Tender For Engineering, Procurement And Construction (Epc) Of Demolition Of Building No P-73 And Reconstruction Of Auditorium Cum Cinema Hall At installation Hamla, Mumbai
Tender Overview
Project Description
Tender for Engineering, Procurement And Construction (Epc) Of Demolition Of Building No P-73 And Reconstruction Of Auditorium Cum Cinema Hall At installation Hamla, Mumbai
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 27-Jun-2026 | Tender Amendment | Other | 06-Jul-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | SCHEDULE 'A' PART- I BUILDINGS & STRUCTURES INCLUDING INTERNAL & EXTERNAL SERVICES AS DEFINED IN ANNEXURE I TO XIV (EPC) |
| 2 | Design & Construction of Auditorium Cum Cinema Hall, AC Plant room (including Central Air conditioning system complete), Sub Station building & pump house cum sump (Fire fighting & Domestic use) details as per scope of work and other documents of tender, complete all as specified and directed. |
| 3 | SCHEDULE 'A' PART 1A (BUILDINGS & STRUCTURES WORKS) Total of Sch-'A' Part-1A B/F |
| 4 | SCHEDULE 'A' PART-II (SITE CLEARANCE, AREA DEVELOPMENT, EXCAVATION & EARTHWORK)Total of Sch-'A' Part-II B/F |
| 5 | SCHEDULE 'A' PART-III (DEMOLITION & DISMANTLING)Total of Sch-'A' Part-III B/F |
| 6 | SCHEDULE 'A' PART-IV (ROAD, HARD STANDING & CULVERT) Total of Sch-'A' Part-IV B/F |
| 7 | SCHEDULE 'A' PART-V (SEWAGE DISPOSAL)Total of Sch-'A' Part-V B/F |
| 8 | SCHEDULE 'A' PART-VI (AREA DRAINAGE)Total of Sch-'A' Part-VI B/F |
| 9 | SCHEDULE 'A' PART-VII (RAIN WATER HARVESTING) Total of Sch-'A' Part-VII B/F |
| 10 | SCHEDULE 'A' PART-VIII (EXTERNAL ELECTRIFICATION) Total of Sch-'A' Part-VIII B/F |
| 11 | SCHEDULE 'A' PART-IX (EXTERNAL WATER SUPPLY)Total of Sch-'A' Part-IX B/F |
| 12 | SCHEDULE 'A' PART-X (Water Cooler) Total of Sch-'A' Part-X B/F |
| 13 | SCHEDULE 'A' PART- XI (MISCELLANEOUS ITEMS) |
| 14 | DEMOLITION / DISMANTLING |
| 15 | Removal Debris obtained from demolition of bldg outside MD land (i) Before quoting the tender, the bidders are advised to ascertain the distance outside MD and, at which the excavated material/ debris are to be disposed off. No extra claim what-so-ever shall be entertained on this account.(ii) This item shall be considered as per the requirement at site. |
| 16 | External Electrification |
| 17 | Supply, install, testing and commissioning of indoor 11 KV HT switch gear, extendible type, vertical isolation and horizontal draw out, vacuum circuit breaker (VCB), rupturing capacity 350 MVA, 630 Amps, with DC tripping arrangement mounted on structural steel frame outdoor type with separate indoor control panel with over current and earth fault relays of suitable rating and each fitted with following :-(a) 01 Nos vacuum interrupters of rating 11 KV, 3 phase, 50 Hz, 350 MVA, 630 Amps mounted on common base segregated epoxy body for higher electrical insulation and to maintain pole discrepancy as per IEC 56 and self aligned type isolating contacts, manual and motor operating (230 volt AC ), spring charged mechanism, 24V DC shunt Close coil with CT/ PT , manual closing and tripping push buttons, mechanical operation counter 8 NO+8NC breaker operating auxiliary switch, spring charge /discharged indication, circuit breaker service /test position indication all as directed - 1 No.(b) Self powered microprocessor controlled numeric relay comprising of two over current, one earth fault protection relay with high set for both phase and earth with fault memory, universal auxiliary supply. Make : ABB / Siemens / L&T Schneider/ Easun Rayroll / Ashida IS:3231, 88686. The setting for over+B19 current shall be 50-200% of 5A (in the step of 10%) and for earth fault element from 20- 80% of 5A (in the step of 10%). |
