| 1 | Taking down copper/aluminium point wiring (light, fan, socket or power) complete, including fixtures and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fitting etc. removing materials to store for keeping in safe custody or for taking into credit (credit for above items shall be made as per condition laid down under schedule of credit seprately ) and making good disturbed surfaces of walls, floors etc complete all as specified and directed |
| 2 | Material and Labour for point wiring using approved colour coding as per IS ( Red, black and green for single phase circuits), with multi stranded copper conductor 1.5 Sqmm nominal cross sectional area,single core, PVC insulated and sheathed FRLS cable1100 volts grade , ISI-694 (1990) marked with valid CML No in and including medium grade,PVC casing & capping of suitable size on walls/roof/floor etc, ISI marked with suitable accessories , mild steel/ pressed steel sunken box of 1.2 mm thick and 60 mm deep ( with earth dolly ) duly painted with two coat of anti corrosive paint/aluminium paint over a coat of red oxide primer internally and two coats of black bituminous paint over a coat of red oxide externally , covered with 3 mm thick plastic laminated sheet cover for fixing of switches, sockets and fan regulator etc, including PVC insulated multistranded copper conductor 1.5 Sqmm nominal cross sectional area single core FRLS cable as earth continuity conductor to common earth and connecting to earth dolly complete all as specified and directed by engr in charge for the following :- Make: Polycab /Finolex/ Plaza |
| 3 | One fan/light /bell point controlled by one switch/bell push |
| 4 | One switch socket outlet 5 Amps on independent board |
| 5 | One socket outlet 5 Amps on the same board |
| 6 | All as per Item No 2 here-in-before but with 2.5 Sqmm PVC insulated multistranded copper conductor cable including 2.5 sqmm PVC insulated but sheathed copper conductor FRLS cable 1100Volts grade and 2.5 sqmm as earth continuity conductor for one switch socket outlet 15 Amps on independent board complete all as specified and directed by Engr- in - Charge. |
| 7 | All as per Item No 2 here-in-before but with 4.0 Sqmm PVC insulated multistranded copper conductor cable including 4.0 sqmm PVC insulated but unsheathed copper conductor FRLS cable 1100Volts grade and 4 sqmm as earth continuity conductor for power socket on independent board complete all as specified and directed by Engr- in - Charge. |
| 8 | Material and Labour for point wiring using approved colour coding as per IS ( Red, black and green for single phase circuits), with multi stranded copper conductor 1.5 Sqmm nominal cross sectional area, single core, PVC insulated and unsheathed FRLS cable1100 volts grade , ISI-694 (1990) marked with valid CML No in and including medium grade, PVC Conduit of suitable size on walls/roof/floor etc, ISI marked with suitable accessories , mild steel/ pressed steel sunken box of 1.2 mm thick and 60 mm deep ( with earth dolly ) duly painted with two coat of anti corrosive paint/aluminium paint over a coat of red oxide primer internally and two coats of black bituminous paint over a coat of red oxide externally , covered with 3 mm thick plasticlaminated sheet cover for fixing of switches, sockets and fan regulator etc, including PVC insulated multistranded copper conductor 1.5 Sqmm nominal cross sectional area single core FRLS cable as earth continuity conductor to common earth and connecting to earth dolly complete all as specified and directed by engr in charge for the following :-Make: Polycab /Finolex/ RR |
| 9 | One fan/light /bell point controlled by one switch/bell push |
| 10 | One switch socket outlet 5 Amps on independent board |
| 11 | One socket outlet 5 Amps on the same board |
| 12 | All as per Item No 5 here-in-before but with 2.5 Sqmm PVC insulated multistranded copper conductor cable including 2.5 sqmm PVC insulated but unsheathed copper conductor FRLS cable 1100Volts grade and 1.5 sqmm as earth continuity conductor for one switch socket outlet 15 Amps on independent board through medium PVC conduit complete all as specified and directed by Engr- in - Charge. |
