| Sl. No. | Item Description |
| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: GE Utilities Udhampur Name of Work:Repair/Maintenance of DG Sets of various capacities and allied system installed & Repair/Maintenance of Highmast lights, Streetlights and other connected items at water supply installations under GE (Utilities) Udhampur Contract No: GE/U-72/2026-27 Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Ser.No. Item Description Item Code / Make Quantity Units Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT Without Taxes TOTAL AMOUNT TOTAL AMOUNT In Words |
| 2 | Servicing of diesel engine generating set of capacity 500 KVA/600KVA of any make, including the following works are as under: -(a) Servicing of Engine(i) Re-greasing all grease points.(ii) Tighten the nuts, bolts of pipe lines of fuel oil, lubricating oil, water and check for leakages and examine the all main connections.(iii) Check water/coolant level in radiator.(iv) Check crank case oil level.(v) Clean/replaced lubrication oil filters.(vi) Clean/replaced air filters.(vii) Check that lubricating oil contains no water. Examine lubricating oil and renew if needed (viii) Check tappet clearance and all nuts for tightness.(ix) Wash felt pads of fuel filter.(x) Drain air receiver.(xi) Grease valve stems.(xii) Check all wiring, battery water level, gravity of battery, inspect all bushes and bush holder, cleaning of surface of commutators.(b) Servicing of alternators(i) Check temp rise of bearings.(ii) Check bushes on exciter commutator and the alternator slip rings run without chattering or sparking.(iii) Check if bushes freely slide in holder and whether bush springs are in order. |
| 3 | (iv) Check if oil rings are freely rotating in the bearings.(v) Check oil level in bearings.(vi) Wipe clean the alternator and exciter.(vii) Check all wiring and rectify any defect with new wiring.(viii) Surface and clean the commutator.(ix) Take insulation and earth test on alternator and exciter and if defective investigate cause and remedy.(x) Check joints, clamping and bolting in all the wiring including control panels and rectify any defects.(xi) Check greases in all roller and ball bearings and make up if inadequate.(xii) Check the degree of wear of commutator bushes and renew if necessary.(xiii) Tighten all nuts in the rotors of alternator and exciter.(xiv) Check air gaps between starters and rotors and clean off any projections on the rotor.(C) Clean the complete bottom inner/outer side up to floor level carried out with kerosene. all accessible associated internal parts were also cleaned throughly with kerosene to the maximum ossible extent.Note for item No. 1 to 4 : Items to be replaced will be measured and paid separately, as supply only and labour for fixing deemed to be include as part of servicing. |
| 4 | Description all as per Ser item No 1.00 here- in- before, but 250 KVA to 320 KVA as per existing Mak, Complete all as specified and directed by Engr-in-Charge. |
| 5 | Description all as per Ser item No 1.00 here- in- before, but 200 KVA as per existing Make. Complete all as specified and directed by Engr-in-Charge. |
| 6 | Description all as per Ser item No 1.00 here- in- before, but 40 KVA to 100 KVA as per existing Make. complete all as specified and directed by Engr-in-Charge. |
| 7 | Supply & Fix fuel filter primary & secondary. (Set of Two) suitable of existing make & specification for 500/600 KVA DG set complete all as specified and directed by Engr-in-Charge. |
| 8 | Supply & Fix fuel filter primary & secondary. (Set of Two) suitable of existing make & specification for 250 KVA to 320 KVA DG set complete all as specified and directed by Engr-in-Charge. |
| 9 | Supply & Fix fuel filter primary & secondary. (Set of Two) suitable of existing make & specification for 200 KVA DG set complete all as specified and directed by Engr-in-Charge. |
| 10 | Supply & Fix fuel filter primary & secondary. (Set of Two) suitable of existing make & specification for 40 KVA to 100 KVA DG set complete all as specified and directed by Engr-in-Charge. |
| 11 | Supply & Fix Oil filter element suitable (in replacement) of existing make & specification for 500/600 KVA DG set. Complete complete all as specified and directed by Engr-in-Charge. |
| 12 | Supply & Fix Oil filter element suitable (in replacement)of existing make & specification for 250KVA to 320 KVA DG set. Complete all as specified and directed by Engr-in-Charge. |
| 13 | Supply & Fix oil filter element suitable (in replacement)of existing make & specification for 200 KVA DG set. Complete all as specified and directed by Engr-in-Change. |
| 14 | Supply & Fix oil filter element suitable (in replacement)of existing make & specification for 40 KVA to 100 KVA DG set. Complete all as specified and directed by Engr-in-Charge. |
| 15 | Supply & Fix air cleaner filter element including outer and inner element suitable (in replacement) of existing make & specification for 500/600 KVA set. Complete all as specified and directed by Engr-in-Charge. |
| 16 | Supply & Fix air cleaner filter including outer and inner element suitable of existing make & specification for 250 KVA to 320 KVA set. Complete all as specified and directed by Engr-in-Charge. |
| 17 | Supply & Fix air cleaner filter including outer and inner element suitable of existing make & specification for 200 KVA set. Complete all as specified and directed by Engr-in-Charge. |
| 18 | Supply & Fix air cleaner filter including outer and inner element suitable (in replacement)of existing make & specification for 40 KVA to 100 KVA set. Complete all as specified and directed by Engr-in-Charge. |
| 19 | Supply & Fix ‘V' belt for dynamo A-49/50 or suitable of existing make & specification for 40 KVA to 600 KVA set complete all as specified and directed by Engr-in-Charge. |
| 20 | Supply & Fix flexible pipe for fuel pump to PT pump with banjo, banjo washer and nut, bolts suitable of existing make & specification for 500/600 KVA set. Complete all as specified and directed by Engr-in-Charge. |