| 18 | (c) 1 No. 96 Sqmm flush pattern digital ammeter (0 - 100A) suitable to CT ratio. Make : AE / MECO / L&T / Secure / C&S with (d) 1 No. 3 way and OFF ammeter selector switch for reading the current in any phase on the above ammeter.(d) 1 No. 96 sqmm flush pattern digital voltmeter (0-12 KV) suitable to the CT ratio. Make - AE / MECO / L&T / Secure / C&S batteries complete suitable for protection / operation of relays-01 No. with 1 No. 3 way and OFF voltmeter selector switch for reading the voltage between two phases on the voltmeter (f) Multifunctional meter -1No(g) 1No. AC static, HT, Trivector meter. Meter should be supplied with Backlit LCD/LED display of measured value (s) shall be displayed on seven segment, seven digit liquid crystal display (LCD/LED) Display unit / register. |
| 19 | (i) RED /GREEN- VCB ON-OFF indication, (ii) Amber:- Trip indication, (iii) White:- Trip circuit healthy indication with push button, (iv) BLUE:- VCB mechanism spring charged indication(m) One set of heat shrinkable PVC sleeved, 400 amps copper busbar-1 set(n) 1 No. panel space strip heater-100 watt(cotinuosly rated) with thermostate with manual ON-OFF switch-1 set(o) Structural steel frame including PCC fdnand earth work as per manufacturer specification.(p) 1 No 3 way breaker control switch with positions TRIP- NEUTRAL -CLOSE(q) Manual charging/ operaing arrangment.(r) Fuses for metering and protection system(s) (i) Auto trip (ii) Motor /manual charged spring operating /closing mechanism. (iii) Fault alarm (iv) Manua tripping (t) Complete control panel wiring with suitable size copper e (u) Test Terminal Block (TTB) to test meters and relays with sealing arrangement. (t) Power pack with 1AH batteries and |
| 20 | NOTE:- (i) Contractor shall submit the technical drawing, Constructional drawings, safety features drawing etc.for approval of accepting officer. (ii) The contractor shall intimate for factory inspection for routine tests as per 1s & ANSIC-57.12.90 (Latest revision) in the OEM factory in presence of rep nominated by accepting officer before despatch from factory. Tests after installation shall also be carried out through SEl for which GE will intimate through proper channel. |
| 21 | Supply and fix adapter panel rated 11 KV/630 Amps ,3 ph,,with Copper Bus Bar (R-Y-B) for direct bus coupling to the existing RMU(Make ABB) on site with existing VCB in existing sub stn.Note: Copper BUS BAR in the adapter panel shall be directy coupled to the VCB with BUS-to- BUS coupling and not accepted by any cable or through HT fuse and contractor shall visit the site to inspect the RMU/VCB for manufacturing the adaptor before placing the order complete all as specified and directed. |
| 22 | Supply, Install, test and commission, Indoor type, LT panel box, cubicle type, factory fabricated, CPRI approved (any company from list of make), panel board made with 2 mm thick CRCA Sheet, weather and vermin proof, floor mounted, Class 7 tank process, powder coated in siemens gray colour inside and outside, 3 phase, 4 wire system copper bus bar mounted on hygroscopic insulator housed in separate bus bar chamber covered with R-Y-B and black PVC heat shrinkable sleeve, with 50mmx50mmx6mm angle iron frame with and including PCC 1:3:6 type C2 foundation and covering front and back opening hinged door along with suitable locking arrengement including necessry bus bar tappings, copper control wiring of required size, connecting cable with necessary cable glands, lugs etc, independent chamber to accomodate the MCCBs MCBs, measuring instruments, Bus bar and cable gallary chember ,proper arrangements for ventilation complete with provn for connecting earthing at both sides of panel board and comprises as following:- (MAIN PANEL) |
| 23 | INCOMERi)MCCB microprocessor based release 4 pole 400 A, incomer, 415V, 50Hz, 50 KA - 01 No. (Incomer) |
| 24 | OUTGOINGi) MCCB 4 Pole,400 A, 415V, 36 KA microprocessor based release - 2 Nos. (for AMF PANEL, Spare)ii) MCCB 4Pole, 100 A, 415V, 25 KA microprocessor based release - 2 No. (APFC Panel, Spare ) |
| 25 | BUSBARi) 500 A rated copper bus bar with colour coded heat shrinkable sleeve |
| 26 | METERING & INDICATIONi) Ammeter,Digital type, with suitable CTs - 5 setii) Voltmeter, Digital type - 01 setiii) R-Y-B phase indicating lamp- 03 Nosiv) Multifunction meter -01 |
