| 1 | Supply and fix electric water heater, storage type Inner container material Steel with Glass and having 2 Nos Heating element type of Incoloy with Glass coated heating element upto 2 KW capacity 25 litre, 230 Volts 50 Hz , temp range 35 to 75 C, with 7 Years on Tank,4 Years on Heating Element and 2 Years on Other Parts, with Outer body material of ABS, PUF insulation, lined BEE 5 Star, with product dimension of 470x470x371mm rated vertical type complete with all accessories such as safety valve, thermostate, NRV, connection piece etc all as specified and directed by Engr-in-Charge. (Make ERICA DIGITAL : VOLUME 25 LTR of Jaquar or equivalent in Havells/Bajaj/Recold/Haier/Orient/Hindware) |
| 2 | Supply and fix electric water heater, storage type Inner container material Steel with Glass and having 2 Nos Heating element type of Incoloy with Glass coated heating element upto 2 KW capacity 70 litre, 230 Volts 50 Hz , temp range 35 to 75 C, with 7 Years on Tank,4 Years on Heating Element and 2 Years on Other Parts, with Outer body material of ABS, PUF insulation, lined BEE 5 Star, with product dimension of 470x470x371mm rated complete with all accessories such as safety valve, thermostate, NRV, connection piece etc vertical type all as specified and directed by Engr-in-Charge. (Make Versa Vertical Manual 70 Ltr of Jaquar or equivalent in Havells/Bajaj/Recold/Haier/Orient/Hindware) |
| 3 | Supply and fixing of geyser Bolt 120mm Long with nut & washers, complete all as specified and directed. |
| 4 | S & F submain wiring with 2 single core (FRLS) PVC insulated unsheathed multistranded flexible copper conductor cable, of 4.0 Sqmm and one single core 4.0 Sqmm flame retardent low smoke (FRLS) PVC insulated, unsheathed, multistranded, flexible copper cable as earthing lead , all as per IS 694/1990 drawn through including concealed in brick masonary PVC conduit and conduit accessories heavy duty ISI marked, providing Copper cable sockets plate/ bottle type of adequate size at termination end of cable point wiring in DBs, switch boards, fittings fixtures all as specified and as directed all as specified a Note :- ( Two runs of main copper wire, one run of earth wire cable & PVC conduit shall be measured together as one length). |
| 5 | S & F PVC rigid non-metallic flexible conduit ISI marked of dia 20 mm dia inclusive of all tees, bends, elbows reducers, junction box etc and fixing accessories such as couplers, lock nuts, saddles, etc for telephone cable , TV cable and public address system including where required all as directed by Engineer-in- Charge duly concealed in wall complete all as specified and as directed. |
| 6 | Supply and installation of high-quality, durable material suitable for hot water applications 2 feet PVC connection for geyser, including all necessary fittings such as appropriate joints, couplings, or elbows as required for the installation, connections, and accessories including complete installation, testing, and making good of the site directed by Engineer-in- Charge complete all as specified and as directed. |
| 7 | Supply and fix Sheet metal Enclosure with socket plug top and MCBs Single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB of 20 Amps, 240 Volts 50 Hz all as specified Engineer-in- Charge complete all as specified and as directed. |
| 8 | Material and labour for point wiring using approved colour coding as per IS ,with multistranded copper conductor 4 Sqmm (nominal area), two single core, PVC insulated and unsheathed FRLS cable 1100 Volts for one 3 pin socket outlet plug point,20 Amps independent grade ISI-694 marked drawn through in and including heavy duty PVC concealed conduit including all accessories, Metal flush box of suitable module, with earth dolly, covered with twin colour (specified by Engr-in- Charge)modular white cover plate & frame after chasing in brick masonry walls etc for accomodating modular switches, sockets, regulators etc including PVC insulated multistranded copper conductor 4 Sqmm (nominal area) single core FRLS cable as earth continuity conductor along with wiring and connecting to earth dolly, providing Copper cable sockets plate/ bottle type of adequate size at termination end of cable point wiring in DBs, switch boards, fittings fixtures all as specified and as directed. |
| 9 | M&L including dismantling glazed ceramic coloured tiles of size 600 x 300 x 7mm / 450 x 300 x 7mm / 450 x 350 x 7mm thick, on vertical surfaces of walls such as skirting dado etc. set and jointed in neat cement slurry and pointed in white or colour cement to match including 10mm thick rendering in cement mortar 1:3 complete, all as specified. |