| 13 | All as per Item No 5 here-in-before but with 4.0 Sqmm PVC insulated multistranded copper conductor cable including 4.0 sqmm PVC insulated but unsheathed copper conductor FRLS cable 1100Volts grade and 2.5 sqmm as earth continuity conductor for power socket on independent board through medium PVC conduit complete all as specified and directed by Engr- in - Charge. |
| 14 | Material and Labour for sub main wiring but using two single core multistranded PVC insulated copper conductor FRLS Cable of size 4 sqmm 1100 volt grade drawn into and including PVC Cassing capping of suitable size including 4.0 sqmm. PVC multi standard copper conductor FRLS cable in green colour for continious earthing including chiselling/cutting of wall, floor, making hole through wall & making good disturbed surfaces of wall/floor/ceiling to match with existing surface including taking down old unserviceable/burnt wiring of any type or size complete all as specified and directed by Engr-in-Charge..Note: Two single core cable, earth wire and PVC conduit shall be measured as one length. |
| 15 | All as per item no 08 above but cable of size 6 Sqmm complete all as specified and directed. |
| 16 | Supply and fix ceiling rose surface bakelite with three terminals type complete all as specified and directed |
| 17 | Supply and fix switch piano type one way 6 Amps flush type, 240volt AC complete all as specified and directed |
| 18 | Supply and fix socket outlet 2 in1, 3 pin 5 Amps complete all as specified and directed |
| 19 | Supply and fix switch socket combination(SSC) 2 in 1, 3 pin, 5 Amps flush type, 240 volt AC complete all as specified and directed |
| 20 | Supply and fix switch piano type 16 Amps flush type ,240volt AC complete all as specified and directed |
| 21 | Supply and fix socket outlet 2 in 1, 3/ 5 pin 16 Amps flush type complete all as specified and directed |
| 22 | Supply and fix switch socket combination(SSC) 2 in 1, 3/5 pin, 16 Amps flush type ,240volt AC complete all as specified and directed |
| 23 | Supply and fix Bell push, flush type, 6 Amp flush type, 240volt AC complete all as specified and directed |
| 24 | Supply and fix switch piano type two way 6 Amps flush type, 240volt AC complete all as specified and directed |
| 25 | Supply and fix Bell push, Modular type, 6 Amp flush type, 240volt AC complete all as specified and directed |
| 26 | Supply and fix modular switch 1 way 6A 1 module complete all as specified and directed. |
| 27 | Supply and fix modular switch 2 way 6A 1 module complete all as specified and directed. |
| 28 | Supply and fix modular socket 6A 2/3 pin combined 2 module complete all as specified and directed. |
| 29 | Supply and fix in repair modular socket 6A /16A 2/3 pin combined 2 module complete all as specified and directed. |
| 30 | Supply and fix modular fan regulator,120 watt - 2 module complete all as specified and directed. |
| 31 | Supply and fix stepped type electronic fan regulator 120 watt ,240 olt flush type on the existing phenolic laminated sheet complete all as specified and directed |
| 32 | Supply and fix electric bell Ding Dong, AC 230 volts complete all as specified and directed. |
| 33 | Supply and fix Modular white cover plate with frame of following size complete all as specified and directed. |
| 34 | 1 module |
| 35 | 2 module |
| 36 | 3 module |
| 37 | 4 module |
| 38 | 6 module |
| 39 | 8 module |
| 40 | Supply and fixing in repair RCCB 63 A , four pole, 30 mA complete all as specified and directed by Engr-in-chrge.Make: Hager/L&T/Standard |
| 41 | Supply and fix in repair industrial wall mounted plug socket suitable for IP 44 degree of protection of 32Amps rating 2P+E complete all as specified and directed.Make: L&T/Indoasian/Legrand/C&S |
| 42 | Supply and fix in repair sheet metal enclosures for double door distribution board factory made duly painted of following capacity with 200 amps rated bus bar , suitable for fixing MCB /Isolators complete all as specified and directedMake: L&T/legrand/Havells |
