| 1 | Sub Head I |
| 2 | Supplying, Installation, Testing & Commissioning of following capacity passenger Machine room less (MRL) lift with regenerative drive as per CPWD General Specification for Electrical Works (Part-III Lift & Escalator) 2003, BIS Codes, NBC 2016 as amended upto date having provision for barrier free access as per Harmonised Guidelines & Standards for Universal Accessibility in India - 2021 of MoHUA, serving different floors in the lift shaft as per detailed specifications enclosed and as under including all other equipment and accessories complete as required:-(i) Speed-1 MPS(ii) Floors-2 (G+1)(iii) Travel - 6 to 8 Meters (approx.)(iv) Stops & opening- 1 stops and 1 openings (All Floor are opening in same side)(v) Controller: A.C. variable voltage & variablefrequency(vi) Automatic rescue device (ARD) complete with dry maintenance free batteries as required.vii) Operation: Microprocessor based single automatic push button/simplex selective collective/duplex collective selective with/ without attendant(viii) Power-415 Volts+10%, 3 phase, 50 Hz, 4 wires system(ix) Car Enclosure: Stainless steel scratch proof (Moon Rock/Honeycomb/ Hairline Finish) on all sides and stainless steel decorative ceiling with fans (indirect throw) and LED fitting.(x) The car flooring should be smooth and antiskid as approved by engineer-in-charge.....................Cont................................ |
| 3 | (xi) Type of doors(a) Car: Power operated, center opening horizontal sliding stainless steel scratch proof (b) Landing doors: stainless steel scratch proof.(xii) A hand rail not less that 600mm long at 900mm above floor level to be fixed adjacent to control panel in the lift car.(xiii)Voice announcement system in the car to announce the position of the elevator in the hoist way as the car passes or stops at floor served by the elevator.(xiv) Closed loop Control System, protection against power fluctuation, self diagnostic control, Landing doors 2 hours Fire rated, Overload detection and protection, Overspeed Governer, Dot Matrix LED D &P Indicators In Car & Landings, BMS Compatibility, tamper proof infrared curtain covering almost the entire height of the lift car door, Alarm horn, Anti Nuisance Operation, CCTV camera system with 4 MP IP camera, suitable NVR and HDD for 30 days storage backup , Firemen switch, 2/3 way intercom, Emergency Stop Switch with battery backup for fan and light fitting for 1 hour, pit ladder.(xv) The lift doors shall have a vision panel to enable persons with hearing impairment to signal for help or assistance in the event of an emergency.(xvi) An appropriate technological support be provided (Through emergency messaging services or alarms etc.) to respond to the emergency requirements of person with hearing impairment or deafness....................Cont............................ |
| 4 | (xvii) In case of failure of ARD or other electronic devices, a provision of manual rescue be provided(After installation of lift one year is defect liability period & no extra amount will be paid for any kind of repair/maintenance) |
| 5 | Supplying, Installation, Testing & Commissioning of following capacity passenger Machine room less (MRL) lift with regenerative drive as per CPWD General Specification for Electrical Works (Part-III Lift & Escalator) 2003, BIS Codes, NBC 2016 as amended upto date having provision for barrier free access as per Harmonised Guidelines & Standards for Universal Accessibility in India - 2021 of MoHUA, serving different floors in the lift shaft as per detailed specifications enclosed and as under including all other equipment and accessories complete asrequired:-(i) Speed-1 MPS(ii) Floors-2 (G+1)(iii) Travel - 6 to 8 Meters (approx.)(iv) Stops & opening- 1 stops and 1 openings (Ground Floor & First Floor are opening opposite side)(v) Controller: A.C. variable voltage & variablefrequency (vi) Automatic rescue device (ARD) complete with dry maintenance free batteries as required.vii) Operation: Microprocessor based single automatic push button/simplex selective collective/duplex collective selective with/ without attendant(viii) Power-415 Volts+10%, 3 phase, 50 Hz, 4 wires system(ix) Car Enclosure: Stainless steel scratch proof (Moon Rock/Honeycomb/ Hairline Finish) on all sides and stainless steel decorative ceiling with fans (indirect throw) and LED fitting.(x) The car flooring should be smooth and antiskid as approved by engineer-in-charge.(xi) Type of doors..................Cont........................ |
| 6 | (a) Car: Power operated, center opening horizontal sliding stainless steel scratch proof.(b) Landing doors: stainless steel scratch proof .(xii) A hand rail not less that 600mm long at 900mm above floor level to be fixed adjacent to control panel in the lift car.(xiii)Voice announcement system in the car to announce the position of the elevator in the hoist way as the car passes or stops at floor served by the elevator.(xiv) Closed loop Control System, protection against power fluctuation, self-diagnostic control, Landing doors 2 hours Fire rated, Overload detection and protection, Overspeed Governer, Dot Matrix LED D & P Indicators In Car & Landings, BMS Compatibility, tamper proof infrared curtain covering almost the entire height of the lift car door, Alarm horn, Anti Nuisance Operation, CCTV camera system with 4 MP IP camera, suitable NVR and HDD for 30 days storage backup , Firemen switch, 2/3 way intercom, Emergency Stop Switch with battery backup for fan and light fitting for 1 hour, pit ladder.(xv) The lift doors shall have a vision panel to enable persons with hearing impairment to signal for help or assistance in the event of an emergency.(xvi) An appropriate technological support be provided (Through emergency messaging |services or alarms etc.) to respond to the emergency requirements of person with hearing impairment or deafness.(xvii) In case of failure of ARD or other electronic devices, a provision of manual rescue be provided(After installation of lift one year is defect liability period & no extra amount will be paid for any kind of repair/maintenance) |
