level for emergency operation it should not exceed 88 Db(A)@ 3 meter (Room condition).Incase of not achieving sound , attenutor has to be added.Outlet velocity of the fans should not exceed 18 m/s for emergency application. |
| 6 | Smoke and heat exhaust fans should be tested and certified for 250 Deg C for 2 hour in accordance to standard 'BSEN12101-3:2015 from TUV SUD PSB Singapore or equivalent internationally recognized fire laboratory |
| 7 | Emergency Operation |
| 8 | 1500 CFM @25 static pressure |
| 9 | 2500 CFM @25 static pressure |
| 10 | 3000 CFM @25 static pressure |
| 11 | 3500 CFM @25 static pressure |
| 12 | 5000 CFM @25 static pressure |
| 13 | 6000 CFM @25 static pressure |
| 14 | 7000 CFM @25 static pressure |
| 15 | 8000 CFM @25 static pressure |
| 16 | 9000 CFM @25static pressure |
| 17 | 12000 CFM @25 static pressure |
| 18 | 18000 CFM @25 static pressure |
| 19 | Supply and fixing of dual speed Jet fan having 1.7/0.84 Cum/sec air flow 17.70/8.80 air speed alongwith hanging arrangement as required. |
| 20 | DUCTING , GRILLS, DIFFUSER AND DIFFUSER (VENTILATION) |
| 21 | Rectangular ductwork |
| 22 | Supply, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required. |
| 23 | Thickness 0.63 mm sheet (24 Gauge) |
| 24 | Thickness 0.80 mm sheet (22 Gauge) |
| 25 | Thickness 1.00 mm sheet (20 Gauge) |
| 26 | Thickness 1.25 mm sheet (18 Gauge) |
| 27 | Supplying & fixing of powder coated extruded aluminium Return Air Grills with louvers but without volume control dampers complete in confirmation to SMACNA/IS and as per specifications complete etc. as required. |
| 28 | Supply,installation,testing and commissioning of motorized (ON -OFF type ) duct mounted GI volume control damper with enthalpy sensor and necessary control wire (minimum 1.5 sqmm)for integration & as per drawing and specifications. |
| 29 | Damper |
| 30 | Actuator |
| 31 | Supply,installation,testing and commissioning of flexible duct connections constructed of fire resistance flexible double canvas sleeve as per the drawings and specifications. |
| 32 | Supply , Erection of exhaust air louver with extruded aluminium grill with SS wire mesh and GI volume control damper with 20 micron filters |
| 33 | Supply, installation, testing and commissioning of main panel board outdoor IP 55 type cubical Fully automatic DOL starter suitable for operating 3.7 kw motors/fan capacity, complete with contactors,Timer, overload protection relay, current sensing type single phase preventer, ON indications, push buttons, auto / manual / off selector switch,other accessories. complete as required. |
| 34 | Supply, installation, testing and commissioning of main panel board outdoor IP 55 type cubical Fully automatic DOL starter suitable for operating 5.5 kw motors/fan capacity, complete with contactors,Timer, overload protection relay, current sensing type single phase preventer, ON indications, push buttons, auto / manual / off selector switch,other accessories. complete as required. |
| 35 | Associated Electrical Work |
| 36 | Indoor Type Main Panel |
| 37 | Design, Manufacturing, Supply, Commissioning & Testing of Main LT Panel cum Starter Panel. The panel will be totally enclosed type with, free standing, floor mounted, outdoor duty, dust & vermin proof, , front operated, electrical panel fabricated from 2 mm thick M.S. Sheet as per specifications & drawing laid in this document and will be complete with the main and auxiliary bus bars, multimeter, indication lamps, CT's, protection MCB, interconnection wiring, earth bus and will be powder coated finish with 50 micron thickness. |
| 38 | INCOMMER |
| 39 | 1 Nos. 1000 Amp FP ACB 25 KA, having R,Y,B Phase indication Lamp with control MCBOn, Off, Trip Status Indication with control MCB |
| 40 | BUSBARS |
| 41 | 1 Nos. 1200 Amp FP busbars of aluminium alloy as per SLD. |
| 42 | OUTGOING |
| 43 | 500Amp. 10KA FP MCB 3 No. |
| 44 | Indoor Type Sub Panel |
