| 1 | Taking down carefully existing point wiring of any type/ any size (ie on wooden/ batten, surface conduit, casing capping or concealed conduit) complete for light, fan, socket or power point etc including removing switches, sockets, holders, ceiling rose, pendants, regulators, light fittings, switch board outlets with sheets and other materials from site for refixing of serviceable light and for taking credit of unserviceable light as per Sch of credit and making good disturbed surface of walls,roof, floors etc. with any type of civil wk involved complete all as specified and as directed. |
| 2 | M&L for point wiring for light point with 1.5 Sqmm (nominal area) FRLS PVC insulated unsheathed multi stranded copper conductor of size 1.5 Sqmm cable drawn in existing conduit terminated in existing sunken pressed steel boxes duly painted with anti corrosive paint over a coat of red oxide primer with plastic laminated bakelite sheet top cover 3mm thick make hylum or equivalent fixed with nickel polished screws with cup washers etc including FRLS PVC insulated unsheathed multi stranded copper conductor 1.5 Sqmm single core as earth continuity conductor (green colour) connected with earth dolly with thimble complete all as directed by Engineer-in-Charge. |
| 3 | Ditto all as per srl item No. 2 above, but for one Fan point controlled by one switch complete all as specified |
| 4 | Ditto all as per srl item No. 2 above, but for one bell point controlled by one bell push complete all as specified and as directed. |
| 5 | Ditto all as per srl item No. 2 above, but for one light point controlled by two way switches complete all as specified and as directed. |
| 6 | Ditto all as per srl item No. 2 above, but for one socket outlet 5 Amps on independent board complete all as specified and as directed. |
| 7 | Ditto all as per srl item No. 2 here-in-before, but for one socket outlet 5 Amps on the same board controlled complete all as specified and as directed. |
| 8 | Ditto all as per srl item No. 2 here-in-before, but with 2.5 Sqmm (nominal area) FRLS copper cable for one 3 Pin 15 Amp socket on independent board including one 2.5 Sqmm copper conductor multi stranded green colour PVC insulated unsheathed FRLS cable 1100 volts grade as earth wire connected to common earth and earth dolly with all accessories complete all as directed by Engineer-in-Charge. |
| 9 | S&F in replacement switch piano flush type, 5 Amps, 240 Volt AC single pole, one way complete all as specified and as directed. |
| 10 | S&F in replacement switch piano flush type, 5 Amps, 240 Volt AC single pole, two way complete all as specified and as directed. |
| 11 | S&F in replacement switch piano flush type, 15 Amps, 240 Volt AC single pole, one way complete all as specified and as directed. |
| 12 | S&F in replacement socket out let 5 Amp, 5 pin flush type complete all as specified and as directed. |
| 13 | M&L in replacement Socket outlet multi purpose 2 in 1, 5/6 pin, 5 & 15 Amps, flush type complete all as specified and as directed. |
| 14 | M&L in replacement Bell push switch, flush type 5 Amps, SP, 240 volts complete all as specified and as directed. |
| 15 | S&F five step fan regulator, electronic type, single phase, including connection complete all as specified and as directed. |
| 16 | M&L for point wiring with modular accessories for light point with 1.5 Sqmm (nominal area) FRLS PVC insulated unsheathed multi stranded copper conductor of size 1.5 Sqmm cable drawn in and including concealed rigid PVC conduit medium grade not less than 20mm dia with accessories including cutting chases for laying of conduit /fixing of boxes in walls/floor etc including making good to disturbed surfaces as per adjoining specification and terminated in and incl sunken pressed steel modular boxes(1.6 mm thick sheet and min 50 mm deep) with suitable modules white cover plate fixed with nickel polished screws etc including FRLS PVC insulated unsheathed multi stranded copper conductor 1.5 Sqmm single core as earth continuity conductor (green colour) connected with earth dolly with thimble complete all as specified and as directed by Engineer-in-Charge |
| 17 | Ditto all as per srl item No. 16 above, but for one fan point controlled by one switch complete all as specified and as directed. |
| 18 | Ditto all as per srl item No. 16 above, but for one bell point controlled by one bell push complete all as specified and as directed. |
| 19 | Ditto all as per srl item No. 16 above, but for one light point controlled by 2 Nos, two way switch complete all as specified and as directed. |