| 10 | S&F 15mm bore tubes medium grade galvanized ISI marked with all fittings short pieces and fixed complete to walls, floor, ceiling etc all including taking down existing G I tubing as specified. Make: JINDAL, TATA, RAVINDRA |
| 11 | S&F 20mm bore tubes medium grade galvanized ISI marked with all fittings short pieces and fixed complete to walls, floor, ceiling etc all including taking down existing G I tubing as specified. Make: JINDAL, TATA, RAVINDRA |
| 12 | M&L cutting chases pinning in brick/Stone work for concealing water tubing and making good to facing where required and pointing in cement motar 1:3, cutting n.exc. 10cm girth all as specified. |
| 13 | Supply and Installation, commissioning of Inverter type wall mounting air cooled split type unit air conditioner electric driven single phase indoor unit and outdoor unit with cordless remote control unit and with in built airioniser and plasma filter for better indoor air quality cutting ,brazing and connecting the copper pipe of size 1/2 inch and 1/4 inch size of pipe and making holes as for passing of copper pipes and electric cables and pressure testing with nitrogen and freon gas vacumising the system and charging the Non CFC refrigerent and testing the complete system for smooth functioning of split AC up to satisfactioning, above 3 star rating, confirming to IS-1391 Para II 1992 herimatically sealed air compressor working with Non CFC refrigerent suitable for wall mounting 4500 K cal/ hrs 1.5 Ton complete with stand for fixing on wall/ground all as specified and directed. |
| 14 | S & F for copper tubing of size 1/2” for discharge line any make of split AC of capacity 1/1.5 ton with insulation sheet of pipe tube type insulation including removal of old existing unsv one complete all as specified and directed. |
| 15 | S & F for copper tubing of size 1/4” for discharge line any make of split AC of capacity 1/1.5 ton with insulation sheet of pipe tube type insulation including removal of old existing unsv one complete all as specified and directed. |
| 16 | Supply and fixing copper cable 2.5 sqmm x 4 core for out door to indoor connection of split Acs all as specified and directed. |
| 17 | S & F for flexible PVC pipe 15mm dia heavy duty from outdoor unit to indoor unit for drain of water including clamping to the wall and brought down up to ground level (-1 Mtr) complete all as specified and directed. |
| 18 | S & F for new powder coated Mild Steel fabricated stand suitable for outdoor unit of Split AC of 1.5/ 2 TR to install outdoor unit on wall/ floor as required on site with legs and bracing complete all as specified and directed. |
| 19 | Supply, Installation and Testing of 12.5M High mast shaft in two sections suitable for 47 m/sec wind speed as per IS 875 part 3, with head frame, winch mounting bracket, luminaries carriage suitable to install 06 nos luminaries in symmetrical arrangement . The Raising and Lowering system shall be of 2 Continues Rope system without any intermediate compensating disc with double drum winch. The wire rope shall be of minimum 6mm Stailess Steel of grade AISI 316, 3 mm section thickness, top dia 150 mm, bottom dia 340/360 mm, with Stainless steel (AISI 316) 2/3 wire rope system, PCD - Pitch Circle Dia - 445 mm, Integral power tool motor, manual handle, Junction box including Construction of shallow foundation with M25 grade concrete for the highmast and foundation bolts manufactured from special steel along with nuts, washers, anchor plate and common template complete all as specified and directed. Bajaj, BHMRL12.5C LED |
| 20 | Supply & Fix 200W LED Flood light fitting complete with driver and necessary accessories as required to mount on the Lantern carriage. Housing material of the flood light should be of Matt Grey polyster powder coated pressure Die-cast aluminium housing, with heat resistant toughened clear glass fitted with SS screws. The system lumen output should not be less than 120 lumens /watt . Fixture should be suitable for a input voltage range of 120 V to 270 V with input power supply of 230 V AC. Ingress protection class of IP 66. BAJAJ CAT Ref: PRAZE F 180L WH NB-A5 TG SD |
| 21 | Supply, Install and Testing of outdoor (3.15 mm Thick) stand mounted feeder pillar with 16A TPN MCB incomer, single dial time switch, 16A TP contactor for the automatic switching of luminaries, power tool control with 2 no 6A contactors and raise lower push button, Incoming 10 sq. mm and out going 2.5 sq. mm terminals. |