| 27 | Supply, Install, test and Commission, Indoor type, LT panel box, cubicle type, factory fabricated, CPRI approved (any company from list of make), panel board made with 2 mm thick CRCA Sheet, weather and vermin proof, floor mounted, 7 tank process, powder coated in siemens gray colour inside and outside, 3 phase, 4 wire system copper bus bar mounted on hygroscopic insulator housed in separate bus bar chamber covered with R-Y-B and black PVC heat shrinkable sleeve, with 50mmx50mmx6mm angle iron frame with and including PCC 1:3:6 type C2 foundation and covering front and back opening hinged door along with suitable locking arrangement including necessary bus bar tappings, copper control wiring of required size, connecting cable with necessary cable glands, lugs etc, independent chamber to accomodate the MCCBs MCBs, measuring instruments, Bus bar and cable galley chamber, proper arrangements for ventilation complete with provn for connecting earthing at both sides of panel board and comprises as following:- (UTILITY PANEL ) |
| 28 | INCOMERi) MCCB 4 pole 400 A, 415V, 50Hz, 36 KA microprocessor based release- 01 No. (Incommer) |
| 29 | OUTGOINGi) MCCB 4P 160 A, 25 KA microprocessor based release - 03 Nos (AC plant,Bldg, Spare)ii) MCCB 4P 125 A,25 KA microprocessor based release - 02 Nos (Fire fighting+ SPARE)iii) MCCB 4P 63 A,16 KA microprocessor based release - 01 Nos (WS Pump Panel)iv) MCB TP 40 A - 3 Nos (Booster pump + street lights + Spare).v) Digital timer switch - 01 Nos |
| 30 | BUSBAR500 Amps copper bus bar with colour coded heat shrinkable sleeve |
| 31 | METERING & INDICATIONi) Ammeter, Digital type, with suitable CTs - 01 setii) Voltmeter, Digital type - 01 setiii) R-Y-B phase indicating lamp- 03 Nosiv) Multi function meter with suitable CT's -01 No. |
| 32 | Supply, Install, test and commission, Indoor type, LT panel box, cubicle type, factory fabricated, CPRI approved (any company from list of make), panel board made with 2 mm thick CRCA Sheet, weather and vermin proof, floor mounted, Class 7 tank process, powder coated in siemens gray colour inside and outside, 3 phase, 4 wire system copper bus bar mounted on hygroscopic insulator housed in separate bus bar chamber covered with R-Y-B and black PVC heat shrinkable sleeve, with 50mmx50mmx6mm angle iron frame with and including PCC 1:3:6 type C2 foundation and covering front and back opening hinged door along with suitable locking arrangement including necessary bus bar tappings, copper control wiring of required size, connecting cable with necessary cable glands, lugs etc, independent chamber to accomodate the MCCBs MCBs, measuring instruments, Bus bar and cable gallary chamber, proper arrangements for ventilation complete with provn for connecting earthing at both sides of panel board and comprises as following:- (BLDG PANEL) |
| 33 | INCOMER |
| 34 | i) MCCB 4 pole 160 A , 415V, 50Hz, 25 KA thermal magnetic release - 01 No. (Incommer) |
| 35 | OUTGOING |
| 36 | i) MCCB 4 Pole, 63 A, 415V, 16 KA thermal magnetic release - 4 Nos. |
| 37 | ii) MCB TPN 40 A - 2 Nos |
| 38 | iii) MCB SPN 40 A - 2Nos |
| 39 | BUSBAR |
| 40 | i) 200 A rated copper bus bar with colour coded heat shrinkable sleeve |
| 41 | METERING & INDICATION |
| 42 | i) Ammeter,Digital type, with suitable CTs - 01 set |
| 43 | ii) Voltmeter, Digital type - 01 set |
| 44 | iii) R-Y-B phase indicating lamp- 03 Nos |
| 45 | iv) Multifunction meter -01 |
| 46 | Supply, Install, test and commission, Indoor type, LT panel box, cubicle type, factory fabricated, CPRI approved (any company from list of make), panel board made with 2 mm thick CRCA Sheet, weather and vermin proof ,floor mounted, Class 7 tank process, powder coated in siemens gray colour inside and outside, 3 phase, 4 wire system copper bus bar mounted on hygroscopic insulator housed in separate bus bar chamber covered with R-Y-B and black PVC heat shrinkable sleeve, with 50mmx50mmx6mm angle iron frame with and including PCC 1:3:6 type C2 foundation and covering front and back opening hinged door along with suitable locking arrangement including necessary bus bar tappings, copper control wiring of required size, connecting cable with necessary cable glands, lugs etc, independent chamber to accomodate the MCCBs MCBs, measuring instruments, Bus bar and cable gallery chamber ,proper arrangements for ventilation complete with provn for connecting earthing at both sides of panel board and comprises as following:- WATER SUPPLY PUMP PANEL |