| 20 | Ditto all as per srl item No. 16 above, but for one socket outlet 5 Amps on independent board complete all as specified and as directed. |
| 21 | Ditto all as per srl item No. 16 above, but for one socket outlet 5 Amps on the same board controlled by one switch complete all as specified and as directed. |
| 22 | Ditto all as per srl item No. 16 above, but with 2.5 Sqmm (nominal area) FRLS PVC insulated unsheathed multi stranded copper conductor cable for one 3 Pin 15 Amp socket on independent board incl Modular cover plate and suitable metal sunken box of suitable modules including one 2.5 Sqmm FRLS PVC insulated unsheathed multistranded copper conductor cable green colour 1100 volts grade as earth wire connected to earth dolly with all accessories complete all as directed by Engineer-in-Charge. |
| 23 | S&F Modular switch piano flush type, 6 Amps, 240 Volt AC single pole, one way complete all as specified and as directed. |
| 24 | S&F Modular switch piano flush type, 16 Amps, 240 Volt AC single pole, one way complete all as specified and as directed. |
| 25 | S&F Modular socket out let 6 Amp, 5 pin, 2-in-1 flush type complete all as specified and as directed. |
| 26 | S&F Modular socket outlet multi purpose 2 in 1, 5/6 pin, 6 & 16 Amps, flush type complete all as specified and as directed. |
| 27 | S&F Modular switch piano flush type, 10 Amps, 240 Volt AC single pole, two way complete all as specified and as directed. |
| 28 | S&F ceiling rose surface type PVC/ polycarbonate 65mm x 50mm three terminal complete all as specified and as directed. |
| 29 | S&F mini modular MCB 6 A-20 A SP C curve IS 608981:2002 ISI mark complete all as specified and as directed. |
| 30 | S&F flat indicator red complete all as specified and as directed. |
| 31 | S&F 2 Module five step fan regulator, electronic type, single phase, including connection complete all as specified and as directed. |
| 32 | M&L in replacement Bell electric AC (Ding Dong) 240 volt SP complete all as specified and as directed. |
| 33 | S&F in repair for batten holder insulated body with matching colour back plate all as specified and directed |
| 34 | S&F USB charger 3000 mA ,15 W type A + C 1 module complete all as specified and as directed. |
| 35 | S&F light dimmer 400 W module 1lase marking complete all as specified and as directed. |
| 36 | S&F LED tube light fitting polycarbonate housing 1 x 20 Watt, appx 4 feet long, with decorative box linear, housing environment friendly, including electric connection with using 2 core flexible copper conductor cable 23/0.00076 from ceiling rose to tube fitting, complete fitting with all accessories and following specifications, complete all as directed by Engineer-in-Charge :- (a) Lumen system efficacy of luminaire should be minimum 110 Lumen per watt. (b) Input Voltage range : 140 to 270 volts. (c) Temp operating range : Minus 5°C to Plus 45°C (d) Power factor : Minimum 0.95 (e) THD : Current THD Max10% and voltage THD max 5% (f) IP rating : IP-20. (g) LED Driver of the same make as of the luminaire. (h) LED driver should be complete with all protections viz open/short circuit protection, over voltage protection, all as per standard design of manufacturer. (j) Surge protection minimum 2.5 kV. (k) CCT : Minimum 6000K (l) CRI : greater than 90 (m) Rated life time : 25000 burning hrs @L70 (Average 10 to 12 hrs daily) |
| 37 | S&F LED lights fitting 1x 20 Watt, 220V,AC smart extruded aluminium batten (4 ft) with higher efficacy with Microwave sensor to save more energy reduce the light intensity by 70 percent during non occupancy of person with using 2 core flexible copper conductor cable 23/0.00076 from ceiling rose to tube fitting, complete fitting with all accessories and following specifications, complete all as specified and directed by Engineer-in-Charge. :- (a) Lumen system efficacy of luminaire should be minimum 110 Lumen per watt. (b) Input Voltage range : 140 to 270 volts. (c) Temp operating range : Minus 5°C to Plus 45°C (d) Power factor : Minimum 0.95 (e) THD : Current THD Max10% and voltage THD max 5% (f) IP rating : IP-20. (g) LED Driver of the same make as of the luminaire. (h) LED driver should be complete with all protections viz open/short circuit protection, over voltage protection, all as per standard design of manufacturer. (j) Surge protection minimum 2.5 kV. (k) CCT : Minimum 6000K (l) CRI :Greater than 90 (m) Rated life time : 25000 burning hrs @L70 (Average 10 to 12 hrs daily) |