| 21 | Supply & Fix flexible pipe for fuel pump to PT pump with banjo, banjo washer and nut, bolts suitable of existing make & specification for 250 to 320 KVA set. Complete all as specified and directed by Engr-in-Charge. |
| 22 | Supply & Fix flexible pipe for fuel pump to PT pump with banjo, banjo washer and nut, bolts suitable of existing make & specification for 40 to 100 KVA set. Complete all as specified and directed by Engr-in-Charge. |
| 23 | Repair/replacement and calibration of FIP of capacity 500/600 KVA DG Sets including replacement of plunger, manifold washer, etc all as required other minor items and testing after re-fixing on engine and setting the rated RPM complete all as specified and directed by Engr-in-Charge. |
| 24 | Description all as per Ser item No 21.00 here- in- before, but 250 KVA to 320 KVA as per existing Make. |
| 25 | Description all as per Ser item No 21.00 here- in- before, but 200 KVA as per existing Make. |
| 26 | Description all as per Ser item No 21.00 here- in- before, but 40 KVA to100 KVA as per existing Make. |
| 27 | Dismantling and taking out of self-starter from mounting and to carryout complete servicing/overhauling of the same with carbon brush, armature coil, field coil, solenoid switch, bush and pinion and other related components of DG set capacity 500/600 KVA suitable of existing make & specification, complete all as specified and directed by Engr-in-Charge. |
| 28 | Description all as per Ser item No 25.00 here- in- before, but 250 KVA to 320 KVA. |
| 29 | Description all as per Ser item No 25.00 here- in- before, but 200 KVA. |
| 30 | Description all as per Ser item No 25.00 here- in- before, but 40 KVA to100 KVA. |
| 31 | Repair/Replacement and callibration of injector assy including replacement injector cups barrel, nozzles,o rings screen filter and setting the oil pressure with suitable for 500/600 Kva DG sets as per existing Make. complete all as specified and as directed by Engr-in-Charge. |
| 32 | Description all as per Ser item No 29.00 here- in- before, but 250 KVA to 320 KVA . |
| 33 | Description all as per Ser item No 29.00 here- in- before, but 200 KVA . |
| 34 | Description all as per Ser item No 29.00 here- in- before, but 40 KVA to100 KVA . |
| 35 | Repair/servicing and overhauling of unserviceable dynamo by dismantling the same from DG set after taking down the fan belt and pulley. Repair of the same with armature coil, carbon (1 set) field coil, clutch bearing etc and other related items and duly re-assembling all the dismantled items and refixing the same on mountings and testing complete of DG set capacity 500/600 KVA suitable of existing make & specification, complete all as specified and as directed by Engr-in-Charge. |
| 36 | Description all as per Ser item No 33.00 here- in- before, but 250 KVA to 320 KVA. |
| 37 | Description all as per Ser item No 33.00 here- in- before, but 200 KVA. |
| 38 | Description all as per Ser item No 33.00 here- in- before, but 40 KVA to100 KVA. |
| 39 | Supply & fix automatic voltage regulator, Diode forward and reverse rotating rectifier assembly complete including taking down unserviceable AVR of DG set capacity 500/600 KVA suitable of existing make & specification, complete all as specified and as directed by Engr-in-Charge. |
| 40 | Description all as per Ser item No 37.00 here- in- before, but 250 KVA to 320 KVA. |
| 41 | Description all as per Ser item No 37.00 here- in- before, but 200 KVA. |
| 42 | Description all as per Ser item No 37.00 here- in- before, but 40 KVA to100 KVA. |
| 43 | Supply and fixing in repalcement of battery cable lead (copper) of size 35 Sqmm (198cm long) or as per sample, complete all as specified and as per directed by Engr-in-Charge. |
| 44 | Supply and fixing in repalcement of inter connection battery cable lead (copper) with terminal size 35 sqmm (30cm long) or as per sample, complete all as specified and as per directed by Engr-in-Charge. |
| 45 | Supply and top up Engine Oil SAE 20W/40 Make: HP/Indian oil/Castrol or its equivalent complete all as specified and as per directed by Engr-in-Charge. |
| 46 | Supply and top up Engine Oil SAE 15W/40 Make: HP/Indian oil/Castrol or its equivalent complete all as specified and as per directed by Engr-in-Charge. |
| 47 | Supply and top up DAFC 50% Make: HP/Indian oil/Castrol or its equivalent complete all as specified and as per directed by Engr-in-Charge. |
| 48 | Supply and topping up of acid mixture suitable for lead acid batteries of 12 volts complete all as specified and directed by Engr-in-Charge. |
| 49 | Supply and topping up of distilled water suitable for lead acid batteries of 12 volts complete all as specified and as per directed by Engr-in-Charge. |
| 50 | Battery terminal +ve and -ve with bolt & nuts complete all as specified and as per directed by Engr-in-Charge. |
| 51 | Fan belt A-44, A-42, A-41, A-40 or as existing size & make suitable for DG sets of capacity 40 KVA to 600 KVA complete all as specified and as per directed by Engr-in-Charge. |
| 52 | Diesel benjo Hose pipes of 1.0 Meter length with both edges brass clamps of existing model suitable to DG Set of capacity up to 125 KVA including taking down old unserviceable one complete all as specified and directed by Engr-in-Charge. |
| 53 | Diesel benjo Hose pipes of 1.0 Meter length with both edges brass clamps of existing model suitable to DG Set of capacity above 125KVA up to 600 KVA including taking down old unserviceable one complete all as specified and directed by Engr-in-Charge. |
| 54 | Control panel of 500 KVA DG set consist of control cubical fabricated sheet construction indoor type suitable for mounting accessories as comprises below, complete all as specified and directed by Engr-in-Charge. :-(i) Operator interface:- (a) Manual start/Stop (b) Auto/remote start (c) Auto LED (d) Manual LED (e) Common shutdown LED (f) Common warning LED (g) Exercise LED (h) Emergency stop (local/ remote) (j) Alphanumeric screen (k) Remote start input active LED(I) Fault reset(ii) Threshold warning indictions :- (a) Low oil pressure (b) Low Engine coolant temp (c) High engine coolant temp (d) Low coolant level (e) Low battery voltage (f) High battery engine (g) Battery alt charge fault (h) Over current (j) Over load |
