| 1 | Taking down carefully existing copper/Aluminium point wiring (light, fan, socket or power) complete including fixture and fittings such as switches, bell pushes, ceiling roses, pendants, regulators, sockets, light fitting, call bells etc. removing materials to store for keeping in safe custody or for taking credit(credit for above items should be made as per conditions separately) and making good disturbed surfaces of walls, floors etc. to match existing colour complete all as specified and directed. |
| 2 | Material and labour for concealed one light / fan point controlled by one, one way modular switch 06 Amp wiring with 1.5 Sq mm nominal cross sectional area, single core, 1100 Volt grade, multi-stranded, PVC insulated, unsheathed FRLS copper conductor cable with and including continuous earth wire of size 1.5 Sq mm nominal cross sectional area, single core, 1100 Volts grade, multi-stranded, PVC insulated, unsheathed, FRLSH copper conductor cable and connected to common earth and earth dolly with suitable copper lugs and drawing into and including rigid non-metallic PVC conduit of 20 mm dia in medium grade complete with and including all PVC conduit accessories concealed into wall by cutting of chases in wall complete and including modular metal flush boxes not less than 1.6mm thick alongwith modular cover plate with frame of any size for mounting of any type modular switches/sockets/bell switch /fan regulator and brass screws, cup washers etc complete, making good the distributed surfaces completely matched and finished with existing surfaces including painting of walls etc complete all as specified and directed. |
| 3 | All as per srl item No. 2.00 (here-in-before) but One 3 pin socket outlet 6 Amp on same board point, complete all as specified and directed |
| 4 | All as per srl item No. 2.00 (here-in-before) but One 3 pin socket outlet 6 amp on the independent board point with PVC FR-LSH Cable size 2.5 Sqmm complete all as specified and directed complete all as specified and directed |
| 5 | All as per srl item No. 2.00 (here-in-before) but One bell point controlled by one bell push on independent board complete all as specified and directed. |
| 6 | All as per srl item No. 2.00 (here-in-before) but One light point controlled by two way switch complete all as specified and directed |
| 7 | All as per srl item No. 2.00 (here-in-before) but for 15/16 Amp socket out let/power point by using 2.5 Sqmm PVC insulated unsheathed copper conductor cable FR-LSH multi strand on independent board including provn of 2.5 Sqmm unsheathed, multi stranded copper conductor cable FR-LSH continues as earth wire connected to earth dolly etc complete all as specified and directed |
| 8 | All as per srl item No. 2.00 (here-in-before) but for 15/16 power point (AC & Geysers) by using 4.0 Sqmm PVC insulated unsheathed copper conductor cable FR-LSH multi strand on independent board including provn of 4.0 Sqmm unsheathed, multi stranded copper conductor cable FR-LSH continues as earth wire connected to earth dolly etc complete all as specified and directed |
| 9 | Material and labour for one light / fan point controlled by one, one way modular switch 06 Amp wiring with 1.5 Sq mm nominal cross sectional area, single core, 1100 Volt grade, multi-stranded, PVC insulated, unsheathed FRLS copper conductor cable with and including continuous earth wire of size 1.5 Sq mm nominal cross sectional area, single core, 1100 Volts grade, multi-stranded, PVC insulated, unsheathed, FRLSH copper conductor cable and connected to common earth and earth dolly with suitable copper lugs and drawing into and in existing rigid non-metallic PVC conduit including modular metal flush boxes not less than 1.6mm thick alongwith modular cover plate with frame of any size for mounting of any type modular switches/sockets/bell switch /fan regulator and brass screws, cup washers etc complete, making good the distributed surfaces completely matched and finished with existing surfacess including painting of walls etc complete all as specified and directed. |
| 10 | All as per srl item No. 3.00 (here-in-before) but One 3 pin socket outlet 6 Amp on same board point, complete all as specified and directed |
| 11 | All as per srl item No. 3.00 (here-in-before) but One 3 pin socket outlet 6 amp on the independent board point with FR-LSH cable 2.5 Sqmm complete all as specified and directed |
| 12 | All as per srl item No. 3.00 (here-in-before) but One bell point controlled by one bell push independent board complete all as specified and directed. |
| 13 | All as per srl item No. 3.00 (here-in-before) but One light point controlled by two way switch complete all as specified and directed |
| 14 | All as per srl item No. 3.00 (here-in-before) but for 15/16 Amp socket out let/power point by using 2.5 Sqmm PVC insulated unsheathed copper conductor cable FR-LSH multi strand on independent board including provn of 2.5 Sqmm unsheathed, multi stranded copper conductor cable FR-LSH continues as earth wire connected to earth dolly etc complete all as specified and directed |