| 38 | S&F LED tube light fitting polycarbonate housing 1 x 10 Watt, appx 2 feet long, with decorative box linear, housing environment friendly, including electric connection with using 2 core flexible copper conductor cable 23/0.00076 from ceiling rose to tube fitting, complete fitting with all accessories and following specifications, complete all as directed by Engineer-in-Charge :- (a) Lumen system efficacy of luminaire should be minimum 100 Lumen per watt. (b) Input Voltage range : 140 to 270 volts. (c) Temp operating range : Minus 5°C to Plus 45°C (d) Power factor : Minimum 0.95 (e) THD : Current THD Max10% and voltage THD max 5% (f) IP rating : IP-20. (g) LED Driver of the same make as of the luminaire. (h) LED driver should be complete with all protections viz open/short circuit protection, over voltage protection, all as per standard design of manufacturer. (j) Surge protection minimum 2.5 kV. (k) CCT : Minimum 6000K (l) CRI : Minimum 80 (m) Rated life time : 25000 burning hrs @L70 (Average 10 to 12 hrs daily) |
| 39 | S&F Rechargeable Emergency inverter type with backup of 3 hrs, LED batten light fitting 20 Watts, compact type, LED cool light, 6500K, 2000lm with operating voltage 220 V-240 V, energy efficient, AC, minimum 3 feet long with decorative box linear, including 2 core flexible copper cable from ceiling rose to tubelight complete all as specified and directed by Engineer-in-Charge. |
| 40 | S&F Surface mounted LED panel, slim type premium diffuser to ensure glare free even light distribution 34 watt, 6500K, input voltage range 140 to 270 V, Temp operating range upto 45 degree Celsius, PF 0.95 of miniumum 2 x 2 ft with all mounting accessories, PVC/Polycarbonate body with all diffuser, driver, surge protection as per standard manufacturer complete all as specified and directed by Engineer-in-Charge. |
| 41 | S&F LED lamp 9 watt B22 WW complete all as specified and directed by Engineer-in-Charge. |
| 42 | S&F LED lamp 12 watt B22 CW complete all as specified and directed by Engineer-in-Charge. |
| 43 | S&F in repair edge lit sleek round recessed/surface as per requirement mounted LED 12 W down light with white powder coated die cast housing and diffuser for low galre illumination complete all as specified and as directed. |
| 44 | S&F in repair edge lit sleek square recessed/surface as per requirement mounted LED 18W down light with white powder coated die cast housing and diffuser for low galre illumination complete all as specified and as directed. |
| 45 | S&F LED strip 75 W warm white Non integral flexible with LED driver IP 65 LED strip light with high brightness for indoor/outdoor applications strip suitably can be cut at marked interval to suit desired length complete all as specified and as directed. |
| 46 | S&F LED Flood light fitting 50 watts,made up of pressure die-cast aluminium housing with toughened glass with mandatory secondary optics lenses, with SS screws, IP-66, luminaire efficacy more than 120 Lm/W, CCT 5700K ANSI, CRI>70, THD<10%, PF >0.95, LED source : Hi power LED 3 to 5W High power type .Fitting should be double driver moisture resistant, with internal surge protection 4KV having under voltage, over voltage, phase to phase protection and short circuit protection and auto recovery mode, operating range 150 V to 270 V AC at 50Hz, Auto Cut off >300 V and separte Surge protection device 10 KV complete having fixing bracket clamp. |
| 47 | S&F LED bollard 9W/10W in rectangular shape with opal acrylic diffuser and Ip 65 protection with necessary required PCC(1:3:6) for fixing complete all as specified |
| 48 | S&F LED post top made 45 W warm white in die cast aluminium bottom housing and spun aluminium top reflector with decorative clear acrylic diffuser and IP65 protection opal diffuser available complete all as specifief and directed. |
| 49 | M&L in replacement of sub main wiring with two run of single core FRLS PVC insulated unsheathed multistranded copper conductor cable of 6 Sqmm drawn through in and including PVC rigid non metallic concealed conduit (medium grade) with all fittings including earth continuity FRLS PVC insulated unsheathed multistranded copper conductor cable 6.0 Sqmm (as specified) complete with any type of civil work involved to make good disturbed surfaces all as specified.Note : Two run of 6 sqmm wire and one run of 6 sqmm wire as earth wire including PVC concealed conduit shall be measured as one unit |
| 50 | M&L in replacement of sub main wiring with two run of single core FRLS PVC insulated unsheathed multistranded copper conductor cable of 4 Sqmm drawn through in and including PVC rigid non metallic concealed conduit (medium grade) with all fittings including earth continuity FRLS PVC insulated unsheathed multistranded copper conductor cable 4.0 Sqmm complete with any type of civil work involved to make good disturbed surfaces all as specified.Note : Two run of 4 sqmm wire and one run of 4 sqmm wire as earth wire including PVC concealed conduit shall be measured as one unit |
| 51 | M&L in replacement of sub main wiring with four run of FRLS PVC insulated unsheathed multistranded copper conductor single core cable 6 Sqmm drawn through in and including PVC rigid non metalic concealed conduit (medium grade) and one run of FRLS PVC insulated unsheathed multistranded copper conductor single core cable (green colour) of size 6 sqmm with any type of civil work involved to make good disturbed surfaces complete all as specified and as directed.Note : Four run(3P+01 N) of 6 sqmm wire and one run of 6 sqmm wire as earth wire and PVC concealed conduit shall be measured as one unit |
| 52 | S&F 10 watt LED bulkhead having LED strip & inbuilt driver, aluminium housing with opal/ polycarbonate diffuser including taking out old fitting all as specified and as directed. |
| 53 | S&F energy efficient astronomical type LED security light fitting of 25W pressure die cast aluminium housing/body, heat resistant clear toughened glass, better optics for uniform distribution street luminaire, with driver, including electric connection with using 3 core flexible copper conductor cable 1.5Sqmm from ceiling rose to light fitting, fixing the light fitting with new bracket made out of GI tubing light grade 25mm dia, 1.2 metre long bent to shape at 120 degree angle at half metre from bottom, including two Nos clamps made out of MS Flat iron size 25x3 mm with suitable nuts and bolts for fixing of bracket including painting to MS clamp and nut bolts with two coats of aluminium paint over a coat of red oxide primer, complete fitting with all accessories and following specifications, complete all as specified and directed by Engineer-in-Charge. :- (a) Lumen system efficacy of luminaire should be minimum 120 Lumen per watt. (b) Input Voltage range : 140 to 270 volts (c) Temp operating range : Minus 10°C to Plus 50°C (d) Power factor : Minimum 0.95 (e) THD : Max10%. (f) IP rating : IP66. (g) IK rating : Minimum IK07 (h) Built in potted LED Driver of the make as of the luminaire. (j) LED driver should be complete with all protections viz open/short circuit protection, over voltage protection, all as per standard design of manufacturer. (k) Surge protection 10 kV (inbuilt + extended) (l) CCT : 5700 K. (m) CRI : Minimum 70 (n) Lens - High Efficiency wide angle lens. (o) BIS Approved fixtures and driver (p) Rated life time : 25000 burning hrs @L70 (Average 10 to 12 hrs daily)(q)LED source : Hi power LED 3 to 5W High power type |
| 54 | Fixing only serviceable tube light fittings any type and any description retrieved under item Srl No. 01, including necessary electric connection with round flexible wire with multi stranded copper conductor of size 0.50 sqmm, 3 core, 1100 volts grade complete all as directed. |
| 55 | M&L for sub main wiring with two run of single core FRLS PVC insulated unsheathed multistranded copper conductor cable of 6.0 Sqmm drawn through in and including in existing concealed conduit (medium grade) with all fittings including earth continuity single wire FRLS PVC insulated unsheathed multistranded copper conductor cable 6.0 Sqmm ( green insulation) with any type of civil work including making good to disturbed surfaces to match existing surface complete all as specified and as directed. NOTE: Two run of 6.0 sqmm wire and one run of 6.0 sqmm wire as earth wire ishall be measured as one unit. |
| 56 | M&L for sub main wiring with two run of single core FRLS PVC insulated unsheathed multistranded copper conductor cable of 4.0 Sqmm drawn through in existing concealed conduit with all fittings including earth continuity single wire FRLS PVC insulated unsheathed multistranded copper conductor cable 4.0 Sqmm ( green insulation) with any type of civil work including making good to disturbed surfaces to match existing surface complete all as specified and as directed. NOTE: Two run of 4.0 sqmm wire and one run of 4.0 sqmm wire as earth wire including shall be measured as one unit. |
| 57 | S&F in repair single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB of 20 amp 240 V 10 KA complete all as specified and as directed. |
| 58 | S&F three pole and neutral enclosure with a two pin and earth plug and socket complete with one TPN MCB of 32 amp 240 V 10 KA complete all as specified and as directed. |
| 59 | S&F in repair (concealed flush to wall) factory made DB (made out of CRCA sheet not less than 1.2mm thick, fitted with DIN channel neutral link and 200 Amp rated bus bar) SPN, 12 Way 240V, suitable for mounting MCB/Isolator etc, conforming to IS-13032, DB shall be semi glosy finished with epoxy polyster based powder paint sprayed and backed at high temperature between powder paint process to ensure smooth finish and protection against corrosion atmosphere. The DB shall be double door type with hinged door with locking arrangement, the DBs shall be same make as MCBs, DB shall be provided with level marking indicating the incoming and outgoing circuits on always as specified. The DBs shall be of IP-54 protection class, and including making good disturbed surfaces of walls as necessaty complete all as directed by Engineer-in-Charge.Note :- MCB/Isolator etc shall be measured and paid separately under appropriate item of BOQ. |
| 60 | S&F (concealed flush to wall) factory made DB (made out of CRCA sheet not less than 1.2mm thick, fitted with DIN channel neutral link and 200 Amp rated bus bar) SPN, 8 Way 240V, suitable for mounting MCB/Isolator etc, conforming to IS-13032, DB shall be semi glosy finished with epoxy polyster based powder paint sprayed and backed at high temperature between powder paint process to ensure smooth finish and protection against corrosion atmosphere. The DB shall be double door type with hinged door with locking arrangement, the DBs shall be same make as MCBs, DB shall be provided with level marking indicating the incoming and outgoing circuits on always as specified. The DBs shall be of IP-54 protection class, and including making good disturbed surfaces of walls as necessaty complete all as directed by Engineer-in-Charge.Note :- MCB/Isolator etc shall be measured and paid separately under appropriate item of BOQ. |
| 61 | S&F (concealed flush to wall) factory made DB (made out of CRCA sheet not less than 1.2mm thick, fitted with DIN channel neutral link and 200 Amp rated bus bar) SPN, 4 Way 240V, suitable for mounting MCB/Isolator etc, conforming to IS-13032, DB shall be semi glosy finished with epoxy polyster based powder paint sprayed and backed at high temperature between powder paint process to ensure smooth finish and protection against corrosion atmosphere. The DB shall be double door type with hinged door with locking arrangement, the DBs shall be same make as MCBs, DB shall be provided with level marking indicating the incoming and outgoing circuits on always as specified. The DBs shall be of IP-54 protection class, and including making good disturbed surfaces of walls as necessaty complete all as directed by Engineer-in-Charge.Note :- MCB/Isolator etc shall be measured and paid separately under appropriate item of BOQ. |
| 62 | S&F in repair TPN DB 4 way double door, including 63 Amp MCB TPN, having copper bus bar for neutral and earth, blankng strips complete all as specified and as directed. |
| 63 | S&F in repair TPN DB 4 way (8+12 module )double door Phase selector DB, suitable for 63 Amp MCB TPN, having copper bus bar for neutral and earth, blankng strips complete all as specified and as directed. |
| 64 | S&F (concealed flush to wall) factory made VTPN (Vertical type), 4 Way 415V, as per IEC 61439-3, DB (made out of CRCA sheet not less than 1.2mm thick, with copper bus bar rating of suitable capacity, with two neutral bar, 2 earth bar and cable tie for cable management, suitable for MCCB 4 pole upto 125Amp, as incomer and suitable for mounting MCBs as outgoing, DB shall be semi glosy finished with epoxy polyster based powder paint sprayed and backed at high temperature between powder paint process to ensure smooth finish and protection against corrosion atmosphere. The DB shall be double door type with hinged door with locking arrangement, the DBs shall be same make as MCBs, DB shall be provided with level marking indicating the incoming and outgoing circuits on always as specified. The DBs shall be of IP-54 protection class, and including making good disturbed surfaces of walls as necessaty complete all as directed by Engineer-in-Charge.Note :- MCBs for outgoing shall be measured and paid separately under appropriate item of BOQ.directed. |
| 65 | S&F in repair MCCBs 125 Amp 4 pole 415 V , adjustable thermal and fixed magnetic settings (0.8 to 1.0) to Ics=100% Icu short circuit setting fixed breaking capacity 25 KA with phase barriers/ separator/spacer/copper spreader link and required nut bolts complete all as specified and as directed. |