| 45 | Design, Manufacturing, Supply, Commissioning & Testing of Main LT Panel cum Starter Panel. The panel will be totally enclosed type with, free standing, floor mounted, outdoor duty, dust & vermin proof, , front operated, electrical panel fabricated from 2 mm thick M.S. Sheet as per specifications & drawing laid in this document and will be complete with the main and auxiliary bus bars, multimeter, indication lamps, CT's, protection MCB, interconnection wiring, earth bus and will be powder coated finish with 50 micron thickness. |
| 46 | INCOMMER |
| 47 | 1 Nos. 500 Amp FP MCCB 25 KA, having R,Y,B Phase indication Lamp with control MCBOn, Off, Trip Status Indication with control MCB |
| 48 | 500Amp ATS |
| 49 | BUSBARS |
| 50 | 1 Nos. 1200 Amp FP busbars of aluminium alloy as per SLD. |
| 51 | OUTGOING |
| 52 | 125Amp. 10KA FP MCCB 12 No. |
| 53 | Indoor Type Floor Panel |
| 54 | Design, Manufacturing, Supply, Commissioning & Testing of Main LT Panel cum Starter Panel. The panel will be totally enclosed type with, free standing, floor mounted, outdoor duty, dust & vermin proof, , front operated, electrical panel fabricated from 2 mm thick M.S. Sheet as per specifications & drawing laid in this document and will be complete with the main and auxiliary bus bars, multimeter, indication lamps, CT's, protection MCB, interconnection wiring, earth bus and will be powder coated finish with 50 micron thickness. |
| 55 | INCOMMER |
| 56 | 1 Nos. 125 Amp FP MCCB 25 KA, having R,Y,B Phase indication Lamp with control MCBOn, Off, Trip Status Indication with control MCB |
| 57 | BUSBARS |
| 58 | 1 Nos. 160 Amp FP busbars of aluminium alloy as per SLD. |
| 59 | OUTGOING |
| 60 | 63Amp. 10KA FP MCCB With Suitable Size Star Delta Starter 12 No. |
| 61 | 63Amp. 10KA FP MCCB 4 No. |
| 62 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. |
| 63 | 100 mm width X 50 mm depth X 1.6 mm thickness |
| 64 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 65 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 66 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 67 | Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 68 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 69 | Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. |
| 70 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 71 | Supply of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. |
| 72 | 6 sq. mm 3 core |
| 73 | 10 sq. mm 4 core |
| 74 | 16 sq. mm 4 core |
| 75 | 70 sq. mm 3.5 core |
| 76 | 240 sq. mm 3.5 core |
| 77 | 300 sq. mm 3.5 core |
| 78 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. |
| 79 | Above 35 sq. mm and upto 95 sq. mm |
| 80 | Above 95 sq. mm and upto 185 sq. mm |
| 81 | Above 185 sq. mm and upto 400 sq. mm |
| 82 | Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required. |
| 83 | Above 35 sq. mm and upto 95 sq. mm |
| 84 | Above 95 sq. mm and upto 185 sq. mm |
| 85 | Above 185 sq. mm and upto 400 sq. mm |
| 86 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. |
| 87 | Above 35 sq. mm and upto 95 sq. mm |
| 88 | Above 95 sq. mm and upto 185 sq. mm |
| 89 | Above 185 sq. mm and upto 400 sq. mm |
| 90 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. |
| 91 | Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 92 | Above 35 sq. mm and upto 95 sq. mm |
| 93 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 94 | 2 X 6 sq. mm (22mm) |
| 95 | 3 X 10 sq. mm (22mm) |
| 96 | 3 X 16 sq. mm (25mm) |
| 97 | 3½ X 70 sq. mm (35mm) |
| 98 | 3½ X240 sq. mm |
| 99 | 3½ X 300 sq. mm |
| 100 | Supply, installation, testing and commissioning of addressable Phone control module complete as required |
| 101 | Supplying & laying of 2x1.5 sqmm fire survival armoured cable, 600/1000V rated with annealed copper conductor having glass mica fire barrier tape covered by an extruded layer of Cross Linkable Ethylene Propylene Rubber (EPR) insulation and LSZH inner bedding, steel wire armouring & LSZH outer sheath complete as required. |
