| 1 | Loading, Unloading and safe cartage of the following materials from Electricity Store Centre, Bahraich to the work site/dump site. All the material at Sl. No. 1 shall be given by department and rest all the material including civil material will be arranged by the contractor itself. Any other material if required for completion of work which might not have been mentioned in bid document, shall be arranged by the contractor. (De-Centralized Items Provided by the Contractor as per Estimate). |
| 2 | Cartage of PCC Pole 8.5 Mtr. long |
| 3 | Cartage of PCC Pole 9 Mtr. long |
| 4 | Cartage of PCC Pole 11 Mtr. long |
| 5 | Cartage of 11 KV XLPE Cable 3x185mm sq. |
| 6 | Cartage of 33 KV XLPE Cable 3x120mm sq. |
| 7 | Cartage of 33 KV XLPE Cable 3x300mm sq. |
| 8 | 11 KV VCB O/G CTR 200/100/5 Amp |
| 9 | Cartage of AB Cable 3x95+1x50+1x16mm2 |
| 10 | Cable Jointing Kit (I/D) 3x70sqmm |
| 11 | Cable Jointing Kit (O/D) 3x70sqmm |
| 12 | Cable Jointing Kit (O/D) 3x120sqmm |
| 13 | Cable Jointing Kit (O/D) 3x300sqmm |
| 14 | Cartage of 11 KV 3x185 Straight Through |
| 15 | Cartage of 33 KV 3x120 Straight Through |
| 16 | Cartage of 33 KV 3x300 Straight Through |
| 17 | ACSR Weasel Conductor |
| 18 | ACSR Rabbit Conductor |
| 19 | ACSR Dog Conductor |
| 20 | ACSR Panther Conductor |
| 21 | Earthing |
| 22 | Lighting Arrester |
| 23 | Carriage of Other line material |
| 24 | Erection workMinium depth of laying from ground surface to the top of cable as per IS is-i) Low Voltage (1.1 KV) and Control Cable - 0.75 Mtr.ii) 3.3 KV to 11 KV Cables - 0.90 Mtr.iii) 22 KV to 33 KV Cables - 1.05 Mtr.iv) Cables at Road Crossing - 1.00 Mtr. v) Cables at railway level crossings (measured from bottom - 1.00 Mtr.of sleepers to the top of Pipe)Note 1) - The depth may be increased but not more than 1.6 M2)- The standard depth and width for laying the cable are also attached (as per letter No. 561/Director(Tech.)/MVVNL/Camp/Dt. 09-01-26 561 with the tender form. |
| 25 | Erection of Single PCC Pole (8.5 Mtr Long) for 11 KV/HT line alongwith fitting of all accessories on pole including dragging of pole from Dump Site to pit site. |
| 26 | Erection of Single PCC Pole (9 Mtr Long) for 11/33 KV/HT line alongwith fitting of all accessories on pole including dragging of pole from Dump Site to pit site. |
| 27 | Erection of Single PCC Pole (11 Mtr Long) for 11/33 KV/HT line alongwith fitting of all accessories on pole including dragging of pole from Dump Site to pit site. |
| 28 | Erection of Double PCC Pole (8.5 Mtr Long) for 11 KV/HT line alongwith fitting of all accessories on pole including dragging of pole from Dump Site to pit site. |
| 29 | Cartage, Erection and Grouting of stay sets alongwith complete fittings. Cement, Sand & Brick ballast provided by the contractor at his own cost. |
| 30 | Earthing Complete as per RESSPO Norms. |
| 31 | Grouting of Poles with 1:4:8 CC ratio of cement, sand & brick ballast, backfilling of pits with mud completely. All required materials shall be provided by the contractor at his own cost. |
| 32 | Laying & Commissioning of 11 KV XLPE Cable 3x185mm sq. drilling/Brick & Sand as per respo norms. |
| 33 | Laying & Commissioning of 33 KV XLPE Cable 3x120mm sq. drilling/Brick & Sand as per respo norms. |
| 34 | Laying & Commissioning of 33 KV XLPE Cable 3x300mm sq. drilling/Brick & Sand as per respo norms. |
| 35 | Errection & Commissioning of AB cable 3x95+1x50+1x16mm2 including fitting of Accessories (All Accessories shall be Provided by the Contractor). |
| 36 | Fixing of Cable Jointing kit (I/D & O/D) |
| 37 | Fixing of 11 KV 3x185 Straight Through |
| 38 | Fixing of 33 KV 3x120 Straight Through |
| 39 | Fixing of 33 KV 3x300 Straight Through |
| 40 | Fixing of 11 KV VCB O/G CTR 200/100/5 Amp |
| 41 | Fixing of Lighting Arrester |
| 42 | Laying, stringing, sagging & binding of conductors of 33/11 KV in 3 phase, 3 wire line with jumpering (where as required). |
| 43 | (Decentralized Items Provided/Fixing/Erection/Installation/Laying by the Contractor as per Respo Norms). |
| 44 | Stone Pad |
| 45 | PG Clamp |
| 46 | AI Binding Wire |
| 47 | Holding Clamps for Top & Dropper Channel, T-off Channel. |
| 48 | Holding Clamps for Guarding |
| 49 | Holding Clamps for X-Arm |
| 50 | HDPE Pipe 140mm |
| 51 | Red Oxide Paint |
| 52 | Alluminium Lug Long Barrel off size (LS) |
| 53 | Nut Bolt and washer all sizes |
| 54 | Number Plate with clamp and Nut & Bolt |
| 55 | Danger Board barbed wire including jumper |
| 56 | Danger Plate with Clamp and Nut Bolt |
| 57 | 11 KV F-Clamp |
| 58 | GI Barbed wire Please Enable Macros to View BoQ information |