| 7 | Earthing with G.I. earth pipe 4.5 Meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 8 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) |
| 9 | Supplying and laying of following PVC insulated and PVC sheathed /XPLE armounrd Aluminum Conductor power cable of 1.1 KV grade of following size in the existing RCC/ HUME METAL/PVC pipe as required. |
| 10 | 4 X 10 Sq. mm armounrd Aluminum conductor power cable |
| 11 | 3.5 X 50 Sq. mm armounrd Aluminum conductor power cable |
| 12 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required.63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 13 | Providing and fixing in position collapsible steel shutters with vertical channels 20x10x2 mm and braced with flat iron diagonals 20x5 mmsize, with top and bottom rail of T-iron 40x40x6 mm, with 40 mm dia steel pulleys, complete with bolts, nuts, locking arrangement, stoppers,handles, including applying a priming coat of approved steel primer. |
| 14 | Fabrication, Supplying and installation of outdoor type cubical feeder pillar of size 1700mm x 1000mm x 300mm of M.S. sheet 2mm thick (14 SWG) duly compartmentalised having 4 strip busbars of 100amp capacity double door with two nos. godown locking arrangement for protection from rain, dust, duly fixed on M.S. angle iron frame work of size 40 mm X 40 mm X 6 mm (NS) 900 mm long legs out of which 45 cm duly grouted in cement concrete 1:2:4 (1 cement 2 sand :4 stone aggregate 20 mm) and having following accessories mounted inside the cubical panel i/c connection, inter connection with aluminum thimbles, earthing with two nos. earth studs duly painted with one coat of red oxide & two coats of superior quality enamel paint complete etc. as reqd. Supplying & Fixing of following accessories in the existing cubical panel board/feeder pillar including connection testing etc. as reqd.Indoor Panel (more than or equals to 1.3 Sqm.)Incoming:-Fabrication, Supplying and installation of outdoor type cubical feeder pillar of size 1700mm x 1000mm x 300mm of M.S. sheet 2mm thick (14 SWG) duly compartmentalised having 4 strip busbars of 100amp capacity double door with two nos. godown locking arrangement for protection from rain, dust, duly fixed on M.S. angle iron frame work of size 40 mm X 40 mm X 6 mm (NS) 900 mm long legs out of which 45 cm duly grouted in cement concrete 1:2:4 (1 cement 2 sand :4 stone aggregate 20 mm) and having following accessories mounted inside the cubical panel i/c connection, inter connection with aluminum thimbles, earthing with two nos. earth studs duly painted with one coat of red oxide & two coats of superior quality enamel paint complete etc. as reqd...................Cont......................... |
| 15 | Supplying & Fixing of following accessories in the existing cubical panel board/feeder pillar including connection testing etc. as reqd.Indoor Panel (more than or equals to 1.3 Sqm.)Incoming:- a) 250Amp. 25 KA MCCB, TP with neutral link- 1 No.b) Spreder Link for MCCB -1setc) 110A FP power contactor -1 Nos.d) Digital Timer – 1 Nos.Metering:-a) Digital Ammeterb) Digital Voltmeterc) R. Y. B indication Lampd) ASS + VSS Selecter Switche) 6A SP MCB 10KA For Controllingf) CT 200/5A Class-1Outgoing:-a) 125Amp. 18 KA MCCB, TP with neutral link -3 Nos.b) Spreder Link for MCCB -3 set |
| 16 | Fabricating, Supplying and fixing wire mesh protection frame work made out of 40 x 40 mm x 6 mm thick angle and \\"T\\" strengthened with intermediate menberers of MS flat iron of size 32 x 6 mm x 5 mm thick welded at a distance of 30 cm horizontally and vertically and duly welded with wiremesh of size 75 mm x 25 mm made with 6 SWG wire mesh of size 75 mm x 25 mm made with 6 SWG wire on all sides and top i/c providing and fixing of double door gate with double locking arrangement ( Two nos. sliding bolts and one No. go down lock) having 0.5 mtr long legs of 40 mm x 40 mm x 6 mm thick angles iron, duly grouted in cement concrete foundation ration 1:2:4 (1 cement : 2 coarse sand: 4 graded stone aggregate) upto suitable depth painting with on coast of red oxide & two coats of synthetic enamel paint of approval colour and shade etc. complete as reqd. |
| 17 | Supplying and Fixing of 4.5 Kg capacity CO2 type Fire Extinguisher ISI marked Confirming to IS: 15683 complete with delivery horn, squeeze grip release valve, locking arrangement, operation manual, bracket with two screw and sleeve and suitable hanging arrangement complete in all respect etc as reqd. |
| 18 | Supplying and Fixing of 6 Kg duly ISI Marked confirming to Is: 15683-2006 with IS 14609 ISI marked ABC powder complete with squeeze grip release valve, discharge pipe, locking arrangement, pressure gauge, operation manual, bracket with two screw and sleeve and suitable hanging arrangement complete in all respect Please Enable Macros to View BoQ information |