| 1 | Supply, laying & testing High Tension XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables of size 3 core 95 sq mm (heavy duty ) with stranded aluminium conductor, 11000 volts grade Earthed complete all as specified and as directed. |
| 2 | Supply and erection Steel tubular swaged poles with cast iron base plate, finial taper plug,bolt,nuts and screws as specified type 410 SP-55, 11 meter long complete all as specified and as direced. |
| 3 | Material and labour for Mild steel cross arm bracing, supports, clamp and back plates fabricated from structural steel section including nuts, bolts, washers, welding, bending cold or hot,drilling holes for bolts in any shape or size as indicated including painting two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed. |
| 4 | Material and labour for Pin type, porcelain, vitrous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one G I nuts, 150 mm height , 150 mm dia for 11000 volts grade complete all as specified and as directed. |
| 5 | Material and labour for anti climbing device, spike type fabricated out of M S bars (round square and flat) including nuts, bolts washers, and welding into two halves made to shape to suit the cross section of pole complete all as specified and directed. |
| 6 | Material and labour for HT danger notice plate for 25x20 cm size, 1.6 mm thick mild steel, vitreous enamelled white, with letters, figure and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts nuts complete all as specified and directed. |
| 7 | Supply and fix H T 11 KV, out door type gang operated air-break switch (GOD) suitable for vertical mounting fixed type complete with 15 insulators of rating upto 200 Amps, Triple pole, mechanically operated, mounted on insulator and steel frame, with operating mechanism worked from ground level, including drop out fuse set complete all as specified and direced. |
| 8 | S&F Lightening arrestors expulsion type with all fittings, transmission class, Discharge capacity 65 KA for 11KV HT line complete all as specified and as directed. |
| 9 | S & F in repair Explusion fuse unit 11 KV drop out up to 100 Amps complete all as specified and as directed. |
| 10 | M&L for Earthing with Galvanized steel earth plate electrode 60 cm x 60 cm x 6mm thick buried directly in ground vertically to a depth not less than 2.25 mtr below ground level with top edge of earth plate at a depth not less than 1.5 mtr connected to galvanized earth lead wire 4 mm dia as earth lead up to 7.5 mtr long by means of nuts, bolts, thimbles,check nuts and washers etc made of galvanized iron connected to earthing test point all as shown in electrical plate No 3 of SSR Part-I and as specified or indicated and testing on completion including necessary earth work and excavation in any type of soil, PCC (1:3:6) type C1 chamber, pre cast slab 40mm thick in cement concrete (1:2:4) type B1 with 8 mm dia TMT bars reinforced at 10 cm centre to centre both ways, M S handle, funnel with watering pipe, wire mesh and lugs, test point complete all as specified and as directed. |
| 11 | M & L for Earthing with galvanized steel earth plate electrode 60 cm x 60 cm x 6mm thick buried directly in ground vertically to a depth not less than 2.5 mtr below ground level with top edge of earth plate at a depth not less than 1.5 mtr connected to and including galvanized iron strip 25x4mm as earth lead up to 7.5 mtr long by means of nuts, bolts, thimbles,check nuts and washers etc made of galvanized iron connected to earthing test point all as shown in electrical plate No 3 of SSR Part-I and as specified or indicated and testing on completion including earth work and excavation in any type of soil, PCC (1:3:6) type C1 chamber, pre cast slab 40mm thick in cement concrete (1:2:4) type B1 with 8 mm dia TMT bars reinforced at 10 cm centre to centre both ways, funnel with watering pipe, wire mesh and lugs, test point complete all as specified and as directed. |
| 12 | Supply and fix cable end termination jointing kit suitabler for 11 KV grade cable, cold shrink outdoor type complete with jointing materials and accessories suitable for 3 core XLPE armoured Aluminium conductor cable of size of 95 Sqmm complete all as specified and as directed. |
| 13 | Supply and fix straight through jointing kit suitable for 11 KV grade cable, cold shrink type outdoor complete with jointing materials and accessories suitable for 3 core XLPE armoured Aluminium conductor cable of size of 95 Sqmm complete all as specified and as directed. |