| 55 | (iii) Measurement & instrumentation (Engine Side) :- (a) Oil pressure (b) Oil temp (c) Water temp (d) Engine speed (e) Hours Run (f) Numbers of starts (g) Battery voltage (h) Exhaust temp.(iv) Measurement & Instrumentation:- 3 Phase L-L & L-N voltage & Frequency (Alternator Side).(a) 3 Phase current (b) KWH (c) Total KVA (d) Total KW ) P.F (e) per Phase KVAr, KW (f) Per phase KVA |
| 56 | M & L in replacment of 180 AH 12 Volts batteries for DG sets 40 to 600 KVA DG sets including connecting to DG set complete all as specified and directed by Engr-in-Charge. |
| 57 | S & F battery terminal brass complete with GI nuts & bolts including taking out old unserviceable battery terminal brass complete all as specified and directed by Engr-in-Charge. |
| 58 | M&L for replacement of door of sound proof canopy of DG Sets by replacing of door canopy stainless steel hinges with 3 Screws per hinges and any type of welding work for smooth functioning of all doors of DG Sets, complete all as specified and directed by Engr-in-Charge. |
| 59 | Disconnecting all the incoming and outgoing rubber hoses and draining out the water from the choked radiator assembly of the existing make and model and various capacities DG sets and taking down the radiator assembly by unscrewing all mechanical/electrical connections from the existing mounting, transporting the same to civil workshop for carrying out servicing, opening the top and bottom covers of radiator assembly, cleaning thoroughly the chocked pipe of the radiator by using chemical detergent, lime caustic soda, cotton etc., cleaning of all the deposited sediments in the pipes/tubes including arresting of leakage by means of soldering, brazing and transporting back to site and refixing the same in its original position with suitable size nuts, bolts and washers and Anti vibrating mounting(AVM) pads as required as per OEM recomendation etc., for the DG set of capacity up to 200 KVA, complete all as specified and directed by Engr-in-Charge. |
| 60 | Description all as per Ser item No 56.00 here- in- before, but for the DG sets above 200 KVA and up to 600 KVA capacity complete all as specified and directed by Engr-in-Charge. |
| 61 | Drain out the fuel from the fuel tank of DG set of any size/capacity and keeping it in separate container safely, disconnecting all the fuel lines and other mechanical connections and taking out the fuel tank for cleaning, internally and externally by removing all the accumulated dirt/ sediment, leak testing the tank and replacing the drain plug and PVC pipe, calibrating the fuel tank, refilling the drained out fuel back into the tank and marking of liters in gauge and provision of locking arrangements complete all as specified and directed by Engr-in-Charge. |
| 62 | Self starter Motor, 12/24 volts, suitable for existing DG set above 40 KVA to 500 KVA capacity including making all necessary electrical/mechanical connection as per recomendation of OEM of DG Set & dismantling/taking out old unserviceable self starter Motor from existing position complete all as specified and directed by Engr-in-Charge. |
| 63 | Supply and fix new Turbo Charger Assembly DG Sets of capacity up to 200 KVA. (In replacement) duly disconnecting the mechanical and electrical connections from for the following DG sets, opening and thoroughly checking to carry out repairs complete to the Turbo Charger Kit and spares as required at site including any mechanical and reassembling and refixing the new turbo charger assembly to its original position and reconnecting the same including testing complete all as specified and directed by Engr-in-Charge:- |
| 64 | Description all as per Ser item No 60.00 here- in- before, but for the DG sets above 200 KVA and up to 600 KVA capacity complete all as specified and directed by Engr-in-Charge. |
| 65 | Repair /Replacement and servicing to AMF panel of capacity 320 KVA to 600 KVA from the Circuit system by checking the following parameters for proper functioning using CTC for clear off the carbon deposited on cables/parts links . a) Checking / fault diagnosis of Isolator ,Battery charger,Auto/Manual selector switch & Current Transformer. b) Checking the Electronic circuit boards with phase indication lamp 220 V. c) Checking the functionality & caliberation of Power Relays (Cranking Relays). d) Checking the Mechanism of isolator module and vcb module e) Checking the Contactor Assembly & PLCs wtih under+ over voltage relay .Note :- Rates of all spares and Parts including repair and replace are included in quoted rate. |
| 66 | Replacement of microprocessor based control unit suitable to DG set controlls/commands of 250 to 600 KVA capacity with all listed parameters including testing complete all as specified and directed by Engr-in-Charge. |
| 67 | S& F in repair of Over current/Earth fault relay normal inverse (1.3s-3.0 s), very invrse (1.5s), Extrmelt inverse (0.8s) and definite tie(1.0s,10s,100s) suitable to DG set controlls/commands of 250 to 600 KVA capacity with all listed parameters including testing complete all as specified and directed by Engr-in-Charge. |
| 68 | S& F in repair of Genset Battery charger input voltage 220V AC output voltage 24VA DC, output current 16Amp including testing complete all as specified and directed by Engr-in-Charge. |
| 69 | M&L for servicing/callibration /Repair to Air circuit breaker, 800/1000 Amp by OEM OF ACB only for EDO ( Electrically Draw out type/MDO type ( Mannually Draw out type).Taking out ACB for servicing/repair and checking/callibration of microprosser release ,Earth fault protection of 4 pole,50 KA breakingt capacity 415 volts with all draw out type mechanism,advanced self powered electronic protection units,neutral overload protection.automatic earth fault relay/over current relay,automatic safety shutter,inbuild temperature protection.icu=ics=icw(1s)=50 Ka fixed in panel complete including relay wiring checking,LT UG cable connection for its healthy functioning complete all as specified and directed by Engr-in-Charge. Note- Certificate of Servicing /callibration will be providded by the contractor through OEM |
