| 1 | Annexure-A (LABOUR CHARGES) |
| 2 | Chemical Earthing including digging of pit of size 2.5 Mtr depth and make hole of size 150 mm. Placing of earthing electrode (to be supplied by contractor), connecting the same with G.I. Strip (to be supplied by contractor) of size 35x6 mm for a minimum lenght 6 m. treatment of soil with highly condctive substance as per IS 30343 complete in all respect, result of earthing resistance to be recroded in M.B. before and after installation of earthing. The earth resistance after earthing should be less than 1 Ohm. |
| 3 | Earthing of support with M.S. Earth rod of 2.5 meter long by hammaring of M.S. Rod to proper depth and connecting the earth electrode with the help of G.I. wire as per construction manual. |
| 4 | Fabrication of MS Channel angle iron etc in required sizes with drilling of holes upto good finish for top channel, bracing and special type bracket etc. as per RESPO schedule and local approved drawing. |
| 5 | Fixing, tightening and nozzling of stay with pole and stay rod on required tension as per drawing/manual in 33 KV line. |
| 6 | Grouting of Stay in size 0.6x0.6x0.3 in CC ratio 1:4:8 (1 cement : 4 graded stone 20mm nominal size : 8 coarse sand) block including cost of Cement, sand and stone ballast back filling of soil and boulders in pit and ramming and proper alignment, leveling as per RESSPO Manual. |
| 7 | Excavation of earth for pole pit of size 0.9x0.6x1/6 of full length of pole for erection of pole in all types of soil including proper dressing of sides and ramming of bottom including etting out the excavated soil and disposal of surplus excavated soil as directed complete work |
| 8 | Erection of SP-55 single support pole in proper level and alignment along with fixing of all accessories like top channel & clamps as per RESPO manual |
| 9 | Erection of SP-72 single support pole in proper level and alignment along with fixing of all accessories like top channel & clamps as per RESPO manual |
| 10 | Erection of Sp-55 double support pole in proper level and alignment along with fixing of all accessories like top channel, X bracings & clamps as per RESPO manual. |
| 11 | Erection of Sp-72 double support pole in proper level and alignment along with fixing of all accessories like top channel, X bracings & clamps as per RESPO manual. |
| 12 | Erection of SP-72(11KV/33 KV) four pole support pole in proper level and alignment along with fixing of all accessories like top channel, X bracings & clamps as per RESPO manual. |
| 13 | Grouting of pole in size 0.45x0.45x1/9 of the support in CC ratio 1:4:8 (1 cement:4 graded stone20 mm niminal size: 8 coarse sand) block including cost of cement, sand and stone ballast back filling of soil and boulders in pit and ramming and proper alignment, levelling as per RESPO cnstruction manual |
| 14 | Muffing of poles size 0.45x0.60 cm radius with 1:3:6 (1 cement:3 coarse sand :graded stone 10 mm nominal size) block size 45 cm height from ground level including cost of cement,stone and sand etc |
| 15 | Dismantling of existing LT/HT line. including disc fitting, Insulator, clamps, Nut & Bolts and consumer connections and Street light connections etc. including rolling of conductor and cartage back from site to JE store (PCC Single Pole). |
| 16 | Dismantling of existing LT/HT line. including disc fitting, Insulator, clamps, Nut & Bolts and consumer connections and Street light connections etc. including rolling of conductor and cartage back from site to JE store(SP-55 Single Pole). |
| 17 | Dismantling of existing 11 KV HT line. including disc fitting, Insulator, clamps, Nut & Bolts and consumer connections and Street light connections etc. including rolling of conductor and cartage back from site to JE store(ACSR Weasel). |
| 18 | Dismantling of existing 3P 4W LT line, including disc fitting, Insulator, clamps, Nut & Bolts and consumer connections and Street light connections etc. including rolling of conductor and cartage back from site to JE store(ACSR Weasel) |
| 19 | Dismantling of Transformers from double pole /plinth including opening of all connections, circuts & earthing strip etc. (25 KVA). |
| 20 | Dismantling of Transformers from double pole /plinth including opening of all connections, circuts & earthing strip etc. (63 KVA). |