| 14 | Supply and fix Galvanised Iron pipe 80 mm dia bore, light grade with all fittings for cable protection complete all as specified and as directed. |
| 15 | Excavation in trenches in soft / loose soil not exc 1.5 mtr wide and not exc 1.5 mtr in depth for laying of cables etc complete all as specified and as directed. |
| 16 | Excavation in trenches in soft / loose soil not exc 1.5 mtr wide and exc 1.5m but not exc 3mtr in depth for laying of cables or erection of poles etc complete all as specified and as directed. |
| 17 | Returning, filling in trenches including spreading, leveling, watering and well ramming in layers with soil not exc 25 cm thick in each layer complete all as specified and as directed. |
| 18 | Removing excavated soil to a distance not exc 50m and depositing not exc 1.5 mtr above the starting point complete all as specified and as directed. |
| 19 | M & L for Sand cushioning with a layer of river sand 23 cm thick under and above the cable all as per Para 19.75 of SSR part I complete all as specified and as directed.(NOTE:- Punned thickness of 18cm shall be measured for payment) |
| 20 | M&L for un-reinforced Pre-Cast Concrete Cable Cover class HV, type -II flat Size 300 X 180 X40mm for cable protection complete all as specified and as directed. |
| 21 | Material and labour for Plain cement concrete (1:4:8) type D-2 using 40mm graded stone aggregate as in foundations, filling and mass concrete complete all as specified and as directed. |
| 22 | Material and labour for Plain cement concreate (1:2:4) type B-1 using 20mm graded stone aggregate as in coping of pole, in roof kerb or mud stop, rounded or chamfered on edges including necessary formwork complete all as specified and as directed. |
| 23 | Boring of holes under road, pavement, hard standing by trenchless using ultra sounding technique using necessary machine including S & F HDPE pipe of 80 mm dia bore suitable for 0.4 mpa working pressure complete all as specified and as directed. |
| 24 | Supply, install, testing & commissioning of outdoor type, welded stainless steel tank with IP-67 protection for SF-6 Tank and IP 54 protection for outdoor enclosure, both Side extensible type compact RMU (3 way) : one incomer+ one breaker + two outgoing (2OD+1 VL), 11kV, 350MVA, 650 Amps, 21KA (VCB SF6 enclosed) as per IEC-62271, outgoing with copper bus bar, manometer,cable boots for VCB and castle key interlocked and necessary PCC foundation work including providing MS channel and MS angle as per manufacturer recommendation along with bottom cable entry and front cable termination of suitable single run 3core 400sqmm HT cable with following specifications and accessories complete all as specified and as directed:- |
| 25 | (i) A01 as incoming VCB, A02 Outgoing load break switch with three position isolator /earthing switch, bus bars, interlocking earth bars and stored spring energy mechanism.(ii) Stored energy mech for manual operation - 01 No.(iii) Set of 03 No’s Ring core protection CTs of suitable ratio as per feeder load, 1.0 VA, Class 0.1- 01 set in breaker (Transformer rating 1MVA).Capacitive voltage indication fixed type VPIS 9- 15KV - 01 No inbreaker(iv) Control voltage motor 2x12V DC,12AH battery +24V DC battery charger(v) Self powered OC+EF Protection relay type as per manufacturer recommended with rechargeable - 01 No in each breaker(xi) Impluse withstand voltage: To earth and between phases: 75KV Insulation level: -Power frequency 1 min:28 Kv Please Enable Macros to View BoQ information |
| 26 | (i) A01 as incoming VCB, A02 Outgoing load break switch with three position isolator /earthing switch, bus bars, interlocking earth bars and stored spring energy mechanism.(ii) Stored energy mech for manual operation - 01 No.(iii) Set of 03 No’s Ring core protection CTs of suitable ratio as per feeder load, 1.0 VA, Class 0.1- 01 set in breaker (Transformer rating 1MVA).Capacitive voltage indication fixed type VPIS 9- 15KV - 01 No inbreaker(iv) Control voltage motor 2x12V DC,12AH battery +24V DC battery charger(v) Self powered OC+EF Protection relay type as per manufacturer recommended with rechargeable - 01 No in each breaker(xi) Impluse withstand voltage: To earth and between phases: 75KV Insulation level: -Power frequency 1 min:28 Kv Please Enable Macros to View BoQ information |