| 1 | Providing and fixing of Bollard light 12W LED warm white light, height 800 mm, on cement concrete pedestal, made of extruded aluminium profile and die cast aluminium base with UV protected frosted PMAA diffuser for glare free lighting, bollard painted with PU paint, including all connections, interconnections,testing, commissioning as required. Make : Twinkle, Model : Luxmax TBLED 191 or similar in Philips/ Wipro/ Havells |
| 2 | Supplying and drawing following sizes of PVC insulated copper conductor, three core cable in the existing underground DWC HDPE pipe as required, Make: Polycab,Havells,Greatwhite,KEI,Finolex |
| 3 | 1 X 2.5 Sq. mm |
| 4 | Supplying and laying of following size DWC HDPEpipe ISI marked along with all accessories like socket,bend, couplers etc. conforming to IS 14930, Part IIcomplete with fitting and cutting, jointing etc.direct inground (75 cm below ground level) includingexcavation and refilling the trench but excluding sandcushioning and protective covering etc., complete asrequired. |
| 5 | 63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 6 | Earthing with G.I. earth pipe 4.5 Meter long, 40 mmdia including accessories, and providing masonryenclosure with cover plate having lockingarrangement and watering pipe etc. with charcoal/coke and salt as required. |
| 7 | Supplying and laying 6 SWG G.I. wire at 0.50 Meterbelow ground level for conductor earth electrode,including connection/ termination with GI thimble etc.as required. |
| 8 | Providing and laying earth connection from earthelectrode with 6 SWG dia G.I. Wire in 15 mm dia G.I.pipe from earth electrode including connection withG.I. thimble excavation and re-filling as required. |
| 9 | Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. |
| 10 | All kinds of soil. |
| 11 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : |
| 12 | 1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources) |
| 13 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level : |
| 14 | 1:1.5:3 (1 cement : 1.5 coarse sand (zone-III) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 15 | Centering and shuttering including strutting, propping etc. and removal of form for |
| 16 | Columns, Pillars, Piers, Abutments, Posts and Struts |
| 17 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level. |
| 18 | Thermo-Mechanically Treated bars of grade Fe-500D or more. Please Enable Macros to View BoQ information |