| 43 | 12 way SPN , 240V |
| 44 | 8 way SPN 240V |
| 45 | 4 way TPN ,415V |
| 46 | 8 way TPN ,415V |
| 47 | Supply and fix in repair MCCB 125 Amps, 4 pole, Breaking capacity 16 KA, 415 V adjustable type complete all as specified and directed.Make: L &T /Legrand/Indoasian/standard. |
| 48 | All as per item no 31 Above but of capacity 100 Amps. |
| 49 | Supply and fixing miniature circuit breaker (MCB) of following current carrying capacity, in the MCB DB complete with connection testing and commissioning complete all as specified and directed .Make: L&T /Legrand/Havells |
| 50 | SP 5/6 AMP to 32 AMP,240V, 10 KA 'B' curve |
| 51 | SP 40 AMP, 240V, 10 KA 'B' curve |
| 52 | SPN 32 Amps, 240V, 10 KA 'C' curve |
| 53 | SPN 40 Amps , 240V, 10 KA 'C' curve |
| 54 | TPN 63Amps, 240V, 10 KA 'B' curve |
| 55 | Taking down old unserviceable fitting and Supply and fix wall mounted extruded aluminium housing high quality indoor batten of following capacity colour temperature 6500 K (4' long) lumen 2000 -3000, PF> 0.9, THD less 15% diffused connecting with three core flexible copper wire from connecto to ceiling rose/angle holder as per existing site requirement complete all as per specified and directed.Make : Havells/wipro/Halonix Note :- The rates are inclusive of cost of square box-02 Nos including suitable size of clamps and screws etc. |
| 56 | LED tubelight fitting of 20 watt/22 watt , 4 Ft long |
| 57 | LED tubelight fitting of 10watt, 2 Ft long |
| 58 | Taking down old unserviceable Tube light fitting of any type and Supply and fix wall/ceiling mounted Inverter LED tube light fitting 4' feets long with opal diffuser and having aluminium body. Energy efficient high quality invertor batten should have Lithium ion battery of 3.7V, 19 WH having inbuilt battery backup upto 2Hrs with high power brightness having BIS certification, LED fitting should be LM 80 certified with system efficacy greater than 100 lumens/watt, including LED tube 20/22 watt having colour temperature 6500 K , PF> 0.95, THD less 10%, with IP20 protection having open and short circuit protection, having input voltage range 90V to 300V connecting with three core flexible copper wire from connector to ceiling rose/angle holder as per existing site requirement complete all as per specified and directed. Make : Havells/Jaquar/Halonix/Crompton .Note :- The rates are inclusive of cost of square box-02 nos including suitable size of clamps and screws etc. |
| 59 | Taking down old unserviceable fitting and Supply and fix Recess mounting LED flat panel light fitting of following wattage and size with efficient LEDs lumen 2000 to 3000, PF> 0.9, THD less 15% complete all as per specified and directed . Make : Havells/wipro/Halonix |
| 60 | 36 watt, 600mm x 600 mm size |
| 61 | 18/20 watt, (1x1 )ft long |
| 62 | Circular in size 18/20 watt not less then 6 '' dia |
| 63 | Taking down old unserviceable fitting and Supply and fix wall mounted high quality indoor wall bracket light cylinderical/oval shape aesthetically designed fitting with B22D lamp holder and 12 Watt bulb temp range 4000k to 6500 K as per site requirement connecting with three core flexible copper wire complete all as specified and directed by Engr-in-charge. Make : Halonix /Havells/wipro/Benlo |
| 64 | Taking down old unserviceable bldg security light and Supply and fix high efficent LED building security light 30 watt, 230 volts, lumen 2000 to 3000, PF>0.9, THD less 10% made of pressure cast aluminium housing with high power LEDs, lens and toughned glass IP 66 connecting with three core flexible copper wire from connection to ceiling rose complete all as per specified and directed Make: Halonix/Bajaj/Havells |
| 65 | Supply and fix in repair bracket for mounting building security light made out of 40 mm dia Light Grade GI pipe bend in angle with holding MS clamps two nos each bracket of size 25x3 mm including screw etc for fixing complete all as specified and directed by Engr in charge |