| 102 | Providing and fixing Gl Clip in Metal Ceiling System of 600x600 mm module which includes providing and fixing 'C' wall angle of size 20x30x20 mm made of 0.5 mm thick pre painted steel along the perimeter of the room with help of nylon sleeves and wooden screws at 300 mm center to centre, suspending the main C carrier of size 10x38x10 mm made of G.I steel 0.7 mm thick from the soffit with help of soffit cleat 37x27x25x1.6 mm, rawl plugs of size 38x12 mm and C carrier suspension clip and main carrier bracket at 1000 mm c/c. Inverted triangle shaped Spring Tee having height of 24 mm and width of 34 mm made of Gl steel 0.45 mm thick is then fixed to the main C carrier and in direction perpendicular to it at 600 mm centers with help of suspension brackets. ding. |
| 103 | Wherever the main C carrier and spring T have to join, C carrier and spring T connectors have to be used. All sections to be galvanized @ 120 gms/sqm (both side inclusive), fixing with clip in tiles into spring T with : GI Metal Ceiling Clip in plain Beveled edge global whitecolor tiles of size 600x600 and 0.5 mm thick with 25 mm height, made of G I sheet having galvanizing of 100 gms/ sqm (both sides inclusive) and electro statically polyester powder coated of thickness 60 microns (minimum), including factory painted after ben |
| 104 | GAS SUPPURATION SYSTEM |
| 105 | 2kg capacity seamless Alluminium cylinder Paso approved stored pressure type clean agent fire extinguisher alongwith all necessary fitting filled with clean agent FK-5-1-12 complete having operating pressure between 15 bar etc. as required UL & FM listed gas. |
| 106 | 5kg capacity seamless Alluminium cylinder Paso approved stored pressure type clean agent fire extinguisher alongwith all necessary fitting filled with clean agent FK-5-1-12 complete having operating pressure between 15 bar etc. as required UL & FM listed gas. |
| 107 | SITC of Pneumatic Heat detection tube red color made by special modified polyamide (PA), UL and LPCB standard, having burst temperature 100°C to 120°C, inner diameter 4 mm, outer diameter 6 mm, pressurized with nitrogen at 15 bar pressure for automatic detection and suppression system |
| 108 | SITC of End of line adapter along with pressure gauge working pressure 25 bar. UL approved. |
| 109 | SITC of End of Line Plug for automatic fire suppression System used for fitting at tube end to terminate the point. Fitting made by brass nickel plated material. UL approved. |
| 110 | SITC of Pressure Switch at 15 bars. UL approved. |
| 111 | SITC of T connection suitable for 4 / 6 mm. diameter pressurized tubes, brass nickel plated material with maximum working pressure 25 bar. UL approved. |
| 112 | SITC of Master Control Unit micro processor based 4 zone inbuilt GSM dialer audio visual alarm control panel, 2NO/NC potential free relay contacts discharge LED indicator, battery LED indicator, system status indicator and AC power ON LED indicator with inbuilt battery backup 24h . |
| 113 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 114 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 115 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 116 | Providing and fixing 1200 mm W x 2400 mm H double openable Fire doors for Staircase & Lift Lobby comprising of frame made of 2 mm thick MS sheet (14 SWG) clad on both sides with 2.0 mm thick MS sheets with cavity fill of 100 mm thick resin bonded glass wool of 48 kg/cu.m density including nitrile rubber gaskets between MS sheet cladding and frame of MS tube 100 x 40 mm of 14 SWG, self lubricating sliding / double openable door mechaniusm (rollers / ball bearing) in MS channels in floor and on top and heavy duty hardware / locking mechanism etc. complete as required. |
| 117 | Passive Fire Sealents |
| 118 | Through Penetration on Floor (Medium to large size i.e. > 4\\" gaps) |