| 70 | S& F in repair of Digitel KW/PF Meter , voltage -440V,Current-5A, Cos (-0.5-1+0.5) including testing complete all as specified and directed by Engr-in-Charge. |
| 71 | S& F in repair of Annunciator for alarm windos, common shut down,common wiring, Earth fault. Canopy over temp and supply indicator including testing complete all as specified and directed by Engr-in-Charge. |
| 72 | S& F in repair of 3 Phase VIF meter for voltage, ammeter and Hz for 3 phase including testing complete all as specified and directed by Engr-in-Charge. |
| 73 | S& F in repair of contactor 1NO +1NC MNX-A1 3 phase including testing complete all as specified and directed by Engr-in-Charge. |
| 74 | S& F in repair of relay model MSP-4P, voltage rating 240VAC/28VDC, Current rating-3A including testing complete all as specified and directed by Engr-in-Charge. |
| 75 | M&L for earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6.0mm thick buried directly in ground, (Earth pit not less than 2.25 mtr deep below ground level) with top edge of plate not less than 1.5 mtr below normal ground level, connected to galvanised iron strip 25X4 mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanised standard iron or steel all as specified or indicated in electrical plate no 3 of MES Part-I, including testing on completion including the material and labour of the following :-(a) Excavation and earth work for drilling hole for electrode in any type of soil. (b) PCC pit in cement concrete 1:2:4 type B-1.(c) Precast RCC cover with suitable handle 40 mm thick in PCC 1:2:4 type B-1, reinforced with welded steel wire fabric weighing not less than 1.87 Kg/Sqm.(d) Funnel with watering pipe of GI 20 mm nominal bore medium grade and copper lugs etc all as specified. (e) 15 mm nominal bore light grade GI protection pipe 7.5 mtr long for protection of earthing lead from mechanical injury or tempering. |
| 76 | (f) Requisite quantity of common salt and charcoal.(g) Testing of earthing.Note : On testing after completion of earthing, if the desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk and cost to the entire satisfaction of the Engineer-in-Charge. |
| 77 | M&L for disconnecting and taking down old unserviceable control cable any size any description and supply, fixing, testing and commissioning of LT 1100 volts 1.5 Sqmm 10 core copper conductor armoured cable connecting the cable in positioning properly by providing suitable new copper lugs GI bolts & Nuts washers etc complete all as specified and directed by Engr-in-Charge. |
| 78 | Supply, fabricate, erect , connect, test and commissoning of factory made, CPRI approved, cubical type, indoor type LT panal board of size 1500x600x500mm, totally enclosed , dust, weather and vermin proof 1100 Volt grade , 50Hz, AC supply made out by 3.15mm thick CRCA sheet steel for load bearing and 3.15 mm thick for non load bearing, fully compartmentalised, with IP 65 protection all as per conferming to IS 2417 of 1962 complete including the following accessories housed complete all as specified and directed by Engr-in-Charge. (a) Power controls Genset controller 500 KVA for parameter voltage, frequency, oil pressure and water temperature, Automatic start modu;le with LCD display, automatic network failure control, manual stop, auto mode and manual start - 01 Nos (b) MCCB 630 Amp 25 KA four pole 415 volt -01 (c) Voltmeter and Ammeter-01 Set (d) Indicator (RYB) , DG load on, DG running-01 Set (e) control wwiring Genset to LT Panel board compete for all parameter -01 Job (f) Bus bar 1200 Amp with CT&PT- 04 Nos |
| 79 | Supply, fabricate, erect , connect, test and commissoning of factory made, CPRI approved, cubical type, indoor type LT panal board of size 1500x600x500mm, totally enclosed , dust, weather and vermin proof 1100 Volt grade , 50Hz, AC supply made out by 3.15mm thick CRCA sheet steel for load bearing and 3.15 mm thick for non load bearing, fully compartmentalised, with IP 65 protection all as per conferming to IS 2417 of 1962 complete including the following accessories housed complete all as specified and directed by Engr-in-Charge. (a) Power controls Genset controller 250/320 KVA for parameter voltage, frequency, oil pressure and water temperature, Automatic start modu;le with LCD display, automatic network failure control, manual stop, auto mode and manual start - 01 Nos (b) MCCB 400 Amp 36 KA four pole 415 volt -01 (c) Voltmeter and Ammeter-01 Set (d) Indicator (RYB) , DG load on, DG running-01 Set (e) control wiring Genset to LT Panel board compete for controller all above parameter -01 Job (f) Bus bar 800 Amp with CT&PT- 04 Nos |
| 80 | S& F in repair of 4 pole power contactor MCX 41, 325 Amp (under AC-1 duty) 2NO+2 NC suitablable fod terminal L1 to L4 line input and T1 to T4 load output terminal with A1, A2 control coil suitable for 200KVA AMF panel including testing complete all as specified and directed by Engr-in-Charge. |
| 81 | Repair and overhauling of Non clog Centrifugal Pumpset Diesel driven head-10Mtr,2250LPM,1500 rpm with autmatic battery start 12 BHP,1500RPM,air cooled with the following works and replacement of spare parts. (a) Disconnecting the electric connection of the alternator, decoupling from engine and disconnecting unsv/serviceable parts for repair/ replacement such as inlet/outlet manifold, turbocharger, FIP, air cleaner, fuel injectors, cylinder head, tappet cover, cylinder linner, piston assy, connecting rod assy, exhaust valve seat, insert valve seat, fuel pump, L.O. pump, oil pump, piston assy, crank shaft etc. at site and cleaning the reusable parts with Keroscene oil for reuse complete all as specified and directed by Engr-in-Charge.(b) Transportation of unserviceable parts such as cylinder block, cylinder head, oil pump , FIP, L.O. pump, oil pump, injector nozzles, crank shaft etc. |
