| 1 | Dismantalling existing ACSR (of any size or type) from over head elctric line and poles carefully with out making any damage to the other existing lines and removing from site, complete all as per specified and as directed by Engineer-in-charge. |
| 2 | Dismantaling of GI Earth wire and guard wire and gurad wire from existing OH Line, complete all as per specified and as directed by Engineer-in-charge. |
| 3 | Dismantalling of Insulator of any size / grade from over head electric line and setting aside removing from site, complete all as per specified and as directed by Engineer-in-charge. |
| 4 | Dismantalling of cross arms , bracing, support etc of MS Channel or any other section complete and setting removing unserviceable portion from site work, complete all as per specified and as directed by Engineer-in-charge. |
| 5 | Excavation in trenches n.exc 1.5m wide and n.exc 1.5 m in depth for foundation etc or for shafts, wells, cesspits, manholes, pier holes etc n.exc 10 sqm on plan and n.exc 1.5m in depth and getting out in soft/loose soil complete all as per specified and as directed by Engineer-in-charge. |
| 6 | Returning, filling in, including spreading, leveling, watering and well ramming in layers n exc 25cm complete all as per specified and as directed by Engineer-in-charge. |
| 7 | Removing excavated material not exc. 50 m & depositing where directed at a level not exc. 1.5 m above starting point complete all as per specified and as directed by Engineer-in-charge. |
| 8 | Supply, Laying & testing cable XLPE insulated screened PVC beded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with multi stranded aluminium conductor, 1100 volts grade, of size 3.5 core 150 Sqmm, complete all as per specified and as directed by Engineer-in-charge. |
| 9 | Supply, Laying & testing cable XLPE insulated screened PVC beded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with multi stranded aluminium conductor, 1100 volts grade, of size 3.5 core 70 Sqmm, complete all as per specified and as directed by Engineer-in-charge. |
| 10 | Supply, Laying & testing cable XLPE insulated screened PVC beded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with multi stranded aluminium conductor, 1100 volts grade, of size 4 core 16 Sqmm, complete all as per specified and as directed by Engineer-in-charge. |
| 11 | Supply, Laying & testing cable XLPE insulated screened PVC beded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with multi stranded aluminium conductor, 1100 volts grade, of size 4 core 10 Sqmm, complete all as per specified and as directed by Engineer-in-charge. |
| 12 | Demolition of Cement concrete in ground floors and paving not exc 15 cm thickness (below or above GL), complete all as specified and as directed by Engineer-in-charge. |
| 13 | M&L for providing cement concrete type B2 1:2:4 using 40mm graded aggregate in foundation filling and mass concrete, complete all as specified and as directed by Engineer-in-charge. |
| 14 | M&L for Earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6.0 mm thick, buried directly in ground (earth pit not less than 2.25 mtrs deep below ground level) with top edge of the plate not less than 1.5 mtr below normal ground level connected to galvanized iron strip 32x6 mm as earthing lead by mean of bolts , nuts, check nuts and washer of galvanized iron or steel all as shown in electrical plate No 3 of SSR part I of 2009 connected to earthing test point all as specified complete with excavation and earth work PCC pit with 50 mm thick RCC cover (grade M-15) having suitable handle (10 mm MS Rod) 20 mm dia GI light grade ISI marked watering pipe with GI funnel with wire mesh 40 mm bore GI Pipe ISI marked (light grade) for protection of earth lead conductor all as directed and testing on completion, complete all as specified and as directed by Engineer-in-charge. |
| 15 | Supply and lay in trenches, fixed to wall/pole DWC Pipes (Double Wall Corrugated) of dia. 90mm type 450 (450N) as per IS:16025 Part 24 standard for carrying UG cable, complete all as per specified and as directed by Engineer-in-charge. |
| 16 | Supply and lay in trenches, fixed to wall/pole DWC Pipes (Double Wall Corrugated) of dia. 40mm type 450 (450N) as per IS:16025 Part 24 standard for carrying UG cable, complete all as per specified and as directed by Engineer-in-charge. |
| 17 | Supply, lay, commissioning and testing of cable jointing Kit for 1100 V grade cable for outdoor Straight Though heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 70 Sqmm to 150 Sqmm in any posn panel, pole, plinth etc, complete all as per specified and as directed by Engineer-in-charge. |
| 18 | Supply, lay, commissioning and testing of cable jointing Kit for 1100 V grade cable for outdoor End Termination heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 70 Sqmm to 150 Sqmm in any posn panel, pole, plinth etc, complete all as per specified and as directed by Engineer-in-charge. |
| 19 | Supply, lay, commissioning and testing of cable jointing Kit for 1100 V grade cable for outdoor End termination heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 25 Sqmm to 50 Sqmm in any posn panel, pole, plinth etc, complete all as per specified and as directed by Engineer-in-charge. |
| 20 | Supply, lay, commissioning and testing of cable jointing Kit for 1100 V grade cable for outdoor End termination heat shrink type joint complete with jointing material and accessories suitable for 6 sqmm 2 core to 16 Sqmm 4 core armoured aluminium conductor cable in any posn panel, pole, plinth etc, complete all as per specified and as directed by Engineer-in-charge. |
| 21 | M&L for cutting of existing road/hard standing not exc 25x45 cm in wide & depth getting out excavated material for laying cable/GI tube, returning filling & well ramming watering, finishing surface 15 cm from top using PCC 1:3:6 type C1 including removal of surplus soil, complete all as per specified and as directed by Engineer-in-charge. |
| 22 | S&F MCB Single Pole (SP), C-Curve, 230 volts of capacity 6-32 Amp, 10 KA, complete all as specified and as directed by Engineer-in-Charge. |
| 23 | M&L in replacement of 40 mm dia steel tubes (light grade) galvanised with fittings, clamp, nuts, bolta and washers and laid/fix in trenches/wall/pole for protection of underground cable, complete all as per specified and as directed by Engineer-in-charge. |
| 24 | M&L in replacement of 80 mm dia steel tubes (light grade) galvanised with fittings, clamp, nuts, bolta and washers and laid/fix in trenches/wall/pole for protection of underground cable, complete all as per specified and as directed by Engineer-in-charge. |
| 25 | M&L for fabricated CECA outdoor junction box (250mm X 200mm X 120mm) powder coated with hinge operated front opening door suitable for cable entry and out upto 16 sqmm four core duly fixed with dinrail and connector/bus bars suitable for 3 phase cable including clamps nut, bolts and washer etc., complete all as specified and as directed by Engineer-in-charge.Note:- The contract sum shall be calculated by deducting the amount shown in Credit Schedule attached to this tender, from total amount of Schedule 'A'/BOQ. Please Enable Macros to View BoQ information |