| 119 | Providing and Installation Fire stop mortar system Hilti CP 636 , with minimum 2 hours fire rating when tested in accordance with UL 1479/ASTM-E 814 standards, for vertical and horizontal openings in floors or slabs after passing service lines like cables/cable bundles, cable trays etc. The mortar shall be a light weight cementitious product and shall carry test certificate in accordance with IEC 60068-2-57:1999-11 (Environmental Testing) as per Part 2-57: Test for Vibration-Time-history method and VERTEQII for seismic zone 4. The product shall be age tested as per Dafstb and DIBT standards. The product shall carry test certificate for mold resistance rating of 0 as determined by ASTM G21-96. The product shall be age tested as per Dafstb and DIBT standards.The system shall be UL listed & classified and product shall bear the UL and FM approval logo on the packing. If none of UL test certificate comply with actual application, an EJ document prepared by a qualified personnel and based on nearest third party tested & approved systems like UL test certificates & in accordance with IFC guidelines shall be producted by manufacturer. s. |
| 120 | A firestop submittal shall be produced by manufacturer , in accordance with approved passive fire protection method statement, for technical approval. Firestop installation shall be done by Hilti Accredited Firestop Speciality Contractor (HAFSC) or by certified installers gone through Hilti's FIT service and in accordance with Hilti guidelines and UL system test certificate |
| 121 | Through Penetration on Floor for annular gaps up to 50 mm |
| 122 | Providing and installation Acrylic Firestop Sealant Hilti CP 606 in gaps around non combustible penetrants like ducts or metal pipes passing through floor slab to provide minimum 2 hours fire rating when subject to the test conditions of UL 1479/ASTME 814 standards. The product shall be age tested as per DafStb guidelines. Sealant should provide sufficient MAF, water and gas tight seal. Sealant shall also provide airborne sound transmission reduction (STC of 50) and shall be tested as per DIN 52210 for sound insulation. Sealant shall carry test certificate for mold resistance rating of 0 as determined by ASTM G21-96 and should have a VOC content of approx. 75 g/l as per LEED 2009. The sealant shall carry test certificate in accordance with IEC 60068-2-57:1999-11 (Environmental Testing) as per Part 2-57: Test for Vibration-Time-history method and VERTEQII for seismic zone 4.The system shall be UL listed & classified and product shall bear the UL and FM approval logo on the packing. If none of UL test certificate comply with actual application, an EJ document prepared by a qualified personnel and based on nearest third party tested & approved systems like UL test certificates & in accordance with IFC guidelines shall be producted by manufacturer. A firestop submittal shall be produced by manufacturer , in accordance with approved passive fire protection method statement, for technical approval. Firestop installation shall be done by Hilti Accredited Firestop Speciality Contractor (HAFSC) or by certified installers gone through Hilti's FIT service and in accordance with Hilti guidelines and UL system test certificates or approved EJ document. Firestop Speciality Contractor needs to submitt work completition |
| 123 | certificate along with installation report through Hilti documentation Software CFS DM for periodic inspection & maintenance purpose. The gaps around combustible penetrants like plastic pipes or ducts with insulation shall be sealed with an appropriate intumescent technology like FS One Max Sealants, CP 648-E Wraps or CP 644 collars. In case of repenetration requirement, Hilti intumescent based speed sleeve CP 653BA of appropriate size shall be used. Intumescent items shall be paid under separate heads and as mentioned below. |
| 124 | Intumescent firestop Sealant FS One Max |
| 125 | Provide and Installation high performance intumescent firestop sealant Hilti FS One Max around combustible penetrations like plastic pipes or ducts/pipes with insulation passing through floor to provide minimum 2 hours fire rating when subject to test standards of UL 1479/ASTM-E 814. The sealant shall have surface burning characteristics according UL 723 (ASTM E84-96): Flame spread index 0 and smoke development index 5. The sound transmission classification according to ASTM E 90-99 shall be 56 (STC Rating). Sealant shall have mold and mildew resistance and the performance shall be Class 0 according to ASTM G-21. |