| 47 | i) MCCB 4 pole 63 A, 415V, 50Hz, 16 KA thermal magnetic release- 01 No. (Incomer) |
| 48 | ii) MCB TP 32 A -02 No (for 2 Nos of Pumps) |
| 49 | iii) DOL Starter up to 5HP- 02 Nos (for 2 Nos of Pumps) |
| 50 | iv) Ammeter, Digital type, with suitable CTs - 03 set |
| 51 | v) Voltmeter, Digital type - 03 set |
| 52 | vi) R-Y-B phase indicating lamp- 03 set |
| 53 | vii) Multifunction meter -01 set |
| 54 | viii) 100 Amps copper bus bar with colour coded heat shrinkable sleeve |
| 55 | M&L for 7 meter long hot dipped galvanised octagonal poles with top A/F 70 mm bottom A/F 155 mm made out of 3mm thick HT sheet along with base plate of size 260X260 X16 mm including 1500 mm long single arm bracket made out of 48 mm dia GI pipe and M20 x700 m long 'J' type EN8 grade foundation bolts along with template including the following:(a) MCB SP 6A 230 V,10 kA mounted on 3 mm thick Hylam Sheet -1 No.(b) 4 Way connector bolt along with locking arrangement, weather proof and water proof control space.Note: (a) The Rate quoted deemed to include the cost of 50 mm PVC pipe from cable trench to center of the pole concrete and 'J' type EN8 grade foundation bolts.(b) The rate quoted deemed to include the cost of connecting of incoming and outgoing cable in new octagonal poles through PVC pipe including taking out loop extending up to junction box and PCC foundation as per OEM Pole foundation Drawing, connecting complete all as specified and directed. |
| 56 | M&L for 3 Core 1.5 Sq mm size multistranded copper conductor PVC unsheathed 650 / 1100 Volt Grade drawn in through steel tubular poles, for interconnection of cable looping box to Street Light Fitting complete all as specified and directed. |
| 57 | Supply & Fix HT Cable route indicator made out of cast iron 10 cm dia duly engraved with letters 'HT CABLE 11000 Volts\\" fixed in 20mm X 20 mm equal angle 0.5 mtr long icluding provision of PCC foundation/ block 1:2:4 of 20 cm X 20 Cm X 20 cm complete all as specified and directed. |
| 58 | External Water Supply |
| 59 | Supply and install, test and commissioning of monoblock Pumping set, electric driven, 3 phase, 440V, 50Hz, confirming to IS-12469:1988 with CI casing bronze impller and stainless steel shaft mounted on heavy duty berings suitable for 450 LPM discharge and 30 mtr head (minimum capacity of pump 5HP) and including suitable size of PCC foundation with grouting of pumping set complete all as specified and directed (Pump 01 running + 01 Standby). |
| 60 | Supply and fix Cast Iron Air Valves with single air Outlets, conforming to IS 14845 of size 50 mm dia bore and fixing up in Cast Iron Water supply mains of size 50 mm dia |
| 61 | Supply and fix foot valve conforming to IS:4038 50 mm dia. |
| 62 | Supply and fix 4 Sqmm 3 Core Flat copper conductor Cable PVC insulated using starter panel to pumps and motors complete all as directed. |
| 63 | Construction of brick masonry valve chamber of size 0.9m x0.9m x 0.9 mtr (internal dimension) above ground level 30 cm suitable for 100 mm dia sluice valve, 15 cm thick foundation using PCC 1:4:8 type D-2 (using 40 mm graded stone aggregate) over 15 cm thick hardcore, 23 cm thick brick wall, bults in cement and sand mortor 1:4, 15 cm thick internal and external plaster including top of floor in cement and sand mortor 1:3, finished even and smooth, without using extra cement, 10 mm thick mild steel plate cover on 50 mm x 50mmx6 mm MS angle iron frame embeded in PCC 1:2:4 type B-1 (using 20 mm graded stone aggregate) coping having rectangular hinged opening of size with locking arrangement & handle made out of 25 cm dia MS round bar, hold fasts etc, applying one coats of red oxide primer and two coats of synthetic enamelled paint to all steel surfaces and earth work in any type of soil including disposal of surplus soil to a distance not exc. 50 mtr complete . |