| 15 | S & F in repairs Modular switch 1 way 6A/10A 1 module single pole complete all as specified and directed. |
| 16 | S & F in repairs Modular switch 1 way 16A, 1 module single pole complete all as specified and directed. |
| 17 | S & F in repairs Modular Socket oultet 6A - 2/3 pin combined 2 module, 230 volt, multipurpose, complete all as specified. |
| 18 | S & F in repairs of Modular Socket outlet 6A/16A - 2/3 pin combined 2 module, 230 volt,multipurpose, complete all as specified. |
| 19 | S & F in repairs Modular Bell push 1 way 6A, 1 module single pole complete all as specified and directed. |
| 20 | S & F in repairs Modular switch 2 way 6A, 1 module single pole complete all as specified and directed. |
| 21 | S & F in repairs of Modular Fan step regulator, 120W - 2 module with 5 steps type complete all as specified. |
| 22 | Supply and fixing in repair switch 6 Amps, single pole, one way (1 module), in existing switch board as per existing make and shape (any type like ordinary/modular/semi modular ) including making electric connection and testing, fixing at any site complete all as specified and as directed. |
| 23 | Supply and fixing in repair switch 16 Amps, single pole, one way (2 module), in existing switch board as per existing make and shape (any type like ordinary/modular/semi modular ) including making electric connection and testing, fixing at any site complete all as specified and as directed. |
| 24 | Supply and fixing in repair switch 6 Amps, single pole, two way (1 module), in existing switch board as per existing make and shape (any type like ordinary/modular/semi modular ) including making electric connection and testing, fixing at any site complete all as specified and as directed. |
| 25 | Supply and fixing in repair switch 6 Amps, single pole, bell push switch (1 module), in existing switch board as per existing make and shape (any type like ordinary/modular/semi modular ) including making electric connection and testing, fixing at any site complete all as specified and as directed. |
| 26 | Supply and fixing in repair Socket outlet 3 pin, 6A, flush type (2 module), in existing switch board as per existing make and shape (any type like ordinary/modular/semi modular ) including making electric connection and testing, fixing at any site complete all as specified and as directed. |
| 27 | Supply and fixing in repair Socket outlet 2 in 1, 3 pin, 6 and 16 Amp flush type (2 module), in existing switch board as per existing make and shape (any type like ordinary/modular/semi modular ) including making electric connection and testing, fixing at any site complete all as specified and as directed. |
| 28 | Supply and fixing in repair Socket outlet 2 in 1, 3 pin, 6 and 16 Amp flush Combination type , in existing switch board as per existing make and shape (any type like ordinary/modular/semi modular ) including making electric connection and testing, fixing at any site complete all as specified and as directed. |
| 29 | Supply and fixing in repair stepped type electronic fan regulator flush rotary 5 step type (1/2 module), in existing switch board as per existing make and shape (any type like ordinary/modular/semi modular ) including making electric connection and testing, fixing at any site complete all as specified and as directed. |
| 30 | S & F in repairs of buzzer, Ding Dong type AC 230 volts complete all as specified and directed. |
| 31 | S & F in repairs ceiling rose, 6 Amp, 250 volt, AC, ISI marked with three equal size terminals and PVC / Polycarbonate insulated body of 50 x 25 mm size complete all as specified & directed. |
| 32 | S&F in repair Lamp holder PVC/polycarbonate type with back plate complete all as specified |
| 33 | Supply and fixing of 9 watt LED Bulb suitable for B-22 type holder complete all as specified and directed by Engineer-in-charge. |
| 34 | Taking down old complete and supply and fixing of SPN enclosure with a two pin and earth plug and socket complete with and including MCB, SP, AC, 240 volt of 20 Amp, 'C' curve 10 KA breaking capacity and flush to wall including all cuttings & chases etc in wall and making good to the disturbed surfaces to match the existing complete all as specified & directed. |
| 35 | Supply and fixing in replacement of 4 feet long LED tube light fittings, 20 Watt of cool white / warm 6500/3000K comprising of batten with all accessories internally prewired and connecting up with twin core twisted copper conductor cable of suitable size including taking down old fittings complete all as specified and as directed. |