| 66 | Decarbonizing of indoor MCB DB's / Meter box panel and distribution panel of bldgs by dismantling the old MCCB's, old Bus bars , cable connections, old Amps meter and old voltmeter and cleaning the panel with ctc solvent, and removing the old/burnt control wiring, replacing the old/burnt bus bar of any size if any and fixing properly the hanging/loose front and rear opening doors of the panels, by welding of hinges including welding of broken MS sheet using extra sheets of required size also replacing burnt thimbles with new existing size thimbles, indicator lamps, including powder coating painting of panel with suitable 'U' type gasket to make it dust and vermin proof, providing fancy locks incluidng dismantling the existing connected cables and re-connecting the same cables complete all as specified and directed by Engr -in- charge. |
| 67 | Material and Labour for earthing complete in repairs with galvanized steel earth plate electrode 600 mm x 600 mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below ground level) with top edge of plate not less than 1.5 mtr below normal ground level connected to 4.0 mm dia galvanized earth lead wire by means of nuts bolts check nuts and GI washers including PCC pit in PCC 1:2:4 type B-1 (20 mm graded stone aggregate) RCC cover 20 mm dia (medium grade) GI watering pipe with funnel wire mesh and protection pipe of GI of suitbale size upto 7.5 mtr length including charcoal black cotton soil as required at site to achieve the earthing result and common salt, excavation earth work etc in any type of starta complete all as shown in electrical plate No 3 as specified, GI wire suitable size and length for continuity earth wire from test point to main distribution Board complete all as directed. Note: Rate for achieving required depth by compressor machine if required is deemed included in item unit rate. |
| 68 | Material and Labour for repairs /re-fixing on exiting or new location to storage type electric water heater (geyser) of storage capacity 25/35/50 ltrs of any make comprising of the following works mentioned here under againt Ser Nos (a) to (f) at different locations (a) Inspection, taking down, opening ( dismantling ) descaling, brushing, cleaning of storage tank (b) Examine water tightness of storage tank after cleaning.(c) Carry out operation of all stop cocks, pressure reducing valves etc. to ensures free movement of the working parts. (d) Supply and fix Replacement of the rubber / PVC gasket to ensure water tightness. (e) Checking of safety valve (f) Testing of geysers after repairs. |
| 69 | Supply and fix in repairs thermal cutout ISI marked temp range 50 degree to 80 / 90 degree as required at site for geyser of capacity 25/35/50 Ltr of any make complete all as directed by Engr-in-charge |
| 70 | Supply and fix in repairs of safety valve/high pressure valve ISI marked as per site requirement or complete all as per directed by Engineer-in-Charge. |
| 71 | Supply and fix in repairs heating element of following rating as required at site including rubber washers complete all as specified and directed by Engr-in-charge. |
| 72 | 1/1.5 KW,240 volt |
| 73 | 02 KW ,240 volt |
| 74 | Supply and fix in repairs of PVC pipe with brass hexagonal adopters both side, suitable for 15 mm dia pipe 60 cm long for cold water connection complete all as specified and directed by Engr-in-Charge |
| 75 | Supply and fixing in repairs metal braided PVC/CP pipe with brass hexagonal adopters both side, suitable for 15 mm dia pipe 45 CM long for hot water connection complete all as specified and directed by Engineer-in-charge. |
| 76 | Supply and fixing in repairs, non return valve 15 mm dia of brass, ISI marked complete all as specified and directed by Engineer-in-charge. |
| 77 | Supply and fix in repairs stop valve , cast copper alloy screw down high pressure crutch handle, screwed both end for iron pipe suitable for 15 mm bore complete all as specified and directed by Engr-in-Charge |