| 64 | Water Cooler |
| 65 | Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 240 V with output voltage stabilized at 220 with accuracy ± 2.5% and speed of correction 8 Volts per second and of capacity 1 KVA |
| 66 | Stand by DG Set |
| 67 | Supply installation, testing & commissioning of factory assembled Diesel Engine driven generating set coupled with alternator AC to give continuous output of 250 KVA at a power factor of 0.8 lagging, 415 volts, AC, 3 phase, 4 wire, 50 HZ, 1500 RPM, diesel engine liquid cooled, mounted on common base frame complete with in built fuel tank of adequate capacity with fuel line & accessories, PCC foundation work as per manufacturer's instructions, vibration damper pads, micro processor based relay panel for automatic starting on mains failure, control panel showing all parameters of engine & alternator, sound proof canopy & other accessories etc. and confirming to the under mentioned technical specifications as per specified & directed. |
| 68 | (A) DIESEL ENGINE : Water cooled, turbo charged,1500 RPM under NTP conditions conforming to CPCB IV+ Norms with an overload capacity of 10% for 12 Hrs of continuous operation as per complete with the following accessories. |
| 69 | (a) Radiator with blower fan with guard |
| 70 | (b) Pipe coupling for cooling system |
| 71 | (c) Corrosion inhibitor coolant |
| 72 | (d) Filters for fuel/lube oil |
| 73 | (e) Fly wheel housing and fly wheel suitable for alternator |
| 74 | (f) Engine bearing mechanism in fly wheel housing |
| 75 | (g) Shut off coil protection with safety for LLOP /HWT/ Over speed/high and low DC voltage. |
| 76 | (h) Dry type heavy duty replaceable paper element air cleaner with restriction indicator and vacuum indicators . |
| 77 | (J) Residential silencers. |
| 78 | (k) Stainless steel exhaust flexible bellows. |
| 79 | (m) Electric starter motor |
| 80 | (n) Battery charging alternator. |
| 81 | (o) Exhaust piping made out of STIC \\"C\\" class MS Pipe inclusive of all accessories and hardware, necessary support as per manufacturer’s recommendations to sustain back pressure with rain cap. |
| 82 | (n) Battery charging alternator. |
| 83 | (q) First fill of oil, coolant and diesel during commissioning. |
| 84 | (r) Interconnecting copper cabling of adequate capacity between batteries and controller. |
| 85 | (s) Fuel pipe. C class STIC 1\\"/1.5\\"/2\\" dia - 01 lot |
| 86 | (t) Self starter 12 volts DC, mechanical/electrical control and electronic control governor. |
| 87 | (u) Metering equipments for recording |
| 88 | (i) Battery voltage and charging rate |
| 89 | (ii) Coolant temperature |
| 90 | (iii) Lubricating oil pressure |
| 91 | (iv) Engine speed (RPM) |
| 92 | (v) Engine hours run |
| 93 | (vi) Balance of fuel. |
| 94 | (v) Safety as protection control (Trip and indication) |
| 95 | (i) High water temperature |
| 96 | (ii) Low Lube oil pressure |
| 97 | (iii) Low and high speed trip |
| 98 | (iv) High and low DC voltage |
| 99 | (v) over speed Stop |
| 100 | (w) Base frame : Sturdy fabricated welded construction, channel iron base frame (duly painted) for mounting engine and alternator as per manufacturer’s design alongwith AVM pads |
| 101 | (x) Battery: 01 Nos , 12 Volt, 180 AH maintenance free with leads and terminals |
| 102 | (y) Fuel Tank : As per Manufacturer diesel storage capacity full tanks with mounting brackets factory made of 5mm thick HR. MS sheet with level indicator fuel inlet, fuel out let, air vent, drain plug, in let arrangement for diesel filling from exterior of canopy (without opening its panel) etc. complete all as specifid and directed. |