| 21 | Dismantling of Transformers from double pole/plinth including opening of all connections, circuts & earthing strip etc. (100 KVA). |
| 22 | Dismantling of Transformers from double pole/plinth including opening of all connections, circuts & earthing strip etc. (250 KVA). |
| 23 | Dismantling of Transformers from double pole/plinth including opening of all connections, circuts & earthing strip etc. (400 KVA). |
| 24 | Dismantling of Transformers from double pole/plinth including opening of all connections, circuts & earthing strip etc. (500 KVA). |
| 25 | Painting of SP-55 pole with angle and channel and all steel part by one coat of Red Oxide Primer and two coats of aluminium Paint and two strip of fluorescent altemate Red and White paint 30 Cm wide upto 1.5 Mtrs. From ground level. |
| 26 | Painting of SP-72 pole with angle and channel and all steel part by one coat of Red Oxide Primer and two coats of aluminium Paint and two strip of fluorescent altemate Red and White paint 30 Cm wide upto 1.5 Mtrs. From ground level. |
| 27 | Laying of 33 KV Cable in 1.5 mtr depth with suitable trencheless technology including laying in trench with providing & fixing of HDPE pipe PE 100 PN6 & having dia 150 conferming to IS 4984/1995 & having thickness 9.1 to 10.3mm. |
| 28 | Excavation of earth of size 2.1x2.1x1.2 meter for DTR Plinth. |
| 29 | Cement concreting work in ratio 1:4:8 for DTR Plinth. |
| 30 | Brick work in 1:4 ratio for DTR Plinth. |
| 31 | RCC Work of 1:2:4 ratio 15 cm thickness for DTR Plinth. |
| 32 | Cement Plaster on side walls in 1:4 ratio on DTR Plinth. |
| 33 | Erection, providing and fixing of wire mesh of size 50x35 mm around plinth and toe wall duly welded with frame of M.S angle iron 35 x35x6 mm and strip of size 35x6 mm in mid of each side along with wire mesh (width of wire mesh 1.5 meter ) with the height of 0.5 meter above the plinth and 2 meter above the toe wall with 1 No. gate and locking arrangment in the toe wall size including groutin g of 6 Nos. legs in the ratio in block of size 0.25x0.25x0.45 meter including gravlling of shingle of size 20 to 40 mm and complete painting of wire mesh with aluminium paint with two coat (Including the cost of cement and all material). |
| 34 | Installation/mounting of new 100 KVA Tranformer on pole structure and fixing of channel /angle etc. and making all connections of HT and LT side and its complete commissioning. |
| 35 | Installation/mounting of new 63 KVA Tranformer on pole structure and fixing of channel /angle etc. and making all connections of HT and LT side and its complete commissioning. |
| 36 | Installation/mounting of new 25 KVA Tranformer on pole structure and fixing of channel /angle etc. and making all connections of HT and LT side and its complete commissioning. |
| 37 | Installation/mounting of new 400 KVA/500 KVA Tranformer on plinth structure and fixing of channel / angle etc. and making all conn ections of Ht and LT side and its complete commissioning. |
| 38 | Installation/mounting of new 250 KVA Tranformer on plinth structure and fixing of channel / angle etc. and making all connections of Ht and LT side and its complete commissioning. |
| 39 | Laying, Spreading, Stringing and sagging of 11 KV / 33 KV line in 3 phase (3 Phase 3 wire) of ACSR Dog as phase wire with G.I. earth wire complete including fixing of all accessories in 3 Nos. conductor in parallel with binding and jumpering as per profile and profile and sagging chart. |
| 40 | Laying, Spreading, Stringing and sagging of 11 KV / 33 KV line in 3 phase (3 Phase 3 wire) of ACSR Panther as phase wire with G.I. earth wire complete including fixing of all accessories in 3 Nos. conductor in parallel with binding and jumpering as per profile and profile and sagging chart. |
| 41 | Guarding of LT/11 KV Line over (Telephone / Road/L.T. line crossing as per drawing with 6/8 SWG G.I. wire including fixing of guarding channel/ angle as per RESSPO manual. |
| 42 | Guarding of 33 KV Line over (Telephone / Road/L.T. line crossing as per drawing with 6/8 SWG G.I. wire including fixing of guarding channel/ angle as per RESSPO manual. |
| 43 | Laying Sagging of LT XLPE AB CABLE 3X120+1X95+1X16 Sq.mm |
| 44 | Jointing and fixing of cable jointing kit indoor/outdoor 11 KV XLPE heat shrinkable cable boxes |