| 36 | Taking down old complete and Supply and fixing of LED tube light fittings 600 mm,10/12W, 6500K higher energy saving decorative ultra slim square profile LED lighting fixture with extruded aluminium/Polycarbonate housing enviromental friendly, energy efficient ready to use pack and comprising of batten with all accessories internally prewired and connecting up with twin core twisted copper conductor cable complete all as specified and directed. |
| 37 | Supply and fixing in replacement of LED street light fitting 35 Watt 230V AC outdoor type with high pressure die cast aluminium hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant complete with IP 65/66 protection including fixing with GI/MS bracket made out of suitable size of light grade tube upto 1.2 mtr length bent to shape with 02 sets of MS clamps made out of minimum 3 mm MS flat iron with suitable bolt and nuts complete with making connection complete all as specified and directed |
| 38 | Supply and Fixing of ceiling fan 5 star rated ISI marked 1200mm sweep , 230 Volt ,50Hz AC supply with brushless direct current motor (BLDC) 6.00 BEE alogwith down rod, canopy , remote control comprising with battery complete and connecting up including provision of three core flexible PVC cable with stranded copper conductor of size 0.75 Sq.mm from ceiling rose to connector of ceiling fan complete incl taking down existing unserviceable ceiling fan deposit to E/M store all as directed and as specified. |
| 39 | Supply and fixing in replacement of post top lantern LED type 25 watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection with impact and corrosion resistance complete with driver and lamp complete all as specified and directed |
| 40 | Supply and fixing of decorative wall light fixture made of stainless steel suitable for retrofit 9W LED lamp(base B-22) complete with PC diffusor & including one 9W LED lamp(base B-22),and suitable holder 3000/6500K, not less than 90 lumen/watt , wall mounted bracket including making connection and taking down old unserviceable complete all as specified and directed. |
| 41 | Supply and Fixing of steel exhaust fan of sweep 300 mm along with metallic louver complete including cutting of wall, making of proper hole sufficient to fix exhaust fan and smoothing of the surface before fixing of exhaust incl taking down existing unserviceable ceiling fan deposit to E/M store all as directed and as specified. |
| 42 | Taking down old complete and Material and labour sub main wiring with 06 Sq mm nominal cross sectional area, two single core, 1100 Volt grade, multi-stranded, PVC insulated, unsheathed, FRLS copper conductor cable with and including continuous earth wire of size 06 Sq mm nominal cross sectional area, single core, 1100 Volt grade, multi-stranded, PVC insulated, unsheathed, FRLS copper conductor cable and connected to common earth and earth dolly with suitable copper lugs and drawing into in existing surface/recessed PVC/steel conduit complete all as specified and directed. Make of cable - Polycab/Havells/Grandlay cable (Note :- 03 runs of 6.0 sqmm cable will be measured as one running length) |
| 43 | Taking down old complete and Material and labour sub main wiring with 06 Sq mm nominal cross sectional area, two single core, 1100 Volt grade, multi-stranded, PVC insulated, unsheathed, FRLS copper conductor cable with and including continuous earth wire of size 06 Sq mm nominal cross sectional area, single core, 1100 Volt grade, multi-stranded, PVC insulated, unsheathed, FRLS copper conductor cable and connected to common earth and earth dolly with suitable copper lugs and drawing into and including rigid non-metallic PVC conduit of 25 mm dia, medium grade complete with and including all PVC conduit accessories concealed into wall by cutting of chases in wall and making good to the disturbed surfaces to matched and finised with existing surface are included in the ratecomplete all as specified and directed.Note:- (i) 2 run of 6.0 Sqmm main cable, one run of 6.0 Sqmm earth wire and one run length of PVC conduit of size 25mm shall be considered as one running length.(ii) The wiring shall be done in proper color coding using Red,Yellow, Blue for phases, Black for neutral and Green for earth. |
| 44 | Taking down old complete and Supply and fixing of Vertical TPN MCCB DB 04 Way and provision MCCB as incomer,,double door, AC, 440 volt, with 200 Amp rated copper bus bar , sheet metal enclosure completer with IP 54 & IK 09 protection incl MCCB 100 Amps, Four pole, adjustable thermal magnetic protection, 25 KA, 415 V, Icu=Icu (100%), along with cable end box for above DB and flush to wall including all cutting etc in wall and making good to the disturbed surfaces to match the existing complete all as specified and as directed . |
| 45 | Taking down old complete and Supply and fixing of TPN MCCB DB 04 Way and provision MCCB as incomer,,double door, AC, 440 volt, with 200 Amp rated bus bar , sheet metal enclosure completer with IP 54 & IK 09 protection along with cable end box for above DB and flush to wall including all cutting etc in wall and making good to the disturbed surfaces to match the existing complete all as specified and as directed . |