| 103 | (B) ALTRERNATOR : 250 KVA at 0.8 PF lagging, 415 volts, 3 Phase, 4 wire, 50 Hz at 1500 RPM self excited and self regulated with AVR brushless excitation band of voltage ± 1% of rated voltage from no load to full load insulation class H, self ventilated and conforming to IS4722, BS5000, IEC 34/1, IS0 8528, BS5514, I503046, suitable for above mentioned diesel engine. |
| 104 | (C) ACOUSTIC ENCLOSURE : M & L for acoustic for the above 125 KVA DG set to reduce noise level to 75 dB measured at 1.0 distance for audible frequencies as per guidelines of Central p[ollution Control Board as manufacturer's specification and commissioning of follwing from authorised OEMs of Gen Set Manufactures Specified:- (i) Sound insulation : 100 mm thick Rock wool (density 64 KG/Cum)(ii) Outer body : 1.6 mm thick CRCA(iii) Door : 1.6 m thick CRCA(iv) Innar asaurface : 1.0 mm thick CRCA/ GI sheet(v) Base Frame :ISMC 300(vi) inside illumination : 1 no - 1 x 18 wat FTL fitting |
| 105 | (D) Automatic Main Failure control (AMFC) panel:- Indoor type, factory fabricated cubical type, free standing, floor mounted, AMF control panel with all necessary connections complete, provided with removable rear door & hinged front door for easy accessibility, fabricated out of not less than 2.0 mm thick CRCA Sheet powder coated CPRI approved comprising of following :- |
| 106 | (i) AMF control circuit with 4 pole, MCCB 400 Amps cu of 35/36 kA at 415 volts - 02 Nos micro processor based with thermal and magnetic release setting 70% to 100%. each one for Main supply and DG set supply incoming supply with HRC back up fuse complete with all DC control relays/line voltage monitor (LVM) as per OEM specifications incorporating engine start and stop complete as specified and directed. |
| 107 | (ii) Digital ammeter (0-500 amps) and voltmeter (0-500 Volts) with selector switch |
| 108 | (iii) Digital frequency meter. |
| 109 | (iv) Digital power factor meter (-1.0 to +1.0) |
| 110 | (v) Indicating lamps for supply \\"ON\\" and Load \\"ON \\" |
| 111 | (vi) Instrument fuses (HRC type) |
| 112 | (vii) Push button 01 No each for start, stop & reset |
| 113 | (Viii) Copper busbar of capacity 200 amps. for phases and neutral |
| 114 | (ix) Bottom gland plate including glands for incoming and outgoing LT cables |
| 115 | (x) Circuit diagram plate |
| 116 | (xi) Automatic battery charging unit including facility for over charging stop /trickle charging /boost charging 12 volt complete with DC ammeter, DC voltmeter, Charging set selector switch, |
| 117 | (xii) Facility for remote / auto start, auto/manual synchronizing ,audio-visual annunciation and indication lamps for engine fault |
| 118 | (E) Civil Work :-All civil work related to foundation for DG set and installation of panel and equipment and depth of foundation shall be minimum 300 mm with antivibration pads, or as recommended by the manufacturers. Cables from DG set to AMF panel to main panel will be measured under relevant schedule.Note:- The fuel for final testing of 12 hours shall be supplied by the contractor and cost deemed to be included in the above offer. All other necessary equipments like resistance load strip heater of suitable capacity/rating and any other items required for final testing shall be provided by the contractor without any extra cost to department. |
| 119 | ARBORICULTURE |
| 120 | Supply and Fixing fine sand at site including royalty and carriage for preparing compost at site (sand shall be brought at site and stacked for measurement before incorporating in the work). |
| 121 | Supply and Fixing sweet/good earth at site including royalty and carriage for preparing compost for pits/required for planting trees and shrubs etc (sweet/good earth free from objectionable extraneous matter, toxic material and termites shall be brought at site and stacked for measurement before incorporating in the work 20% of computed volume shall be reduced for loose stacking. |