| 45 | Jointing and fixing of cable jointing kit indoor/outdoor 33 KV XLPE heat shrinkable cable boxes |
| 46 | Cartage of ST pole SP-55 Poles from store centre to construction site with loading, unloading at both points and proper stacking.(Distance 71-100 Km) |
| 47 | Cartage of ST pole SP-72 Poles from store centre to construction site with loading, unloading at both points and proper stacking.(Distance 71-100 Km) |
| 48 | Cartage of other material (other than poles) by vehicle from Store Center to nearest construction site Store including loading and unloading at both ends(distance 71-100 Km) |
| 49 | Headload cartage of ST Pole SP-55 from road to site (distance 0-1 Km) |
| 50 | Headload cartage of ST Pole SP-72 from road to site (distance 0-1 Km) |
| 51 | Head load cartage of small material (distance 0-1 Km) |
| 52 | Headload cartage of 25 KVA transformer from road to site(distance 0-1 Km) |
| 53 | Headload cartage of 63 KVA transformer from road to site(distance 0-1 Km) |
| 54 | Headload cartage of 100 KVA transformer from road to site(distance 0-1 Km) |
| 55 | Headload cartage of 250 KVA transformer from road to site(distance 0-1 Km) |
| 56 | Headload cartage of 400 KVA transformer from road to site(distance 0-1 Km) |
| 57 | Headload cartage of 500 KVA transformer from road to site(distance 0-1 Km) |
| 58 | Dismantling of Fencing and Gate of S/S including fabrication cutting and welding works at 33/11 KV Sub Station. |
| 59 | Dismantling of existing 33 KV HT line. including disc fitting, Insulator, clamps, Nut & Bolts and consumer connections and Street light connections etc. including rolling of conductor and cartage back from site to JE store(ACSR Panther/Dog). |
| 60 | Installation of LT distribution box complete work both 1 phase and 3 phase. |
| 61 | Digging of Pit through Hammer at CC, DAMAR Road |
| 62 | Fixing, tightening and nozzling of stay with pole and stay rod on required tension as per drawing/manual in 11 KV line. |
| 63 | Back cartage of petty material, 0-20 Km |
| 64 | Fixing of L.T.Bare Neutrel PG Clamp 50 Sqmm to 25 sqmm Line to Box. |
| 65 | Fixing of Suspension Clamp with I Hook. |
| 66 | Erection of Dead End clamp. |
| 67 | Fixing of PG Clamp 95-95 sqmm |
| 68 | Digging of Pit for Stay Set. |
| 69 | Erection & Laying of 11KV 3x400 Cable in HDPE |
| 70 | Fixing of Insulation piercing connector for Networking/ Branching/looping. |
| 71 | Annexure-B (SUPPLY ITEMS) (As per UPCL Norms) |
| 72 | Supply of Nut & Bolts off size. |
| 73 | Supply of Bracing Clamp for SP-72 |
| 74 | Supply of Bracing Clamp for SP-55 with N/B |
| 75 | Supply of X-Arm Clamp for ST Pole SP-55 with N/B |
| 76 | Supply of X-Arm F Type Hold Clamp for SP-72, MS 75x8 mm. |
| 77 | Supply of Stay Clamp for SP-55 with N/B |
| 78 | Supply of Suspension Clamp Eye Hook LT ABC Cable. |
| 79 | Supply of Stay Clamp for SP-72 with N/B |
| 80 | Supply of MS Clamp with N&B for Distribution box. |
| 81 | Supply of MS Clamp for Dead End Clamp with N&B |
| 82 | Supply of Dead End Clamp with I Hook. |
| 83 | Supply of stay Insulator 75x90 MM. |
| 84 | Supply of HT Stay Insulator |
| 85 | Supply of G.S. Earth with 7/16 SWG. |
| 86 | Supply of Turn Buckle. |
| 87 | Supply of LT Bare N.Connector PG Clamp 95-25 Sq.MM. |
| 88 | Supply of IPC for 120 Sq.MM to 120 Sq.MM. |
| 89 | Supply of PG Clamp for Panther. |
| 90 | Supply of PG Clamp Dog to Dog. |
| 91 | Supply of MS clamp with N&B for Suspension Clamp. |
| 92 | Supply of LT Bare N.Connector PG Clamp for L-L 95-95 Sq.MM. |
| 93 | Supply of GI Pipe 6 inch Diameter (8 No. 8 M each) |
| 94 | Supply of Eye Bolt size 100x16 |
| 95 | Supply of Piercing Connector 120 to 35 Sq.MM |
| 96 | Supply of HDPE Pipe PE 100 PN6 Dia 150MM. |
| 97 | Supply of PP & Clamp with nut & bolt for guarding. |
| 98 | Supply of Disc fitting for panther 120 KN |
| 99 | Supply of 33 KV Disc Insulator polymer, 70 KN B&S |
| 100 | Supply of LT XLPE Cable 1x35 Sq.MM. |
| 101 | Supply of SMC Three Phase L.T. Distribution Box with inbuilt panal lock, Al bus bar RYB 25x6mm., Al Busbar N. 40x6mm. for connection of L.T. consumer (Sintex make or other ISI mark reputed company ) with Panel Lock with key). |
| 102 | Supply of Aluminium Lug 25 Sq.MM Please Enable Macros to View BoQ information |