| 82 | (c) Grinding, polishing & facing of cylinder heads in and including replacement of seats and minor repair to cylinder head all as directed by Engr-in-Charge. (d) Re-assembling the Engine and alternator complete and connecting the alternator and coupling with engine complete after repair/ replacement of serviceable/unsv spare parts .Note:- (i) The major spare parts required for overhauling of engine shall be measured and paid separately under relevant items.(ii) Minor spare parts such as plain machined washer, set screw, joint, set bolt, O rings, washer, spring dowel, dowel pin, bolts, pins, nuts, banjo bolts, copper washer etc for proper functioning of DG sets deemed to be included in the item rate. |
| 83 | Supply and fixing of spare parts for 12 BHP DG sets as mentioned in item no 77 and replacement as under |
| 84 | Oil filter |
| 85 | Diesel filter |
| 86 | Air filter |
| 87 | 4R Self starter |
| 88 | Belt 3PK |
| 89 | Diesel pipe 3 mtr |
| 90 | 6YDA Coupling |
| 91 | Alternator repairing |
| 92 | Turbo core J92F |
| 93 | Turbo hose |
| 94 | Turbo pipe |
| 95 | Repairing and calibration of fuel pump |
| 96 | Cup, injector |
| 97 | sleeve injector |
| 98 | Calbiration of injector assembly including replacement of injector cups, barrel,nozzles, O-rings screen filter and setting the oil pressure with testing suitable for 12 BHP DG Set as per existing make Kirloskar complete all as specified and directed by Engr-in-Charge. |
| 99 | M & L in replacment of 42 AH 12 Volts batteries for DG sets 12 BHP including connecting to DG set complete all as specified and directed by Engr-in-Charge. |
| 100 | M & L in Tyre coupling Size flexible 11 complete all as specified and directed by Engr-in-Charge. |
| 101 | S&F PVC suction pressure hose pipe 100 mm dia, 5mm thicknes heavy duty complete all as specified and directed by Engr-in-Charge |
| 102 | M & L MS flange suitable for 100 mm dia pipewith complete all as specified and directed by Engr-in-Charge. |
| 103 | Repair and overhauling of Diesel Engine driven generating set 6 cylinder of cap upto 320 KVA installed at Jib water pump complete with the following works and replacement of spare parts. (a) Disconnecting the electric connection of the alternator, decoupling from engine and disconnecting unsv/serviceable parts for repair/ replacement such as inlet/outlet manifold, turbocharger, FIP, air cleaner, fuel injectors, cylinder head, tappet cover, cylinder linner, piston assy, connecting rod assy, exhaust valve seat, insert valve seat, fuel pump, L.O. pump, oil pump, piston assy, crank shaft etc. at site and cleaning the reusable parts with Keroscene oil for reuse all as specified and directed by Engr-in-charge.(b) Transportation of unserviceable parts such as cylinder block, cylinder head, oil pump , FIP, L.O. pump, oil pump, injector nozzles, crank shaft etc. obtain from the above DG sets at site i.e. Jib filter point Udhampur to Kirloskar company or Kirloskar authorised Work shop at Jammu for repair, rectification of defects and retransportation of repaired parts/assembled engine from workshop to installation complete. |
| 104 | (c) Computarised checking of cylinder block for its defects/ leakage in oil and rectification of the same by X ray welding or otherwise as per manufacturer's specification. (d) Grinding, polishing & facing of cylinder heads in and including replacement of seats and minor repair to cylinder head all as directed by Engr-in-Charge. (e) Re-assembling the Engine and alternator complete and connecting the alternator and coupling with engine complete after repair/ replacement of serviceable/unsv spare parts incl testing and commissioning of DG set on full load upto desired satisfaction of Engr-in-Charge complete.Note:- (i) The major spare parts required for overhauling of engine shall be measured and paid separately under relevant items.(ii) Minor spare parts such as plain machined washer, set screw, joint, set bolt, O rings, washer, spring dowel, dowel pin, bolts, pins, nuts, banjo bolts, copper washer etc for proper functioning of DG sets deemed to be included in the item rate. |
| 105 | Supply and fixing of spare parts for 320 KVA DG sets as mentioned in item no 84 and replacement as under |
| 106 | Set Main bearing |
| 107 | Bearing connecting rod |
| 108 | Bushing connecting rod |
| 109 | Cylinder liner assy |
| 110 | Kit piston engine (Piston, piston pin, Piston ring) |
| 111 | Valve exhaust |
| 112 | Valve inlet |
| 113 | Valve guide stem |
| 114 | Inlet & exhaust valve seat |
| 115 | Gasket cylinder |
| 116 | Thrust washer |
| 117 | Push rod |
| 118 | water sealing |
| 119 | Baffle breather |
| 120 | Screen Breather |
| 121 | Bushing camshaft |
| 122 | Set of water hose |
| 123 | Set of fuel fleixible pipe , Manifold fuel pipe. |
| 124 | High pressure pipe ,Manifold fuel pipe. |
| 125 | Gasket kit (Upper and lower) |
| 126 | Main oil seal |
| 127 | M & L for painting of existing LT panel board / LT feeder pillar box, indoor or outdoor type, of size up to 2.0 × 1.50 × 0.60 metres, including inner shell and outer shell as well as angle iron frame, with Siemens Grey shade or matching the existing colour, as directed by the Engineer-in-Charge.The work includes thorough surface preparation by scraping, rubbing down with sand paper, wire brushing/grinding to remove loose paint, rusted and corroded particles; cleaning the surfaces with dry cloths to make them free from dust, grease, and foreign matter; repairing and making good uneven surfaces to achieve a smooth finish. The prepared surfaces shall then be treated with one coat of red oxide zinc chromate primer, followed by two coats of approved synthetic enamel paint, applied uniformly to obtain an even, smooth, and durable finish, complete all as specified and as directed by the Engineer-in-Charge. |