| 46 | Taking down old complete and supply and fixing of sheet metal enclosure distribution board, double door, single pole and neutral, AC, 240 volt, 12 way, with 200 Amp rated copper bus bar and metal door with IP - 43 & IK 09 protection along with cable end box for above DB and flush to wall including all cutting etc in wall and making good to the disturbed surfaces to match the existing complete all as specified & directed. |
| 47 | Taking down old complete and supply and fixing of sheet metal enclosure distribution board, double door, single pole and neutral, AC, 240 volt, 08 way, with 200 Amp rated copper bus bar and metal door with IP - 43 & IK 09 protection along with cable end box for above DB and flush to wall including all cutting etc in wall and making good to the disturbed surfaces to match the existing complete all as specified & directed.Make :- Havells/Legrand/L&T |
| 48 | Taking down old complete and supply and fixing of SP MCB 6-32 Amp ,240Volt 10 KA ‘B’ series complete all as specified and directed. |
| 49 | Taking down old complete and supply and fixing of SPN MCB 40-63 Amp ,240Volt 10 KA ‘C’ series complete all as specified and directed. |
| 50 | Taking down old complete and supply and fixing of DP MCB 63 Amp ,240Volt 10 KA ‘C’ series complete all as specified and directed. |
| 51 | Taking down old complete and supply and fixing of MCCB 4 Pole, 63 Amps, 50 Hz, 25KA, 415 Volts,adjustable thermal and fixed magnetic type with all necessary aluminium lugs and glands, etc complete all as spicified and directed. |
| 52 | Taking down old complete and M&L labour for earthing complete with galvanised mild steel earth plate electrode 60 cm x 60 cm x 6 mm thick buried vertically in ground (earth pit not less than 2.25 metre deep below ground level) with top edge of the plate not less than 1.5 metre below normal ground level steel earth plate connected with GI wire 04 mm dia by means of lug, bolts, nuts, check nuts, washers of galvanised iron or steel GI protection pipe 15 mm bore light grade all as shown in elect plate No 3 on serial page No 497 of SSR part I - 2009 and connecting to main switch board / Main DB’s including excavation, earth work, salt and charcoal dust mixed and packed 150 mm thick around GI earth plate, GI pipe medium grade 20 mm nominal bore watering pipe GI sheet funnel wire mesh, concrete pit, RCC cover 40 mm thick in PCC 1:2:4 type B1 duly reinforced with MS Bars 6 mm dia at the rate of 75 mm centre to centre both way with 12 mm dia lifting handle and pit / chamber in PCC 1:3:6 type C1, Angle iron 40 mm x 40 mm x 3 mm frame for pit cover including testing on completion complete all as specified and directed. Note : (i) Cost of GI earth strip and GI protection pipe upto 7.5 Mtr length shall be deemed to be included in the rate quoted for this item. |
| 53 | Supply and fixing 4 Way (4Module) modular surface Gang Box made out of high grade PVC/ABS material, suitable for modular switches and socket complete all as specified and as directed. |
| 54 | Supply and fixing 6/8 Way (6/8Module) modular surface Gang Box made out of high grade PVC/ABS material, suitable for modular switches and socket complete all as specified and as directed. |
| 55 | Supply and fixing in replacement of metal clad plug top 2 pin & earth, including 3 pin socket( metal clad) complete set ISI marked 20 Amp 250V complete all as specified and as directed. |
| 56 | Taking down unserviceable Ceiling fan / exhaust fan/ wall fan including ceiling cable of any size / sweep and make by disconnecting electric connection, dismantling blades, down rod and refixing the serviceale or new ceiling fan at existing location complete all as specified and directed. |
| 57 | Supply and fixing in replacement dry type capacitor 2.5 mfd suitable for any type and any make fan complete all as specified and as directed. |
| 58 | Supply and fixing of new hanging rod 600/900 mm long alongwith U clamp with rubber reel for any make and any type of ceiling fan complete having two Nos holes all as directed. |
| 59 | Supply and fixing of wire braided Heavy duty Stainless Steel PVC Connection Pipe ISI marked of of 15 mm dia 450/600 mm long suitable for cold & hot water, for water heaters with SS nuts and PVC/rubber sealing washers as per required at site condition complete all as specified and directed |
| 60 | Supply and fixing of Modular Metal Flush Box 4 module duly embedded in wall in cement mortar 1:4 after chase cutting/cutting of wall tile or marble with cutter and matching/making good the existing surface complete all as specified and as directed |
| 61 | Supply and fixing of Modular Metal Flush Box 12 module duly embedded in wall in cement mortar 1:4 after chase cutting/cutting of wall tile or marble with cutter and matching/making good the existing surface complete all as specified and as directed |