| 122 | Supply and Fixing manure at site including royalty and carriage for preparing compost at site (manure shall be brought at site and stacked for measurement before incorporating in the work 8% computed volume shall be reduced for loose stacking. |
| 123 | M &L for Preparing compost pits of size 0.60x0.60x0.60 by excavation in ordinary soil, applying ant termite treatment , planting trees & refilling of the pit with compost (manure sand & sweet earth mixed in ratio (1:1:4) breaking colds, ramming and flooding with water filling with more compost if necessary and fine dressing including removal of rubbish unserviceable materials & surplus soil to a distance n.exc 100 mtr. ATT shall be in form of 200 gms neem cake mixed 2 ml per litre in the first watering of 20 litres per pit. Note :-1. The rate for excavation and getting out of soil shall be deemed to be included in the unit rate of this item .2. The rate for mixing earth, manure and sand, deemed to be included in the unit rate of this item. |
| 124 | Preparing compost pits of size 0.90x0.90x0.90 mtr by excavation in ordinary soil , applying ant termite treatment, planting the tree & refilling of pit with compost (manure sand & sweet earth mixed in ratio 1:1:4 ) breaking clods, ramming and flooding with water with more compost if necessary and fine dressing including removal of rubbish unserviceable materials and surplus soil to a distance n.exc 100 mtr. ATT shall be in form of 200 gms neem cake mixed with every cum of compost followed by Dussban or equivalent applied at 2 ml Pee litre in the first watering of 20 litrs per pit.Note :- 1. The rate for excavation and getting out of soil shall be deemed to be included in the unit rate of this item. 2. The rate for mixing earth, manure and sand, deemed to be included in the unit rate of this item. |
| 125 | Supply and planting following trees in location where shown on drawing and described in schedule ‘A’ and specifications/directed by Engr-In-Charge, girth 80mm to 100mm minimum (measured at 150mm top of roots) and height as shown :- |
| 126 | ALBIZZIA LEEBEK 6’ Height. |
| 127 | ALSONIA SCHOLARIS 6’ Height |
| 128 | BAUHINIA PURPUREA 4’ Height |
| 129 | CARYOTA URENS 6’ Height |
| 130 | ERYTHRINA INDICA 6’ Height |
| 131 | FICUS INFECTORIA 6’ Height |
| 132 | LAGERSTOEMIA FLOS REGIME 6’ Height |
| 133 | PUMERIA ALBA 6’ Height |
| 134 | ROYSTONEA REGIA 6’ Height |
| 135 | SHOREA ROBUSTA 4’ Height |
| 136 | PLUMERIA RUBRA 6’ Height |
| 137 | BAMBUSA VALGARISA 6’ Height |
| 138 | BOTTLE PALM 4’ Height |
| 139 | ASHOKA PENDULA 4’ to 6’ Height |
| 140 | Supply and planting shrubs i.e Aclypha 2’, calliandraz’ , crotons 3’, Hamcha, Jasminum capensis Hibisew', Ticoma as directed by Engr-in-Charge |
| 141 | Supply and plantation of grass selection No 1 by dibbling root method. Note : (a) Ploughting of whole site in soft/ordinary soil upto the depth of 20 cm and removing all the unwanted material such as stones, weads, trees root etc which are not suitable for healthy growth of grass.(b) Dressing and leveling the soil to a required gradient and slope on complete work mentioned in Note (a)above after loosening the soild. (c) Mixing of fertilizers and manure evenly by manually as under :-(i) MANUREOld cow dung or Okhla sludge at the rate of 2.25 cubic feet for 10 Sqm.FERTILIZERS(i) Neem Kholi at the rate of 2 Kg for 10 Sqm.(ii)Benemeal at the rate of 1 Kg for 10 Sqm(iii) DA (16.42 ) at the rate of 0.15 Kg for 10 Sqm(iv) BHC dust 10% or Pin dance dust at the rate of 0.15 kg for 10 Sqm (v)Weedicide at the rate of 0.01.Note:- The manure and fertilizers to be mixed evenly upto maxiumu depth of 15 Cm(d) Fine dressing of top soil after mixing the manure and fertilizers to a required slope.(e) Watering the area after fine dressing of soil after one week continuously still the soil get water upto 10 to 15 cm deep.(f) Final dressing of top surface of soil to required slope an gradient towards the manholes. (g) Plantation of glass at the rate of 10 cm C/C both ways by dibbling root method. |