| 128 | M & L for repairing of outer housing of existing LT panel board / LT feeder pillar box, indoor or outdoor type, of size up to 2.00 × 1.50 × 0.60 metres, fabricated out of 2.0 mm / 3.15 mm thick CRCA sheet, including inner shell and outer shell, complete, including repairing and/or replacement of damaged or deformed portions of outer shell panels, panel doors, MCCB housing doors, changeover housing doors, straightening, refabrication where required, repairing of angle iron frame, tightening and/or replacement of nuts, bolts, screws, clamps, hinges, locking arrangements, and making the housing structurally sound, rigid, and properly aligned. Making good all repaired surfaces, ensuring proper closing and locking of doors, alignment of housings, and restoring the panel to serviceable condition, complete all as specified and as directed by the Engineer-in-Charge.Note: The cost of replacement of minor parts and accessories such as doors, angle iron sections, nuts, bolts, screws, clamps, hinges, and similar items required for execution of the work shall be deemed to be included in the quoted rate. |
| 129 | M&L for replacement on/off load change over switch 630 Amps 4 pole 415 Volt AC 50 Hz conforming to IS:13947, open execution as per existing panel board size including taking down old unserviceable one, complete all as specified and directed by the Engineer-in-Charge.Make: Cat Part No IHCNFO0630 of Havells or equivalent make approved by GE |
| 130 | Material & Labour for in replacement of steel nuts, bolts, washers of any size required at site complete all as specified and directed by the Engineer-in-Charge. |
| 131 | Excavation in trenches for Taking out / Laying HT/LT U/G Cable in any type of hard/ dense soil not exceeding 1.5 m wide and not exceeding 1.5m in depth and getting out complete all as specified and directed by Engr-in-Charge. |
| 132 | Returning , filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25 cm thick complete all as specified and directed by the Engineer-in-Charge. |
| 133 | Removing of excavated materials to a distance not exceeding 50 metre and depositing where directed at a level not exceeding 1.5 metre above the starting point complete all as specified and directed by the Engineer-in-Charge. |
| 134 | Taking out UNSV UG cable of any sizes/ capacity complete all as specified and directed by the Engineer-in-Charge. |
| 135 | Supply and Laying and fixing or passing through pipes or laid under floor of through walls etc jointing and testing LT Cross Linked Polythene Insulated(XLPE insulated) galvanized steel strip armoured electric cable size 10 sqmm 2 core, 1100 volt grade heavy duty ISI marked with aluminium conductor and overall served with an outer sheath of PVC, of cross sectional area including taking down. Note :Excavation, earthwork, Pipe for cable protection, etc to be measured and paid for separately |
| 136 | Description all as per Srl item No 94.00 here-in-before, but cross sectional area 16 sqmm, 4 core. |
| 137 | Description all as per Srl item No 94.00 here-in-before, but cross sectional area 25 sqmm, 3.5 core. |
| 138 | Supply and laying or fixing or passing through pipe, PVC insulated heavy duty industrial cables 5 core copper conductor(flexible) PVC insulated cable 1100 volt nominal area of conductor 2.5 sqmm (in replacement) making connections of street light fittings with overhead lines/UG Cable including taking out old cable complete all as specified and directed by the Engineer-in-Charge.Note :Excavation, earthwork, Pipe for cable protection, etc to be measured and paid for separately |
| 139 | Description all as per Srl item No 97.00 here-in-before, but cross sectional area 2.5 sqmm, 3 core. |
| 140 | Supply and laying Double walled corrugated pipe (DWC) of size 40 mm conforming to IS:14930(part-II)/IS 16205 Part II with necessary snap fit coupler for cable protection in trenches, along wall/pole, etc complete all as specified & directed by Engr-in-Charge. |
| 141 | Painting to RCC /steel tubular poles 9/12 metre long at surface of any description over 10 CM grith or width ,not otherwise described,prepare old or new untreated surface,old painted surfaces including priming cement based paints plaster with synthetic enambled paint coat and plastic emulsion coat over surface with two coats of aluminium paint including brackets, clamps, nuts bolts, washer etc. including making yellow and black strips alternatively (30 cm width each) on pole upto 1.5 metre from the ground level and marking of pole Nos with black paint having back ground yellow as per existing complete all as specified & directed by Engr-in-Charge. |
| 142 | Replacement of old unserviceable rusted GI tubing brackets, 40mm bore, light grade with new GI tubing bracket, 40mm bore, light grade, 1.20 metre length ,made to shape including MS clamp with nuts, bolts and washers etc complete all as specified & directed by Engr-in-Charge. |
| 143 | S&F in replacement Terminal box made out of SMC with hinged door and locking arrangements of size 140x140x95mm including Backlite 4 way connector,M.S. Clamps suitable for pole ,PCC/MS/GI/rail etc. with bolt, nut and washer ,electrical connections including MCB SP 6-32 Amps complete all as specified & directed by Engr-in-Charge. Make - Sintex product or equivalent in Havells/CG/Pplycab/Bajaj. |
| 144 | Supply and Fix insulation tape 25 mm wide 6 Mtr long ISI mark of Red-Yellow-Blue-Black-Green colour complete all as specified & directed by Engr-in-Charge.Make: Steel grip |
| 145 | LED flood light, 170 watt, 230 V, AC outdoor type with thermal management in multiple optics, powder coated, pressure die cast aluminium body with toughened glass visor, and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp,CCT 5700K, lumen efficacy not less than 110 lumen/watts (in repair) complete all as specified & directed by Engr-in-Charge.Note: (a) MS clamp,Brackets required for fixing of fitting are inclusive of rate quoted.(b) Connection & erection of the same on pole shall deemed to be included in quoted rate. |
| 146 | LED flood light, 70 watt, 230 V, AC outdoor type with thermal management in multiple optics, powder coated, pressure die cast aluminium body with toughened glass visor, and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp,CCT 5700K, lumen efficacy not less than 110 lumen/watts (in repair) complete all as specified and directed by Engr-in-Charge.Note: (a) MS clamp,Brackets required for fixing of fitting are inclusive of rate quoted.(b) Connection & erection of the same on high mast pole shall deemed to be included in quoted rate. |
