| 1 | Providing Sports Mast LightingSITC of Energy efficient IP66, IK08 or IK10 LED Floodlight luminaires of wattage 1550-1650W , ambient temp of 35 deg C and having a System Efficacy at Optical level of System minimum 110 lm / watt, compliant to IS-10322/IEC60598. The Luminaire shall be with Single piece pressure die-cast aluminium housing with polycarbonate lens cover dedicated rotational/symmetrical optic with reduced glare properties . The housing shall not be amalgamation of pressure diecast multiple modules/individual housings and shall be corrosion resistant aluminium finished in colour of raw aluminum with U Shaped Mounting Bracket. The end-caps can be easily opened to access the bolts to aim the floodlight; the slot-hole in the bracket facilitates flexible installation. The Luminaire shall be provided the different beam angles (min 3 beam angles) to suit the different mounting arrangement and required lighting parameters. The LEDs shall be SMD High Power LEDs (COB type LED chip is not acceptable. MultiChip LED arrays is not acceptable), Individual LED >1W and min 130lumens/watt (at design operating current and Tj – 85deg C.), CCT: 5700°K, CRI≥90, SDCM ≤ 5, Limits of the harmonic current to be as per IS: 16103 (Part 1): 2012 and IEC 61000-3-2 with Total Harmonic Distortion≤ 20% @ full load. The Luminaire life shall be 50000 Hrs @ Ta35°C. It shall operate at an operating temperature range of -40°C up to +35°C, and shall have Television Lighting Consistency Index (TLCI) ≥ 90. LED luminaires shall be able to offer Dynamic Lighting control with an appropriate DMX enabled driver & system. The luminarie should have Electromagnetic compatibility limits -Limitation of Voltage Changes, Voltage Fluctuations and Flicker in Public Low-Voltage Supply Systems as per IEC 61000-3-3 , for Equipment with Rated Currentof the voltage changes as per IEC 61000-3-3 The Driver shal be BIS certified , CISPR -15 /EMC/EMI complied , the driver shall be potted with epoxy/Asphalt/Silicon & encapsulated. LED Driver shall have efficiency ≥85%,IP66, power factor 0.95 at full power, Flicker Frequency ≤1% as per IEC 61000-3-3 , Surge protection of 10kV should be in IP 65/IP66 box . LED Sports Flood Light luminaires shall be one single unit with Non-integral or Remote gear. External Surge protection (SPD ) both AC and DC with Thermal Protection (TMOVs) of minimum 10KV/5KV with capability to withstand a minimum of 15 pulses of 10KV/5KV to be separately installed (fixed with screws) Externally/Internally with each fixture, compliant to IEC 62305 & IEC 61643-11- 2011. |
| 2 | The Driver unit lifetime should be 50000 hours at operation temperature range with a failure rate of max 0.5% per 5000 hours. Driver shall be DMX dimming control compatible to use with suitable dimming control & control accessories.Driver and SPD should be of the same OEM as of the luminarie to ensure the electrical complatibility / longevity/ performance warrenties and optimised performance . Dimming protocol should be with remote control monitoring and individual light fixture should be addressable and compatible for integration with sound control in future. All components shall be mounted in an outdoor enclosure made of GI /aluminium sheet or on the mast in the luminaire with due ingress protection (IP 66) and impact resistance (IK 08 /IK10 and should be made in 100% recyclable non-corrosive aluminium die cast (aluminium copper content Cu < 1,3%). The Luminaire and Driver shall have BIS certification. Luminaire Driver remote installation, as total weight of the lumiinaries calculated after lux level design required shouldn't exceed 800 kg per exiting structure of High mast. LED luminaire should have minimum 5 year on site warrenty.Besides this the lighting fixture manufacturer should have inhouse NABL accredited lab.. complete in all respect asdesired by engineer -in- charge. |
| 3 | PVC INSULATED SINGLE CORE FR COPPER CONDUCTOR CABLE: Supply and erection of PVC insulated FR single core Unsheathed copper conductor cable (ISI marked) suitable upto 1100 volts grade confirm to IS:694/1990 left bare in pipe or casing of suitable size complete in all respect as desired by the Engineer-in-charge:- |
| 4 | Overall size 2.5sq.mm (Un-sheathed) |
| 5 | Overall size 4sq.mm (Un-sheathed) |
| 6 | Supply and erection of PVC insulated PVC sheathed (3 core) round flexible wire with copper conductor (FR) cable (ISI marked) confirm to IS:694/1990 left bare in pipe or casing of suitable size complete in all respect as desired by the Engineer-in-charge:- |
| 7 | Overall size 2.5sq.mm (50/0.25mm), 3Core |
| 8 | DOUBLE WALLED CORRUGATED (DWC) HDPE PIPES: Supply and erection of Double Walled Corrugated (DWC) HDPE pipe to be laid 1mtr. below ground level including excavation placing the pipe in position and back filling with excavated soil etc. of the required size:- |
| 9 | Double Walled Corrugated HDPE Pipe 50/ 38mm (Outer/ Inner dia.) |
| 10 | PVC, HDPE PIPES & PVC FLEXIBLE PIPES: Supply & erection of PVC Conduit Pipes (ISI marked) as per IS9537:Part-III & HDPE pipes (ISI marked) as per IS:4984:1995 for wiring purposes including bends, junction boxes, Steel hooks, M.S. saddle clamps and other petty materials etc., as per PWD General Specifications:- |
| 11 | Heavy Gauge PVC Conduit Pipe 40mm dia. (Flushed) |
| 12 | Supply and erection of PVC flexible pipe complete without compression glands, locking arrangement, check-nuts as required:- |
| 13 | PVC flexible pipe 25mm dia. |
| 14 | MINIATURE CIRCUIT BREAKERS: Supply and erection of Miniature Circuit Breaker MCB's for circuit protection against overload and short circuit current fault suitable for 240/ 415 volts 50cycles AC supply with breaking capacity of 10kA, Curve-C and low watt losses as per IS/IEC 60898-1, energy limitation class-3, true contact indication, label holder facility in the existing MCB distribution board as per PWD General Specifications including connections with suitable size of thimbles/lugs:- |
| 15 | MCB Double Pole 40amp. (10kA, Curve-C) |
| 16 | MCCB's (FOR PANELS & SHEET ENCLOSURE):Supply and erection of Moulded Case Circuit Breaker (Panel mounting Cubical type) in the existing Cubical Panel (confirm to IEC:60947-2) having Ics=100% Icu, 100% neutral with spreader terminal links, Extended rotary handle and relevant PWD general specifications complete with G.I. Bolts, Nuts & Connection on both sides of MCCB with suitable size of thimbles etc |
| 17 | MCCB Four Pole 400amp., 415volts, ≥36kA Microprocessor Based Adjustable Thermal and Magnetic Setting |
| 18 | Supply and erection of Copper Chemical Earthing 3 meter long earthing rod typically has a copper-bonded steel rod with a minimum 250-micron copper coating, a diameter 50 mm dia with 2 nos. BFC bag and a high tensile strength of around 90,000 psi. For installation, it is placed in an augured hole, surrounded by earth enhancing compound, and suitable for interconnection with other electrodes using a 25x3 mm copper strip or 8mm solid copper conductor, buried at least 3m deep. Complete in all respect as per satisfaction of engineer in charge at site. |
| 19 | Supply, Erection, Testing & Commissioning of Winch Machine 1of capacity 1000kg IIT Vetted for existing 35 mtr (30+5) High Mast with 3 phase electrical motor min 2 hp double drum .It should be motorised as well as manual operated complete in all respect. |
| 20 | SITC Man rider Unit Made up of Steel Frame with Safety Rope Feature and Power Tool with Auto and Manual (Both) Operation with Safe Load Capacity of 300KG with lifting Speed Max 4m/minute & mass of Cage 300kg max. The Manrider unit must have Security lock & overload protection switch. The Lift must decend if there is no power and magnetic brake would be applied immediately. Manrider must have anti fall arresting system with independent safety wire rope of min 8mm & Lifting Wire Rope 6mm as per IS 2266. The breaking System comes into operation immediately when the wire rope failure. It must decend manual even when there is no power for the safety of workman. The safety lock must be Trigger on sudden increase of decending speed. The Manrider Supplied Complete with all accessories in all respect as desired by engineer in charge |
| 21 | Supply, Installation Testing Commissioning of Armoured Cat-6 Cable for Connecting the Controller to the Internet and Cable required for Connecting LAN, CCTV & other equipments in campus. |
| 22 | Supply, Erection, Testing & Commissioning of Control Panel Cubical type of size 2100H x 900L x 500D mm will be made out totaly enclosed free standing type of 14 SWG CRCA sheet Including 3 4 horizontal partitioning of 14no CRCA Sheet , for outdoor application for fitting Drivers for LED Lights, Rod Tip Lock Arrangement anf Fans and Louver. complete in all respect. |
| 23 | Dismentalling of Sports mast Luminaire from existing High Mast of 35 m or above including loading ,unloading ,transportation and other charges complete in all respect as desired by Engineer-in charge |