| 62 | Supply and fixing of Modular white cover plate with frame 4 module complete all as specified and as directed |
| 63 | Supply and fixing of Modular white cover plate with frame 12 module complete all as specified and as directed |
| 64 | Supply and fixing of Modular AC Socket with 25 Amps SP mini MCB, 230 Volts, 50Hz. In 4 module sheet metal enclosure complete all as specified and as directed. |
| 65 | Material and Labour for making circular holes suitable for fixing of exhaust fans (upto 300 mm sweep) by cutting the wall (any thickness) required for exhaust of air and including grouting of rag bolts and nuts complete including finishing of disturbed surfaces using cement mortar 1:3 complete all as required at site and directed by the Engineer-in-Charge. |
| 66 | Isolate/de-energize the supply to the LT Panel Board/meter feeder panel of capacity ranging 63 Amps and voltage 415 Volts/230 Volts, opening the doors/covers of the cubicle enclosure for carrying out the servicing/maintenance/repairs of the Panel Board,modification and switch gear,MCCB, metering etc and re-fixing the same/New in place after repairs including testing and commissioning of the panel board comprising of the following:-a) Cleaning the inside switch gear chambers for removing dust, carbon and rusted surfaces including cleaning with blower b) Check the condition of the DMC/SMC support insulators including cleaning applying Dr beck red for better IR values and replacement of insulators/PVC copper cable size of 10.0 Sqmm if required. c) Tightening up of all bus bar connections, cable connections, replace bolt, nuts wherever required.(d) Repairs Panels /meters box doors with necessary hinged and welding work as per site requirement complete.Note :- MCB/MCCBs will be measured and paid separately and consumables items will be scope of the contractor |
| 67 | Supply and fixing in replacement of heating element (ISI-Marked) 1500/2000 Watt of suitable for as per existing make of Havells/bajaj/crompton/Venus/Racold and any model /any shape of geysers including rubber ring clamping screws etc, complete all as specified and as directed. |
| 68 | Supply and fixing in replacement of stainless steel inner tank with glass line insulation, vertical type, min 6 bar pressure, suitable for 25 ltr capacity including replacement of PUF insulation complete all as specified and directed. |
| 69 | Supply and fixing in replacement of stainless steel Inner cold and hot water circulating apparatus unit assembly ISI marked (Geysers water assembly) as per existing make and shape any type complete suitable for 25 Ltrs capacity all as specified and directred. |
| 70 | Supply and fixing/ grouting, 100mm long (min), 10/12 mm dia mild steel fastener / fastener L-hook ( 02 Nos) with washer for hanging the geyser and making good the disturbed surface with cement mortar (1:4) complete all as specified and as directed. |
| 71 | M&L for Cutting chases, pinning in. making good to facings where required and pointing in cement mortar 1:3 to ends or edges of landings, steps, cills, sunshades, shelves, lintels, etc.; and cutting chases for concealed concealed conduit pipe wiring, etc., and making good, cutting not exc 10 cm girth |
| 72 | Material and labour for 2.5 Sqmm (nominal cross section area) single core FRLSH PVC insulated unsheathed and multi strand copper conductor cable 1100 volt (ISI marked), (using red, black and green etc colour wires as per colour coding i.e for phase, netural, earth wire etc) drawn through PVC pipe or through casing capping complete all as specified and as directed. |
| 73 | Supply and fixing of Hylam sheet cover 3mm thick of size 5\\"x5\\" complete with machine screw/ washer with provision of switches, sockets, fan regulators etc complete all as specified |
| 74 | Supply and fixing of Hylam sheet cover 3mm thick of size 8\\"x5\\" complete with machine screw/ washer with provision of switches, sockets, fan regulators etc complete all as specified |
| 75 | Supply and fixing of Hylam sheet cover 3mm thick of size 11\\"x8\\" complete with machine screw/ washer with provision of switches, sockets, fan regulators etc complete all as specified |
| 76 | Supply and fixing of Hylam sheet cover 3mm thick of size 13\\"x 11\\" complete with machine screw/ washer with provision of switches, sockets, fan regulators etc complete all as specified |
| 77 | S&F in repair MS Sunken box of size 7\\"x 4\\" with approved depth & thickness complete with earth dolly including making good the disturb surfaces CM (1:3) to match the existing complete all as specified Please Enable Macros to View BoQ information |
| 78 | S&F in repair MS Sunken box of size 7\\"x 4\\" with approved depth & thickness complete with earth dolly including making good the disturb surfaces CM (1:3) to match the existing complete all as specified Please Enable Macros to View BoQ information |