| 147 | LED street light fitting 60 Watt , 230 V, AC outdoor type with high pressure die cast aluminum hosing and heat resistant (in repair) complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics with IP-66 protection, CCT 5700K, lumen efficacy not less than 110 lumen/watts complete all as specified and directed by Engr-in-Charge. Note: (a) MS clamp,Brackets required for fixing of fitting are inclusive of rate quoted.(b) Connection & erection of the same on pole shall deemed to be included in quoted rate. |
| 148 | LED street light fitting 30/35 Watt , 230 V, AC outdoor type with high pressure die cast aluminum hosing and heat resistant (in repair) complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics with IP-66 protection, CCT 5700K, lumen efficacy not less than 110 lumen/watts complete all as specified and directed by Engr-in-Charge. Note: (a) MS clamp,Brackets required for fixing of fitting are inclusive of rate quoted.(b) Connection & erection of the same on pole shall deemed to be included in quoted rate. |
| 149 | S &F LED Tiranga Rop light 18 Mtr,IP 65,Input Power 10W/meter,Input Voltage 220-240 VAC Input frequency 50 Hzs,Input current 0.045 Amp/Mtr,Power factor 0.95,Width of strip(+/- 0.1 mm) 8 mm length/reel-18 mtrs,No of led per mtr 120 LED,LED Beam angle 120 degree ,Rope light per Colours length 6 mtr orange, 6 mtr white ,6 mtr Green,Fixing method silicone clip ,Ingrass Protection -IP -65, Ingrass protection method silicone tube ,silicone tube dimention 11.5x5.5 mm+/- 0.5 mm,working temp range-20 degree celcius to + 45 degree celcious ,working humidity range 10-90 RH, including driver for each cut piece complete all as specified & directed by Engr-in-Charge. |
| 150 | S&F in reolacement LED Bollard light 9 W in rectangular shaped victorian design with opal acrylic diffuser IP65 protection and co-related color temperature (CCT) of 3000K complete all as specified & directed by Engr-in-Charge. |
| 151 | S&F Landscape Lights Warm white type SPYKZ LED Spike/Bush light 9 Wattage and co-related color temperature (CCT) 3000K with die-cast aluminium housing designed for rugged outdoor usage & IP 65 protection complete all as specified & directed by Engr-in-Charge. |
| 152 | S&F 20W ALL-IN-ONE SOLAR STREET LIGHT NG SERIES AIO Solar Street Light is made with High Efficiency Mono Crystalline So;ar PV Module, Lithium Ferro Phosphate battery with in-built BMS technology, High Efficacy LED, MPPT Solar Charger Controller and Aluminium Extruded body & is specially progrmmed to automatically control the dimming and brightness of light,which increas the backup time complete all as specified & directed by Engr-in-Charge. |
| 153 | Supply and fix LED spike light fitting 9/10 watts(Multi colour), IP65, Energy Saving LED light with PDC , Aluminium body & secondary Optical lens for superior light distrubution , Efficacy > 55 Lm/W. 5700k , complete all as specified & directed by Engr-in-Charge. |
| 154 | S&F in replacement Power contactor 3 phase 415 Volts, upto 40 Amps, coil voltage of rating 240 Volts including taking down old unserviceable power contactor complete all as specified and directed by Engr-in-Charge. |
| 155 | Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required.) complete all as specified and directed by Engr-in-charge. |
| 156 | MCB TPN -63 Amp, 230V, 50Hz, 10 KA (in replacement) complete all as specified & directed by Engr-in-Charge. |
| 157 | MCB TPN -40 Amp, 230V, 50Hz, 10 KA (in replacement) complete all as specified & directed by Engr-in-Charge. |
| 158 | MCB SP-16 Amp, 230V, 50Hz, 10 KA, (in replacement) complete all as specified & directed by Engr-in-Charge. |
| 159 | MCB SP-25 Amp, 230V, 50Hz, 10 KA, (in replacement) complete all as specified & directed by Engr-in-Charge. |
| 160 | Supply and erecting steel tubular swaged poles erected to truly vertical or planted as strut complete with 6mm thick mild steel base plate(300mmx300mm), welded to pole, finial taper plug, bolts, nuts, and screws. Poles made out of ERW MS tubing conforming to IS-2713 Part-II Type 410 SP-37, 9.0mtr long including drilling of holes of required size for fixing of cross arms, painting the exposed surfaces of pole with two coats of aluminum paint over a coat of red oxide zinc chrome primer and with two coats of black bitumenous paint internally and portion embedded in concrete, making five black & white bands at lower portion of pole each 300mm wide alternately upto the height of 1.5 m and marking pole No. with black paint at suitable height including making two nos holes of suitable size in steel tubular pole by gas welding for passing PVC cable connection from junction box to security lights through pole where junction box to be fitted in pole complete all as specified and directed by Engineer-in-Charge. Note: - Excavation, Earth Work and PCC in foundation shall be measured and paid for separately. |
| 161 | Plain cement concrete M- 7.5, (1:4:8), type D-2 (using 40mm graded crushed stone aggregates) as in foundation complete all as specified and directed by Engr-in-Charge. |
| 162 | Plain cement concrete, M-15, type B-0 (using 20 mm graded crushed stone aggregates) as in coping complete all as specified and directed by Engr-in-Charge. |
| 163 | Supply & fixing GI pipes of size 40 mm dia, Light grade, galvanized with all fitting such as bends, tees, nipples, union and sockets, clamps etc laid in trenches, under floor/walls etc complete all as specified and directed by Engr-in-Charge. |