| 78 | Material and Labour in repairs for following unserviceable copper container of capacity 25/50 Ltrs of solar water heater of any type after completion of work testing the heater complete all as specified and directed by Engr-in-Charge |
| 79 | Copper container 50/100 ltr of water heater (geyser) |
| 80 | Copper container capacity 25 Ltrs of water heater (geyser) |
| 81 | Taking down old unserviceable Ceiling /Exhaust/Air circulator fans of any type from any height and Material and Labour for rewinding of following Ceiling Fan, Exhaust Fan and Air circulator of any type/make by split opening the fan carrying cutting the burnt winding and cleaning the slots and rewinding with super enamelled copper winding wire of appropriate gauge including connection,capacitor base and testing complete all as specified and directed by Engr-in-Charge. Note: Bearing ,fan canopy, capacitor, down rod etc will be measured and paid separately under relevant item of schedule. |
| 82 | Ceiling fan of 1200/1400 mm sweep |
| 83 | Exhaust Fan of sweep 275/300 mm |
| 84 | Exhaust Fan of sweep 350/450 mm |
| 85 | Air circulator of sweep 350/450 mm |
| 86 | Supply only ball bearing (DE/NDE) to match the existing make suitable for 1200/1400 mm sweep ceiling fan including greasing complete all as specified and directed by Engr-in-Charge. Make: SKF/NBC |
| 87 | Supply only ball bearing suitable for 275mm to 450 mm exhaust fan complete all as specified and directed Make : SKF/NBC |
| 88 | Supply only fan capacitor of following capacity |
| 89 | capacitor 2.5 mfd |
| 90 | capacitor 4 mfd |
| 91 | Supply only , rubber yoke, MS Clamps, bolts nuts with split pin suitable for ceiling fan 1200 /1400 mm sweep complete all as specified and as directed by Engr-in-charge. |
| 92 | Supply only gun metal bush of suitable size for ceiling fan 1200 /1400 mm sweep complete all as specifed and directed by Engr-in-Charge. |
| 93 | Supply only fan down rod of following length with white enamel painted with both side hole for hanging fan of sweep 1200/1400mm sweep complete all as specified and directed by Engr in charge |
| 94 | 1 ft long |
| 95 | 2 ft long |
| 96 | Supply only startar for ceiling fan of 1200/1400 mm sweep with silicon coating, anti rust coating, size and slot as per sample, feasible to fix in exisiting rotor size complete all as specified and directed |
| 97 | Supply only rotor for ceiling fan of 1200/1400 mm sweep with silicon coating, anti rust coating, size and slot as per sample, feasible to fix in exisiting startar size complete all as specified and directed |
| 98 | Supply only fan canopy set off white /white coloured as per colour of ceiling fan of sweep1200/1400mm complete all as specified and directed. |
| 99 | Material and Labour in repair for PVC polycarbonate rectangular block for mounting switches, sockets, fan regulator etc with 3 mm thick plastic laminated sheet cover of following size including for fixing existing switches, sockets, regulators and make necessary connection and testing complete all as specified and directed by Engr-in-Charge. |
| 100 | 100 mmx 100 mm and 50 mm deep |
| 101 | 200 mm x 150 mm x 50 mm deep |
| 102 | 250 mm x 200 mm x 50 mm deep |
| 103 | 150 mm x 150 mm x 50 mm deep |
| 104 | Taking down old unserviceable wall mounted study lamp fitting of any type and supply and fix wall study lamp LED bush light with die cast aluminium housing with toughned glass 6 watts including necessary electric connection with PVC insulated multistranded copper cable of suitable size from ceiling rose/junction box to fitting terminal complete all as specified and directed. Please Enable Macros to View BoQ information |
| 105 | Taking down old unserviceable wall mounted study lamp fitting of any type and supply and fix wall study lamp LED bush light with die cast aluminium housing with toughned glass 6 watts including necessary electric connection with PVC insulated multistranded copper cable of suitable size from ceiling rose/junction box to fitting terminal complete all as specified and directed. Please Enable Macros to View BoQ information |