| 126 | Movement capability approx.. 5% (ISO 11600) and the average volume shrinkage is 24% according ASTM C1241. Sealnt shall meet LEED requirements for indoor environmental quality credit (4.1 and 4.2) with a VOC content of 9 g/l. Seismic tested on mechanical performance, smoke and fire-ratings. |
| 127 | The product shall be age tested as per Dafstb and DIBT standards.The system shall be UL listed & classified and product shall bear the UL and FM approval logo on the packing. If none of UL test certificate comply with actual application, an EJ document prepared by a qualified personnel and based on nearest third party tested & approved systems like UL test certificates & in accordance with IFC guidelines shall be producted by manufacturer. |
| 128 | A firestop submittal shall be produced by manufacturer , in accordance with approved passive fire protection method statement, for technical approval.Firestop installation shall be done by Hilti Accredited Firestop Speciality Contractor (HAFSC) or by certified installers gone through Hilti's FIT service and in accordance with Hilti guidelines and UL system test certificates or approved EJ document. Firestop Speciality Contractor needs to submitt work completition certificate along with installation report through Hilti documentation Software CFS DM for periodic inspection & maintenance purpose.Duct/pipes & Cables with insulation (FS One Max Firestop Sealant) |
| 129 | Demolishing R.C.C. work by mechanical means and stockpiling at designated locationsand disposal of dismantled materials up to a lead of 1 kilometre, stacking serviceable andunserviceable material separately including cutting reinforcement bars |
| 130 | Demolishing brick work manually/ by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-charge. |
| 131 | In cement mortar |
| 132 | Dismantling doors, windows and clerestory windows (steel or wood) shutter including chowkhats, architrave, holdfasts etc. complete and stacking within 50 metres lead : |
| 133 | Of area beyond 3 sq. metres |
| 134 | Disposal of building rubbish/ malba/ similar unserviceable, dismantling or waste material by machanical means, including loading, transporting, unloading to approved municipal dumping groung or as approved by Engineer -in-charge, beyond 50 m intial lead , for all leads including all lifts involved. |
| 135 | Brick work with common burnt clay (non moduler) brick of class -150 in super structure above plith lvl upto floor v lvl. In all shape and size in 1:6 (1: cement : 6coarse and mortar in one brick wall (230mm Thick ) |
| 136 | 12 mm cement plaster of mix : |
| 137 | 1:4 (1 cement: 4 coarse sand) |
| 138 | Distempering with 1st quality acrylic distemper (ready mixed) having VOC content less than 50 gms/litre, of approved manufacturer, of required shade and colour all complete, as per manufacturer's specification. |
| 139 | New work ( two or more coats ) over and including water thinnable priming coat with cement primer having VOC content less than 50 gram/litre. |
| 140 | Inner wall surface |
| 141 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. |
| 142 | Supply and fixing of anodized Aluminum door having 2mm thick Aluminum section excluding coating & an average coating of 20 micron fully glazed made of Aluminum door tube size 83.5x44.65mm as Vertical member and 1140x44.45mm size tube in bottom & horizontal members Door chaukhat should be of Aluminum tubular vertical with two openable shutters.The rate will include cost of material fixture 5mm glass Partialy glazed handles, locks,screw necessary beeding & excluding cost of floor spring if required for proper completion of work as per direction of Engineer |
| 143 | Providing and fixing 50 mm thick glazed fire resistant door shutters of 60 minutes fire rating conforming to IS:3614 (Part-II), tested and certified as per laboratory approved by Engineer-incharge, with suitable mounting on door frame, consisting of vertical styles, lock rail, top rail 100 mm wide, bottom rail 200 mm wide, made out of 16 SWGG.I.sheet (zinc coating not less than 120 gm/sqm) duly filled FR insulation material and fixing with necessary stainless steel ball bearing hinges of approved make, including applying a coat of approved fire resistant primer etc. all complete as per direction of Engineer-in-charge |