| 164 | S&F in replacement of automatic street light control Panel three phase with ingress protection IP-65 made of 14 SWG CRCA sheet metal(850 mm HeightX500mm Breath X 400 Depth), self supporting, Floor mounted, dust, vermin and weather proof for outdoor use shall be supplied for locally/automatically switching’ ON/OFF of luminaries (100 W/60 W x 10-20 Nos) having protection IP-66 using Infrared sensor based Nature Switch for automatic switching of street light. Nature switch operation should be based on Natural Light Lux*level. Reqd illuminance level also have part night operation facility for min 4 hrs to max 12 hrs. The sensor along with suitable rating power contractor (s), one Incoming and required no of Outgoing MCBs rating of 63/40 Amps & main load circuit wiring (copper) of min 10 sqmm. The circuit should be also have provision for manual operation (i.e. sensor by pass option) complete all as specified and directed by Engr-in-Charge. Note: Panel should be placed on PCC foundation & M&L for foundation included in quoted rate. |
| 165 | S & F LED Highbay light with lens , 60 watt, 230 V, AC outdoor type with thermal management in multiple optics, powder coated, pressure die cast aluminium body with toughened glass visor, and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp,CCT 5700K, lumen efficacy not less than 130 lumen/watts (in repair) complete all as specified and directed by Engr-in-Charge. |
| 166 | Opening, maintenance and general servicing of arrangement of base compartment with SGDD Type Winch of highmast light & Control gear box including removal of dust, tightening of all nut bolts, cleaning, checking and servicing of winch gear box, power tool, Mast Door, SS wire rope, wire rope clamp and bobbin arrangement, handle for manual operation, mechanical torque limitor, Three-six Pully system, winch suspension system and other allied electrical components complete all as specified and directed by Engr-in-charge.Note : (i) Shifting of winch from AOR of AGE Water supply to workshop (Tro/ Fro) shall deemed to be included in quoted rate.(ii) Repairing/rewinding of Power tool motor 1/1.5 HP shall deemed to be included in quoted rate. |
| 167 | LED flood light, 50 watt, 230 V, AC outdoor type with thermal management in multiple optics, powder coated, pressure die cast aluminium body with toughened glass visor, and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp,CCT 5700K, lumen efficacy not less than 110 lumen/watts (in repair) complete all as specified and directed by Engr-in-Charge.Make-Bajaj Cat Part No. GLATT F 50L WH PO PC SD/Philips / Crompton/Havells, Wipro.Note: (a) MS clamp,Brackets required for fixing of fitting are inclusive of rate quoted.(b) Connection & erection of the same on high mast pole shall deemed to be included in quoted rate. |
| 168 | S&F Weather proof Street light Junction Box with Pole Clamp, Enclosure: 140 x 190 x 100 mm IP65 IP67 Water Proof and IK08 Impact Resistance & Ineffability as per IS13360. Top Cover and Bottom is made with Virgin grade ABS Material. Cable Outlet: PG 29 PVC Cable Gland (2x) and PG 13.5 PVC Cable Gland (1). Terminal: 63A 4 Way TPN Terminal Bar with nuts, Pole Mounting: Nylon 6 30% Glass filled heavy clamp with Stainless steel Hose Clamp up to 4inch Dia Pole complete all as specified and directed by Engr-in-charge. |
| 169 | S&F in replacement Double dome LED type aviation obstruction light provided on top of Highmast. Led lamp 2nos x 100watt aviation obstruction light fitted in a weather- proof box on body unit of Aluminium alloy including taking down old complete all as specified and directed by Engr-in-charge. Note:- (i) Connection & erection of the same on high mast pole shall deemed to be included in quoted rate.(ii) All extra fittings like clamps, Nut bolts, washers required to install the light shall deemed to be included in quoted rate. |
| 170 | MCB SPN-40-63 Amp, 230V, 50Hz, 10 KA, (in replacement) complete all as specified & directed by Engr-in-Charge. |
| 171 | S& F analog time switch Usage for Type Analog Time switch Control Highlights ,Switch Push Button ,Voltage 220 V AC - 240 V AC ,16A Power Source Wired Safety Certification IEC 60730-1/IEC 60730-2-7 Width 54.5 m complete all as specified and directed by Engr-in-Charge. |
| 172 | Lockable feeder pillar box with ingress protection IP-65 made of 14 SWG CRCA sheet metal(850 mm HeightX500mm Breath X 400 Depth), self supporting, Floor mounted, dust, vermin and weather proof for outdoor use shall be supplied for locally/automatically switching’ ON/OFF of luminaries (200 W x 06 Nos) & operation of winch motor. The control panel comprises the following:a) 63 Amps, 4 Pole MCCB for incomer power, Make: ABB/L&T/Siemens/SCHNEIDER.b) 32Amps TPN fuse switch unit as isolator for motor, Make: ABB/L&T/Siemens/SCHNEIDER.c) Earth leakage Relay with core balance transformer, Sensitivity: 30 MA to 2A, Time delay: 0 – 2 sec., Make: SCHNEIDER/ MDS Legrand/L&T/SIEMENS/ABB.d) 32 Amps triple pole AC 3 duty power contactor for lighting circuit, coil Voltage: 230VAC+/-10%, |
| 173 | e) Start/Stop push button for locally switching ON/OFF the luminaries – 1 set. NS type fuses carrier and base for control circuit. (Start/stop PB make:- Schneider Electric, L&T,Siemens and Fuse carrier and Fuse make:- GE,L&T,Siemens,CGL)f) Automatic lighting Switch with digital time switch of rail mounting suitable for astronomical calculations of sun rise and sun set by setting date, time and positions of longitude and latitude, asrto time –switch, 230V AC, 50HZ.g) 2Nos hoisting duty contactor for forward and reversing operation of motor along with Push buttons, LED indication lamps, other requisite switchgears for motor operation. (Contactor Make:- ABB/L&T/Siemens/SCHNEIDER)h) Detachable gland plate and nut-bolt type terminal blocks for incoming and outgoing cable connections.i) Feeder Pillar box to be painted with by 2 coats of primer followed by epoxy grey paint of shade RAL-7035.j) Push button for raising and lowering the mobile part shall operate on \\"Dead man principal\\" i.e. action shall cease as soon as the button is released.k) Single line diagram of electrical circuit to be shown on inner surface of the door of Feeder pillar box.Note: Panel should be placed on PCC foundation & M&L for foundation included in quoted rate. |
| 174 | S& F timeline Astro Street Light Timer with Adjustable High-low Voltage Trip and Cutout and Surge Protection ,Voltage 220 V AC - 240 V AC , compete all as directed. Total in Figures 0.0 0.0 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail