| 1 | Taking down U/S existing sub main wiring copper/ aluminium conductor including PVC or steel conduit/ casing and capping etc.complete all as specified and as directed. |
| 2 | Supply and laying sub main wiring complete with 05 runs ( 3 Nos for three phase, Neutral & Earthing colour code) of single core 6 sqmm fire retardant low smoke and halogen (FRLSH) PVC insulated copper conductor cable multistranded and sheathed LT 1100 V grade drawn through and including steel metallic conduit 20mm dia(minimum) ISI marked and accessories surface fixed on wall /floor etc complete all as specified and as directed.Note:- 05 runs of cable and 01 run of steel conduit shall be measured as one unit for measurement purposes. |
| 3 | Supply and laying sub main wiring complete with 05 runs ( 3 Nos for three phase, Neutral & Earthing colour code) of single core 4 sqmm fire retardant low smoke and halogen (FRLSH) PVC insulated copper conductor cable multistranded and sheathed LT 1100 V grade drawn through and including steel metallic conduit 20mm dia(minimum) ISI marked and accessories surface fixed on wall /floor etc complete all as specified and as directed.Note:- 05 runs of cable and 01 run of steel conduit shall be measured as one unit for measurement purposes. |
| 4 | Supply and laying sub main wiring complete with 03 runs ( Phase, Neutral & Earthing colour code) of single core 4 sqmm fire retardant low smoke and halogen (FRLSH) PVC insulated copper conductor cable multistranded and sheathed LT 1100 V grade drawn through and including steel metallic conduit 20mm dia(minimum) ISI marked and accessories surface fixed on wall /floor etc. complete all as specified and as directed.Note:- 03 runs of cable and 01 run of steel conduit shall be measured as one unit for measurement purposes. |
| 5 | Supply and laying sub main wiring complete with 03 runs ( Phase, Neutral & Earthing colour code) of single core 2.5 sqmm fire retardant low smoke and halogen (FRLSH) PVC insulated copper conductor cable multistranded and sheathed LT 1100 V grade drawn through and including steel metallic conduit 20mm dia(minimum) ISI marked and accessories surface fixed on wall /floor etc complete all as specified and as directed. Note:- 03 runs of cable and 01 run of steel conduit shall be measured as one unit for measurement purposes. |
| 6 | Supply & fixing in repair LED 1x20 watt FLAME PROOF tube light fixture luminaire including integral reflector made of diecast aluminium alloy LM6 , with electronic ballast, bipin holders, .connector block, etc., and all accessories pre-wired and including connecting up with suitable size copper conductor twin core cable including taking out existing unserviceable normal or flame proof light complete all as specified and directed. |
| 7 | S & F in repair round high bay light LED flameproof well glass in die cast AL housing with heat resisitant toughened glass suitable for Gas/Vapour group of IIA & IIB and zone 1 & 2 of 60 watt capacity including taking out existing unserviceable lights. complete all as specified and directed. |
| 8 | Supply and fix in repair Flame proof - weather proof CMRI approved MCB socket & plug with 16 AMP rotary switch combined 16 A, 250V (2P+Earth) complete all as specified and as directed. |
| 9 | Supply and fix in repair Flame proof - weather proof CMRI approved 3 phase MCB socket & plug 32 Amp with rotary switch combined 500V(4P+Earth)complete all as specified and as directed. |
| 10 | Supply & fix in repair Flame proof Sheet metal enclosure SPN 8 way for fixing MCBs 240 volt including MCB DP 32-40 A- 1 No as incomer & MCBs SP 6 to 16 Amps-6 Nos as outgoing complete all as specified and as directed. |
| 11 | Supply & fix in repair Flame proof Sheet metal enclosure SPN 6 way for fixing MCBs 240 volt including MCB DP 32 A- 1 No as incomer & MCBs SP 6 to 16 Amps-4 Nos as outgoing complete all as specified and as directed. |
| 12 | Supply & fix in repair Flame proof Sheet metal enclosure SPN 4 way for fixing MCBs 240 volt including MCB DP 20 A- 1 No as incomer & MCBs SP 6 to 16 Amps-2 No's as outgoing complete all as specified and as directed . |
| 13 | Supply & fix in repair Flame proof Sheet metal enclosure TPN 4 way for fixing MCBs 240 volt including MCB TPN 63 A- 1 No as incomer & MCBs SP 6 to 16 Amps-12 No's as outgoing complete all as specified and as directed . |
| 14 | Supply & Fix in repair Switch flame proof rotary type with termination box in LM6, 16A, single pole 250V complete all as specified and as directed. |
| 15 | Supply & Fix in repair 3 way flame proof junction box suitable for carrying 4/6 sqmm 3 phase/single phase sub main wiring complete all as specified and as directed by Engineer-In-Charge. |
| 16 | Supply & Fix in repair 4 way flame proof junction box suitable for carrying 4/6 sqmm 3 phase/single phase sub main wiring complete all as specified and as directed by Engineer-In-Charge. |
| 17 | S&F as in repairs LED 150 W flood light fitting with lense, high luminous efficacy,protected to IP 66, toughened glass efficient high out put emitter LED for better distribution having surge protection 10 KV, sealed driver applicable for area lighting including electrical connection, complete all as specified and as directed. |
| 18 | S&F in repair aviation light 2 x 10 watt fitting complete LED type double with alternate flashing and dusk automatic control housing cast aluminium base with red diffuse lens , including taking out existing unsv light complete all as specified and as directed . |
| 19 | M&L for earthing complete with GI earth plate electrode 600 mm x 600 mm x 6 mm thick, buried directly and preferably vertically in ground, earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.50 Mtr below ground level. The earth plate to be connected with earth lead of 4 mm dia galvanised iron or steel wire all as shown in electrical plate no 3 to the earthing test point all as specified and directd.The GI wire to be protected by galvanised iron pipe 15mm bore (medium grade) up to up to test point. Earthing shall be include with providing funnel with 20mm bore galvanised iron pipe (light grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) up to 90 cm all around earth plate further filled with 60 cm thick Tibba sand and 2nd layer with 30 cm of Magnesium sulphate powder (compact thickness ) , 3rd layer with tibba sand up to the ground level. Earthing shall also be include for providing concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate), 50mm thick precast RCC (1:2:4) cover slab (re-inforced with 8mm dia TMT bar @ 15 cm C/C bothways and suitable handle made of 10mm dia) including necessary earth work including taking out old unsv earthing from existing location with complete all as specified and directed. |
| 20 | M&L for disconnecting from the transformer /panel board, cutting off worn out aluminium cable end and supply, laying and testing in replacement cable XLPE Insulated ,screened, PVC bedded,galvanized steel strip or wire armoured,electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 95 sq mm 3.5 core including taking out existing cable, complete all as specified and directed. |
| 21 | M&L for disconnecting from the transformer /panel board, cutting off worn out aluminium cable end and supply, laying and testing in replacement cable XLPE Insulated ,screened, PVC bedded,galvanized steel strip or wire armoured,electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 50 sq mm 3.5 core including taking out existing cable, complete all as specified and directed. |
| 22 | M&L for disconnecting from the transformer /panel board, cutting off worn out aluminium cable end and supply, laying and testing in replacement cable XLPE Insulated ,screened, PVC bedded,galvanized steel strip or wire armoured,electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 35 sq mm 3.5 core including taking out existing cable, complete all as specified and directed. |
| 23 | M&L for disconnecting from the transformer /panel board, cutting off worn out aluminium cable end and supply, laying and testing in replacement cable XLPE Insulated ,screened, PVC bedded,galvanized steel strip or wire armoured,electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 sq mm 4 core including taking out existing cable, complete all as specified and directed. |
| 24 | M&L for disconnecting from the transformer /panel board, cutting off worn out aluminium cable end and supply, laying and testing in replacement cable XLPE Insulated ,screened, PVC bedded,galvanized steel strip or wire armoured,electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16 sq mm 4 core including taking out existing cable, complete all as specified and directed. |
| 25 | M&L for disconnecting from the transformer /panel board, cutting off worn out aluminium cable end and supply, laying and testing in replacement cable XLPE Insulated ,screened, PVC bedded,galvanized steel strip or wire armoured,electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 6 sq mm 2 core including taking out existing cable, complete all as specified and directed. |
| 26 | Excavation in trenches not exc. 1.5 m wide and not exc 1.5 mtr deep in soft / loose soil for laying / taking up/ taking down of cables and getting out and levelling of bottom surface to required level complete all as specified and directed by Engineer- in- Charge. |
| 27 | Returning filling in Including spreading, levelling. watering and well ramming soil in layers not exceeding 25 cm thick complete all as specified and directed. |
| 28 | Removing excavated material (ie soil) from site to a distance n. exc 50 mtrs away and depositing where directed at a level n. exc. 1.5 mtr above the starting point all as specified and directed by Engineer-in-Charge. |
| 29 | Material and labour for tiba sand for filling in trenches 8 cm below the UG Cable and 15 cm above the underground cables for cushioning of cables etc, complete all as specified. Note :- Punned thickness shall be measured for payment. |
| 30 | S&F sub class B bricks old size having minimum compressive strength 75 Kg/ Sqcm laid in trenches for cable protection etc complete all as directed by Engineer-in-Charge. Please Enable Macros to View BoQ information |
| 31 | S&F sub class B bricks old size having minimum compressive strength 75 Kg/ Sqcm laid in trenches for cable protection etc complete all as directed by Engineer-in-Charge. Please Enable Macros to View BoQ information |