| 142 | M&L 60 mm thick precast cement concrete 1:2:4 type B-1 using 20mm graded aggregate as in lawn pavers of size 60cm x60 cm with a gap of 50mm either side over 50mm thick approved earth including filling earth in the gaps (good for growing glass) as per specifications, the pattern, design shape and location as directed by Engr-in-Charge complete all as specified. |
| 143 | S&F 25mm GI tubing medium grade galvanised with all fittings and fixed complete to walls and ceiling or laid in floors :- |
| 144 | Ditto but 20 mm of size. |
| 145 | S&F sprinklers of cast brass alloy 20 mm dia with wheeled pipe stand complete all as specified directed. |
| 146 | S&F 15mm bore chromium plated fancy type bib taps long body with crutch or butterfly handle, screwed down for iron pipe or for brass ferrule. |
| 147 | S&F GI union socket of 25 mm complete all as specified and directed. |
| 148 | S&F 20mm dia low density polyethylene pipe (LDPE) pressure rating 6kg/Sqcm laid in trenches commplete all as specified and directed. |
| 149 | FURNITURE |
| 150 | Manufacture & Supply of Chair push back as specifed 1. Flexi High Back with cupholder Main Chair - Spcification - \\"SEAT ASSEMBLEY : The seat assembly is made of polyurethance foam moulded with M.S tubularframe insert which is upholstered with foam laminated fabric. The insert is tubular frame made of 1.9+ 0.02 cm x 0.16 + 0.013 cm thk MS. E.R.W round tube with flexible support straps running across the length and width of the frame. The seat has an auto-tiput feature making it stay in upright position when not in use enabling clear row passage \\" Approx. Seat Size : 45.5cm(W) x 46.5cm(D).2. BACKREST ASSEMBLY : The back assembly has a flexi back mechanism. It is made of polyurethance foam moulded with M.S. tubular frame insert,upholstered with foam laminated fabric and has a plastic back cover. The insert is a tubular frame made of 1.9 + 0.02cm x0.16 + 0.013 cm thk M.S E.R.W round tube with flexible support straps running across the lenght and width of the frame. \\"Approx. Back Size : High Back - 45.5cm(W) x 82.4cm(H).3. HIGH RESILIENCE (HR) POLYURETHANE FOAM : The HR polyurethane foam is moulded with density = 45 +/- 3kg/m3 4. SIDE PANEL/AISLE PANEL : The chair rests on the ground on two side panels fabricated using 8.0+ 0.03 cmx 4.0 + 0.03cm x 0.12 + 0.0096 cm M.S ERW Tubes which are CO2- Argon Welded. The side panel frame is grouted to the floor using 2 nos of anchors for each panel through M.S. bush which are welded to 5.0 + 0.03cm x 2.5 + 0.03cm x 0.12 + 0.0096 cm tube. The Anchor Bolts are covered with polypropylene Foundation Bolt Cover.5. PP ARMREST WITH CUP HOLDER : The Amrest is made up of compounded Polypropylene. The Armrest is fitted with the side panel. |
| 151 | Manufacture & Supply of Chair CBA steel with arms and including cushioned seat and back complete all as specified and shown on drawing No. FD-75(M) |
| 152 | Manufacture & Supply of Recepatacle PVC 20 Ltr (MAP), complete all as specified and shown on drawing No. FD/E6/MAP/13 |
| 153 | Manufacture & Supply of Stool steel 2\\" high, complete all as specified and shown on drawing No. FD-81. |
| 154 | Manufacture & Supply of Table office clk steel, complete all as specified and shown on drawing No. FD-1004. |
| 155 | Manufacture & Supply of Desk stand lecture, complete all as specified and shown on drawing No. FD-125(M). |
| 156 | Manufacture & Supply of Settee for 4 pers/Sofa set for four person , complete all as specified and shown on drawing No. FD-281. |
| 157 | Manufacture & Supply of Stool dressing, complete all as specified and shown on drawing No. FD-282. |
| 158 | Manufacture & Supply of Chair CB steel w/o arms and incuding cushioned seat and back, complete all as specified and shown on drawing No. FD-75(M). |
| 159 | Manufacture & Supply of Table 3' x 2' with drawer steel, complete all as specified and shown on drawing No. FD-1008. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 3 daysBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 3 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender