| 1 | WORK NAME |
| 2 | Construction of tuba-well from ground levels to accommodate housing and assembly pipe of following sizes in all types of alluvium strata by percussion/ rotary drilling method and with gravel as per 15:4097-1967 and packing as per 15:2800 (Part 1- 11) 1979 as amended upto date (the work includes the cost of gravel & its primary packing and packing during development, lowering of housing & strainer assembly pipes, with supply and wrapping of 1 coir-rope, wherever necessary for arresting fine sand particles. The work will not include cost of housing pipe and strainer pips assembly and development work, but work would be completed after obtaining sand free water). Upto 100 Meter depth Nominal bore 150mm dia |
| 3 | Construction of Tube-well upto 100 Meter depth and above in all type of rocks by DTH system and over burden to accommodate casing pipe of following sizes in all types of soils and over burden including lowering of casing pipes but excluding cost of casing pipes as per IS: 2800 (Part I & II) 1979 specifications. The work would be completed after obtaining sand free water. The tube well should have a throughout bore as per nominal dia of casing pipeNominal bore 150mm dia |
| 4 | Supply of ERW M.S. black casing pipe ISI marked (IS: 4270/1992) of grade Fc410 of following nominal bore sizes at site of work. 150 mm dia |
| 5 | Supply and fixing of tube well cover of M.S. sheet (6mm thick) with nuts and bolts complete for casing size: 150 mm dia |
| 6 | P/Laying ISI marked P.V.C. insulated submersible cable confirming to(IS:694) and as per IS 8130: 2013 of 1.1 kV grade. Wire should be made from 99.90% purity copper, stranding in acc. to IS:8130/IEC 60228 for lower watt loss, oxygen free for less chances of oxidization, insulation PVC type A/C/D, flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, existing pipe/open trench / Cable tray / on surface including making connection ete, as required. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR 4.0 Sq.mm 3 core flat / Round |
| 7 | Providing & Fixing of HDPE pips Cosfiring4:22 for water supply suitabits for subscribo dejat pump wit Ratings is suckut, ellews, to ste complain allpost. All r pes approved by Enging. For 6pers of products work, refer Aus \\"A\\" made with sDS for vertical insaallation 40 mm OD 6kg/cm2 |
| 8 | SITC of Radial/mixed Now 151 marked water and sms-potrus liquid fifted submersible motor pump sets suitable for 100/150mm dia borewell. The size of adopter fixed on top of the motor should exoced the top of coupier, for salegaurd the coupler. The construction material of motor and pump should match 15:204: 2018 and 15: 9283 guideline. The radial now pumpsa should operate at 5 star energy efficiency level of BEE and mixed flow pump set should operato at 3 star energy level of BEE, accompained by valid BEE ccrtificate. Moter should be 182 class as per IEC 60034-2-1:2007, IEC 60034-30: 2008, & 1512615-2011 with required accessories including making connection suitable for Bore well. The job includes labour part of lowering of riser pipe G.I/H.D.P.E. with rope, cables & pump. 7 installation of complete fitting and accessories, jointing of clectrical cables up to Staner. All labour for icsting of submersible pumps set and supply of water to water mains, complete in all respect. OEM shall have submit NABL/CPRI/ERDA accredisted lab type test certificate before execution. All as por pes approved by Engineer in-charge. For additional technical parameters of products/ work, refer Annexure \\"A\\" utached with this BSR. 100 mm diameter Submersible pump shall have following HP Rating, phase, Head range, Discharge rango respectively. 2.0 HP, 1 0, (7-95)Mtr, (55-22) LPM |
| 9 | SITC of Contactor OEM Fabricated DOL/Star-Delia Starter panel with switchgear selection as per Type-2 Cordination Chart and made out from 1.6 mm thick powder couted CRCA sheet, enclosure comprising of over load protection relay, short circuit & single phasing protection, Illuminated ON/OFF push butions, ammeter, voltmeter, indicating lamps etc, suitable for following 8 rating motors complete in all respect. All as per pre approved by Engineer in-charge. For additional technical parameters of products/work, refer Annexure \\"A\\" attached with this BSR For single phase Submersible/Monoblock pump 2.0 HP to 3.0 HP (DOL starter) |
| 10 | Providing and fixing 3 layer PP-R (Poly propylene Random copolymer) pipes SDR 7.4 U V stabilized & anti- microbial fusion welded, having thermal stability for hot & cold water supply including all PP-R plain & brass threaded polypropylene random 9 fittings ile fixing the pipe with clamps at 1.00 m spacing. This includes testing of joints complete as per direction of Engineer in- charge. Internal work-Exposed on wall PN-16 Pipe, 25 mm OD |
| 11 | Providing & Fixing in position, MS fabrication work using angles, sqr tubes, c channels ete for various partition frame as per Design & Instructions & Complete in all aspects. including all materials labour, finishing etc complete |
| 12 | Providing and fixing PTMT bib cock of approved quality and colour. 15mm nominal bore, 86 mm long. Weighing not less than 88 gms. |
| 13 | Providing & Laying of Polypropylene rope Confirming to IS:5175 for submersible pump of following sizes. complete in all respect. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work, refer Annexure \\"A\\" attached with this BSR. 12mm (suitable up to 50 mm OD pipe) |
| 14 | Providing and placing on terrace (at all floor levels) polyethylene water storage tank ISI: 12701 marked with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank Please Enable Macros to View BoQ information |