| 1 | Supply & Replace in replacement MCCB along with both side spreader link and nut bolts of appropriate size (Conforms to IEC:60947-II/ IS:13947-II) in existing LT Panel box/ Feeder Pillar boxes (KIOSK), in MCCB DBs of capacity 630 Amps, 4 Pole, 35 KA, 415 Volt including disconnecting/ taking out existing old unsv/ burned MCCB complete all as specified and directed. |
| 2 | All as per item No 1.00 here in before but of capacity 315-400 Amps, 4 pole, 36 KA |
| 3 | All as per item No 1.00 here in before but of capacity 250 Amps, 4 pole, 36 KA |
| 4 | All as per item No 1.00 here in before but of capacity 200 Amps, 4 pole, 36 KA |
| 5 | All as per item No 1.00 here in before but of capacity 160 Amps, 4 pole, 36KA |
| 6 | All as per item No 1.00 here in before but of capacity 125 Amps, 4 pole, 16 KA |
| 7 | All as per item No 1.00 here in before but of capacity 100 Amps, 4 pole, 16 KA |
| 8 | All as per item No 1.00 here in before but of capacity 63 Amps, 4 pole, 16 KA |
| 9 | S&F in replacement MCCB, 63 Amps, 3 pole, 415 Volts with breaking capacity 16KA, including disconnecting/ taking out existing old unsv/ burned MCB complete all as specified and directed. |
| 10 | All as per item No 9.00 here in before but of capacity 100 Amps, 3 pole, 415 Volts with breaking capacity 16KA |
| 11 | All as per item No 9.00 here in before but of capacity 160 Amps, 3 pole, 415 Volts with breaking capacity 16KA |
| 12 | S&F in replacement MCB, SP 6-32 Amps, 'C' Curve with breaking capacity 10KA, including disconnecting/ taking out existing old unsv/ burned Isolator complete all as specified and directed. |
| 13 | Supply and fixing in replacement of automatic street light switch using infrared sensor based nature switch for automatic switching of street lights. Nature switch operation should bebased on natural light lux level. Required illuminance level for switching on is < 30 Lux and for switching off > 10 lux. The sensor should also have part night operation facility of min 4 hrs to max 12 hrs. The sensor along with suitable power contactors incoming outgoing MCBS SP and automanual (sensor bypass selection option should be enclosed in a pole / wall mountable enclosure made of rust proof electric shock proof termite proof and FR grade SMC Box conforming to IP54 single phase load of 8 KW with circuit wiring min 10 sq. mm copper wire 63 Amps contactor ans suitable MCBs at both positions at incoming and out goings of breaking capacity 10 KA complete including necessary clamp (2 sets) / anchor bolt (4 no's) for fixing on pole / wall complete all as directed including taking down old one Model no Swadeep-02 EC 8KW 1P or equivalent from Havells/ Legrand. |
| 14 | Supply and fixing in replacement of automatic street light switch using infrared sensor based nature switch for automatic switching of street lights. Nature switch operation should bebased on natural light lux level. Required illuminance level for switching on is < 30 Lux and for switching off > 10 lux. The sensor should also have part night operation facility of min 4 hrs to max 12 hrs. The sensor along with suitable power contactors incoming outgoing MCBS SP and automanual (sensor bypass selection option should be enclosed in a pole / wall mountable enclosure made of rust proof electric shock proof termite proof and FR grade SMC Box conforming to IP54 three phase load of 12 KW with circuit wiring min 10 sq. mm, 3 no's contactor each of 40 - 50 amps, incoming outgoing MCB (3 no's) rating 40 amps of breaking capacity 10 KA complete including necessary clamp (2 sets) / anchor bolt (4 no's) for fixing on pole / wall complete all as directed including taking down old one Model no Swadeep-02 EC 12KW 3P or equivalent from Havells/ Legrand. |
| 15 | Supply, lay, commissioning and testing of cable jointing Kit Heat shrinkable type for 1100 V grade cable for straight through joint with jointing material and accessories suitable for LTUG cable of size 16 to 50 Sqmm, 3.5 Core complete all as specified and directed. |
| 16 | All as per item No 15.00 above but suitable for aluminium conductor cable of size from 70 sqmm, 3.5 Core to 95 Sqmm, 3.5 Core |
| 17 | All as per item No 15.00 above but suitable for aluminium conductor cable of size from 120 sqmm, 3.5 Core to 185 Sqmm, 3.5 Core |
| 18 | All as per item No 15.00 above but suitable for aluminium conductor cable of size from 240 sqmm, 3.5 Core to 240 Sqmm, 3.5 Core Please Enable Macros to View BoQ information |
| 19 | All as per item No 15.00 above but suitable for aluminium conductor cable of size from 240 sqmm, 3.5 Core to 240 Sqmm, 3.5 Core Please Enable Macros to View BoQ information |