| 144 | Reinforced cement concrete work in beams, suspended floor, roofs having slope up to 15° landings, balconies, shelves, chajjas, lintels, bands,plain window sills, staircases and spiral stair cases above plinth level up to the floor five level, excluding the cost of centering, shuttering, finishing and reinforcement with 1:1.5:3 (1cement: 1.5 coarse sand(zone-III)derived from natural sources : 3 graded stone aggregrate 20mm nominal size derived from natural sources). |
| 145 | Ground floor |
| 146 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level. |
| 147 | Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 148 | Above plinth Lvl. |
| 149 | Centering and shuttering including strutting, propping etc. and removal of form for |
| 150 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation M-150 in Superstructure above plinth level up to floor V level in all shapes and sizes in : |
| 151 | Cement Mortar 1:4 (1 Cement : 4 Coarse sand 2.25FM |
| 152 | GROUND FLOOR |
| 153 | Providing and fixing 18 mm thick gang saw cut, mirror polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing of edges to give high gloss finish etc. complete at all levels. |
| 154 | Granite stone slab of colour black, Cherry/Ruby red |
| 155 | Area of slab over 0.50 sqm |
| 156 | Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge. |
| 157 | Demolishing R.C.C. work by mechanical means and stockpiling at designated locationsand disposal of dismantled materials up to a lead of 1 kilometre, stacking serviceable andunserviceable material separately including cutting reinforcement bars |
| 158 | Demolishing brick work manually/ by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-charge. |
| 159 | In cement mortar |
| 160 | Dismantling doors, windows and clerestory windows (steel or wood) shutter including chowkhats, architrave, holdfasts etc. complete and stacking within 50 metres lead : |
| 161 | Of area beyond 3 sq. metres |
| 162 | Disposal of building rubbish/ malba/ similar unserviceable, dismantling or waste material by machanical means, including loading, transporting, unloading to approved municipal dumping groung or as approved by Engineer -in-charge, beyond 50 m intial lead , for all leads including all lifts involved. |
| 163 | Brick work with common burnt clay (non moduler) brick of class -150 in super structure above plith lvl upto floor v lvl. In all shape and size in 1:6 (1: cement : 6coarse and mortar in one brick wall (230mm Thick ) |
| 164 | 12 mm cement plaster of mix : |
| 165 | 1:4 (1 cement: 4 coarse sand) |
| 166 | Distempering with 1st quality acrylic distemper (ready mixed) having VOC content less than 50 gms/litre, of approved manufacturer, of required shade and colour all complete, as per manufacturer's specification. |
| 167 | New work ( two or more coats ) over and including water thinnable priming coat with cement primer having VOC content less than 50 gram/litre. |
| 168 | Inner wall surface |
| 169 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. |
| 170 | Supply and fixing of anodized Aluminum door having 2mm thick Aluminum section excluding coating & an average coating of 20 micron fully glazed made of Aluminum door tube size 83.5x44.65mm as Vertical member and 1140x44.45mm size tube in bottom & horizontal members Door chaukhat should be of Aluminum tubular vertical with two openable shutters.The rate will include cost of material fixture 5mm glass Partialy glazed handles, locks,screw necessary beeding & excluding cost of floor spring if required for proper completion of work as per direction of Engineer |