| 22 | M&L for Earthing complete with galvanized steel earth plate electrode 600x600x6 mm thick buried directly in ground (earth pit not le. than 2.25 m deep below normal ground level) with top edge of the plate not le. than 1.5 m below normal ground level connected to GI Earth wire 4 mm dia by means of bolts and nuts checknuts and washers of galvanized iron or steel all as specified and shown in electrical plate no.5 of .R part I including nece.ary excavation and earth work in any type of soil PCC 1:3:6 type C1 chamber with RCC 1:2:4 type B1 40 mm thick cover with MS rod 8mm dia 150mm long reinforcement, watering funnel, 40 mm dia light grade for protection of earth electrode 20 mm dia for watering all as specified and directed and tested on completion. |
| 23 | Excavating in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for laying cables and getting out in hard/dense soil for laying cable/erecting poles all as specified and directed. |
| 24 | Returning and filling in soil including spreading leveling watering and well ramming in layers not exceeding 25cm all as specified. |
| 25 | Removing surplus excavated material to a distance not exceeding 50 Mtr and depositing where directed at a level not exceeding 1.5 M above the starting point. |
| 26 | Supply and laying 40 mm outer dia, double walled corrugated (DWC) HDPE duct pipe conforming to IS- 14930 Pt-II with antirodent and non flame propogating properties plete with fittings for cable protection complete all as specified and as directed. |
| 27 | Supply, laying, testing and connecting of cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 10 sq mm 4 core |
| 28 | Supply, laying, testing and connecting of cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 06 sq mm 2 core |
| 29 | Supply, lay, joint, test and commissioning of LT under ground cable 1100 volt grade , XLPE insulated and PVC sheathed heavy duty armoured with aluminium conductor , IS 7098-I Marked, Laid in trenches/ducts/fixed on poles/walls/laid under roads/paths/drains/culverts or encased in GI pipe including cable glands, lugs jointing material etc of 16 Sqmm 4 Core Size complete all as specified and directed |
| 30 | S & F sheet metal enclosure MCB DB SPN 4 way with 200 Amps rated bus bar 240 Volts double door with magnetic locking system including necessary provision for inserting the DBs in wall by cutting the brick/ stone masonary etc and making good of disturbed surface to match the existing colour of wall complete all as specified and as directed |
| 31 | S & F for MCB triple pole and neutral 415 Volts, 32 Amps, 10 KA. (ICS=ICU=100%) |
| 32 | S & F heavy duty industrial grade electrical circular socket connector outlet 5 holes (03 phase + neutral + earth) mounted inside a metal enclosure suitable for high power application of rating 32 Amps including necessary provision for fixing the enclosure in wall etc complete all as specified and as directed. Make : Havells, L&T, or equivalent |
| 33 | S & F submain wiring with 4 single core (FRLS) PVC insulated unsheathed multistranded flexible copper conductor cable, of 6.0 Sqmm and two single core 6.0 Sqmm flame retardent low smoke (FRLS) PVC insulated, unsheathed, multistranded, flexible copper cable as earthing lead , all as per IS 694/1990 drawn through including PVC conduit and conduit accessories heavy duty ISI marked, providing Copper cable sockets plate/ bottle type of adequate size at termination end of cable point wiring in DBs, switch boards, fittings fixtures all as specified and as directed complete all as specified and as directed. Note :- ( Four runs of main copper wire, two run of earth wire cable & PVC Casing caping/ conduit shall be measured together as one length). |
| 34 | M&L for Earthing complete with galvanised steel earth plate electrode 60×60cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than 1.5 metres below normal ground level, connected to galvanised iron strip 25×4mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion |
| 35 | Note : 1. Rerformance security:- Refer Condition 22 of Special Conditions. 2. Quoted Contract Sum shall be arrived at after deducting the amount of Credit Schedule (refer Schedule of Credit in pdf form for quantity, rate and amount etc.) for old unserviceable materials retrieved from site. Please Enable Macros to View BoQ information |