| 66 | S&F MCB SP 6 to 32 Amps 240 V, 10 KA, B curve as per complete all as specified and directed by Engr-in-charge. |
| 67 | S&F MCB SPN 40 Amps 240 V, 10 KA, B curve as per complete all as specified and directed by Engr-in-charge. |
| 68 | S&F in repair TPN FP MCB 63 Amps, 10 KA, B curve complete all as specified and directed by Engr-in-charge. |
| 69 | S&F 1 Module blank (dummy) plate suitable for Modular switch cover plate complete all as specified and as directed. |
| 70 | M&L for XLPE insulated in replacement , PVC sheathed galvanised steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 35 sqmm 3.5 core complete laid in trenches passing through pipes/culverts/ under roades/ alon wall all as directed by Engineer-in-Charge. |
| 71 | M&L for XLPE insulated,in replacement PVC sheathed galvanised steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 25 sqmm 4.0core complete laid in trenches passing through pipes/culverts/ under roades/ alon wall all as directed by Engineer-in-Charge. |
| 72 | M&L for XLPE insulated,in replacement PVC sheathed galvanised steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 16 sqmm 4.0core complete laid in trenches passing through pipes/culverts/ under roades/ along wall all as directed by Engineer-in-Charge. |
| 73 | Excavation in trenches not exceeding 1.5m in wide and not exceeding 1.5 m in depth for laying of pipe etc and getting out in soft soil, complete all as specified and as directed. |
| 74 | M&L for returning, filling in including spreading leveling watering and well ramming in layers not exc. 25 cm thick complete all as specified and as directed.(Surplus soil if any shall not be removed but left over the trench) |
| 75 | M&L for removing surplus soil to a distance not exc. 50 M and depositing where directed at a level not exceeding 1.5 Mtr above the starting point complete all as specified and as directed. |
| 76 | M&L for sand cushioning with clean dry sand to cables with layer of sand 8 cm before laying of cable and 15 cm thick after laying of cable complete all as specified and as directed.Note : For payment purpose punned thickness of 18 cm shall be measured against spread thickness of 23 cm as mentioned in para 19.75 of SSR part-I. |
| 77 | M&L for providing PCC cable cover class LV type-I of size 250x150x40mm laid in perpendicular to the cable abutting each other all as specified and as directed at site. |
| 78 | M&L for Earthing complete in replacement with galvanised steel earth plate electrode 60cmx60cmx6.0mm thick burried directly in ground (earth pit not less than 2.25 metres deep below normal ground level with the top edge of electrode not less than 1.5 metres below normal ground level connected to galvanised earth lead wire 4mm dia by means of bolts, nuts, check nuts and washers of galvanised iron and incl GI lead protection pipe of GI light grade 15mm dia upto 7.5 mtrs and watering pipe 20mm bore of GI medium grade with funnel and wiremesh, earth plate covered on all sides with min 150mm thick alternate layers of charcoal, salt all as shown in electrical plate No 3 of SSR Part-I 2009 connected to earthing point with PCC chamber and RCC cover in 1:2:4 complete with any type of earth work involved.all as specified and as directed and testing on completion. Note:- PCC Chamber shall be constructed at least 0.50 mtr away from on the earth pit electrode and pipe for watering shall be provided in slanting manner.Note:Earth plate weight will be approved by Engr in charge before execution of earth work. |
| 79 | M&L for check by electric audit expert electric wiring per building(temporary/permanent) and prepare electric wiring test sheet in format as per annexure I and submit in the form of booklet per unit of buildings complete all as specfied and as directed. |
| 80 | S&F 1100 volts grade heavy duty PVC insulated & PVC sheathed stranded aluminium conductor of size 10 sqmm twin core flat cable in service incl Taking down/ out unserviceable conductor connection all as directed. Note:contractor has to provide 80 pecent of quantities for LEDs fittings of any type and any capacity within one month after issue of work order before order for purchase neccesary sample approval by GE of items are necessary.PV and TC and necessary LM 79 and LM 80 report by NABL lab will be prodube by the contractor for overall performance of a complete LED and long term lumen maintenence and color stability of LED package. 1000 Rs/- Recovery per day will be float from RAR if No item will received after one month of work order date. Please Enable Macros to View BoQ information |