| 171 | Providing and fixing 50 mm thick glazed fire resistant door shutters of 60 minutes fire rating conforming to IS:3614 (Part-II), tested and certified as per laboratory approved by Engineer-incharge, with suitable mounting on door frame, consisting of vertical styles, lock rail, top rail 100 mm wide, bottom rail 200 mm wide, made out of 16 SWGG.I.sheet (zinc coating not less than 120 gm/sqm) duly filled FR insulation material and fixing with necessary stainless steel ball bearing hinges of approved make, including applying a coat of approved fire resistant primer etc. all complete as per direction of Engineer-in-charge |
| 172 | Reinforced cement concrete work in beams, suspended floor, roofs having slope up to 15° landings, balconies, shelves, chajjas, lintels, bands,plain window sills, staircases and spiral stair cases above plinth level up to the floor five level, excluding the cost of centering, shuttering, finishing and reinforcement with 1:1.5:3 (1cement: 1.5 coarse sand(zone-III)derived from natural sources : 3 graded stone aggregrate 20mm nominal size derived from natural sources). |
| 173 | STAIRCASE FLIGHT |
| 174 | Ground floor |
| 175 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level. |
| 176 | Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 177 | Above plinth Lvl. |
| 178 | Centering and shuttering including strutting, propping etc. and removal of form for |
| 179 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation M-150 in Superstructure above plinth level up to floor V level in all shapes and sizes in : |
| 180 | Cement Mortar 1:4 (1 Cement : 4 Coarse sand 2.25FM |
| 181 | GROUND FLOOR |
| 182 | Providing and fixing 18 mm thick gang saw cut, mirror polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing of edges to give high gloss finish etc. complete at all levels. |
| 183 | Granite stone slab of colour black, Cherry/Ruby red |
| 184 | Area of slab over 0.50 sqm |
| 185 | Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge. |
| 186 | Dismantling aluminium/ Gypsum partitions, doors, windows, fixed glazing and false ceiling including disposal of unserviceable material and stacking of serviceable material with in 50 meters lead as directed by Engineerin-charge. |
| 187 | Providing and fixing false ceiling at all heights with integral densified calcium silicate reinforced with fibre and natural filler false ceiling tiles of Size 595x595 mm of approved texture, design and patterns having NRC (Noise Reduction coefficient) of 0.50 (minimum) as per IS 8225:1987, Light reflectance of 85% (minimum). Non combustible as per BS:476 (part-4), fire performance as per BS:476 (part 6 &7), humidity resistance of 100%, thermal conductivity < 0.043 W/m K as per ASTM 518:1991, in true horizontal level suspended on inter-locking metal powder coated T-Grid of hot dipped galvanised iron section of 0.40 mm thick on Silhouette profile,rotary stiched double webbed white with 6 mm reveal profile (white/ black) |
| 188 | ,comprising of main-T runners of size 15x42 mm of length 3000 mm, cross - T of size 15x42 mm of length 1200 mm and secondary intermediate cross-T of size 15x42 mm of length 600 mm to form grid module of size 600 x 600 mm, suspended from ceiling using galvanised mild steel items (galvanizing @ 80 grams per sqm) i.e. 50 mm long, 8 mm outer diameter M-6 dash fasteners, 6 mm dia fully threaded hanger rod upto 1000 mm length and L-shape level adjuster of size 85x25x2 mm. Galvanised iron perimeter wall angle of size 22x19x0.40 mm of length 3000 mm to be fixed on periphery wall / partition with the help of plastic rawl plugs at 450 mm center to center and 40 mm long dry wall S.S screws. The work shall be carried out as per specifications, drawing and as per directions of the Engineer-in-Charge. |
| 189 | Repalce falceceiling (LABOUR RATE) |
| 190 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required |
| 191 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 192 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required. (For light plugs to be used in non residential buildings). |
| 193 | Supply and fixing of Acrylic Emergency EXIT Sign Board with LED Lights and Battery Backup complete in all respects |
| 194 | GST Extra as applicable Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail