| 1 | Excavating in trenches n.exc 1.5 m width and n.exc 1.5m in depth for taking out cable and cable cover and getting out in any type of soil complete all as specified and directed by Engr-in-charges. |
| 2 | Returning, filling in, including spreading levelling, watering and well ramming in layers n.exc 25 cm complete all as specified and directed by Engr-in-charges. |
| 3 | Removing excavated materials n.exc 50 mtr depositing where directed at a level n.exc 1.5 m above the starting point complete all as specified and directed by Engr-in-charges. |
| 4 | M&L for sand cushioning to PVC/ XLPE cables with tibba sand and punning to provide required cover to UG cables complete all as specified and directed by Engr-in-charges.Note : For the purpose of payment only punned thickness will be measured |
| 5 | Supply and laying reinforced precast concrete cable cover, class LV, type 2 flat, size 300mm x 180mm x 40mm Complete all as specified and directed by Engr-in-charges. |
| 6 | M &L for Road cutting with the layer of bitumen/boulders in trenches n.exc. 45 m width and n.exc 0.6 m in depth for taking out cable and cable cover and getting out complete all as specified and directed by Engr-in-charges. |
| 7 | Supply & Laying, connection with lugs of suitable size at both end and testing electric under ground LT cable XLPE insulated armoured aluminium conductor cable 1100 volts grade of size 10 sqmm 4 core Complete all as specified and directed by Engr-in-charges. |
| 8 | Supply & Laying, connection with lugs of suitable size at both end and testing electric under ground LT cable XLPE insulated armoured aluminium conductor cable 1100 volts grade of size 25 sqmm 3.5 core Complete all as specified and directed by Engr-in-charges. |
| 9 | Supply & Laying , connection with lugs of suitable size at both end and testing electric under ground LT cable PVC/XLPE insulated armoured aluminium conductor cable 1100 volts grade of size 35 sqmm 3.5 core in trenches, ducts, pipe on walls, poles Complete all as specified and directed by Engr-in-charges. |
| 10 | Supply & Laying, connection with lugs of suitable size at both end and testing electric under ground LT cable XLPE insulated armoured aluminium conductor cable 1100 volts grade of size 50 sqmm 3.5 core in trenches, ducts, pipe on walls, poles Complete all as specified and directed by Engr-in-charges. |
| 11 | Supply & Laying, connection with lugs of suitable size at both end and testing electric under ground LT cable XLPE insulated armoured aluminium conductor cable 1100 volts grade of size 70 sqmm 3.5 core in trenches, ducts, pipe on walls, poles Complete all as specified and directed by Engr-in-charges. |
| 12 | Supply & Laying, connction with lugs of suitable size at both end and testing electric under ground LT cable XLPE insulated armoured aluminium conductor cable 1100 volts grade of size 95 sqmm 3.5 core in trenches, ducts, pipe on walls, poles Complete all as specified and directed by Engr-in-charges. |
| 13 | Supply & Laying, connction with lugs of suitable size at both end and testing electric under ground LT cable XLPE insulated armoured aluminium conductor cable 1100 volts grade of size 120 sqmm 3.5 core in trenches, ducts, pipe on walls, poles Complete all as specified and directed by Engr-in-charges. |
| 14 | Checking and attending to welding work in reapirs to iron frame gate, LT Panel / Bus bar's door and other iron misc works, repair by welding (run or spot welding as per site requirement) including replacement of defective items/material alongwith & including welding machine golves, welding glass, welding rod any other tools required, as per requirement Complete all as specified and directed by Engr-in-charges. |
| 15 | Material and labour for cutting of tree-branches touching HT/LT OH lines having girth n.exc 30cm and removing the branches to a distance n. exc 50 Mtr and as desired complete all as specified and directed by Engr-in-charges. |
| 16 | M & L for Cable route marker made out of GI non corrosion of size 150mm x 150mm x 5mm of plate and suitable height at least 1 feet from ground after grouting into the ground including writing the HT/LT Cable by engraqving/ painting complete fixed in PCC including excavation and RF and removing Complete all as specified and directed by Engr-in-charges. |
| 17 | Taking down carefully aluminimum conductor from overhead pole for taking in schedule of credit complete all as specified and directed by Engr-in-charges. |
| 18 | Taking down old unsv bus bars, and supply, install, testing & commissioning of bus bar chamber of size 60 cm x 60cm x 40 cm outdoor type suitable for LT 415 volts 3 phase 4 wire system factory made cubical complete materialised dust and vermin proof (protection class IP 54), made out of 3.15mm thick MS sheet (CRCA) including factory made hinged type door both side opening with locking arrangement duly painted with two coats of synthetic enamel paint with powder coated finish over a coat of zinc chrome primer complete all as specified and directed by Engineer-in-Charge. The panel board shall be comprising of the following accessories |
| 19 | (a) Copper bus bar cap 250 Amp - 04 |
| 20 | (b) Digital Voltmeter - 96 x 96 mm flush secure panel mounting type 0-500V with selector switch - 01 |
| 21 | (c) Digital Amp meter - 96 mm X 96 mm flush secure panel mounting type 0-100 Amps with selector switch with CT - 01 |
| 22 | (d) RYB neon indicating lamp set of three- 01 |
| 23 | Note : (i) Rates are deemed to be inclusive of PCC platform of suitable size and 45cm height and 4 Nos legs of 50mmx50mmx6mm and 60 cm in height for fixing the panel. (iii) Danger notice plate (02 Nos) LT size 20cm x 15cm shall be fixed on the panel. (iv) Contractor will provided powder coated finish paint on panel. |
| 24 | Taking down old unserviceable Old LT panel and Supply, install, testing and commissioning of electric panel board outdoor type suitable for LT 415 volts 3 phase 4 wire system factory made cubical complete materialised dust and vermin proof (protection class IP 54), made out of 3.15 mm thick MS sheet (CRCA) including factory made hinged type double door both side opening with locking arrangement duly painted has bolt type) with two coats of synthetic enamel paint with powder coated finish over a coat of zinc chrome primer including carry out internal connection with suitable copper bus bar and single core copper cable, including cable alley for incoming and outgoing cable complete all as specified and directed by Engineer-In-Charge. The panel board shall be comprising of the following accessories :- |
| 25 | (a) Copper bus bar cap 600 Amp - 04 |
| 26 | (b) MCCB four pole with thermal magnetic release adjustable type with breaking capacity 35 KA, 400 Amp - (incomming) 01 |
| 27 | (c) MCCB four pole with thermal magnetic release adjustable type with breaking capacity 35 KA, 250 Amp - (Outgoing) - 02 |
| 28 | (d) MCCB four pole with thermal magnetic release adjustable type with breaking capacity 35/36 KA,160 Amp (out going)- 01 |
| 29 | (e) Digital Voltmeter-96 x 96 mm flush secure Panel mounting type 0-500V with selector switch - 01 |
| 30 | (f) Digital Amp meter 96 mm X 96 mm flush secure Panel mounting type with selector switch with CT - 01 |
| 31 | (g) RYB neon indicating lamp set of three- 01. |
| 32 | Notes : (i) Rates are deemed to be inclusive of PCC platform of suitable size and 45cm height and 4 Nos legs of 50mmx50mmx6mm and 60 cm in height for fixing the panel (ii) MCCB shall be fixed in suitable sheet metal enclouser (iii) Danger notice plate (02 Nos) LT size 20cm x 15cm shall be fixed on the panel (iv) Contractor will provided powder coated finish paint on panel. |
| 33 | Supply & fixing PVC pipe of dia 20mm with required clamps and nut & bolts any type and any grade to LT pole for proection of street light cable or Complete all as specified and directed by Engr-in-charges. |
| 34 | Supply and fixing SMC junction box including 1 x MCB SP 6 Amp with bus bar suitable for connection (Incoming / outgoing) of three phase & neutral on the LT electric pole of rectangular or circular shape as existing at a height of in between 1-2 mtr with nut, bolt, washer etc complete all as specified and directed by Engr-in-charges. |
| 35 | Supply and laying or fixing or passing through pipe, 1100 volts grade heavy duly cable with PVC insulated aluminium conductor served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall PVC sheathed solid conductor 4 sqmm nominal cross section with 2 core in service connections or Complete all as specified and directed by Engr-in-charges. |
| 36 | Taking out old Unsv MCCB 400 Amps and Supply and Fix MCCB 400 Amps, 415 Volts TPN, 36 KA breaking capacity and thermal magnetic release type Complete all as specified and directed by Engr-in-charges. |
| 37 | Taking out old Unsv MCCB 250 Amps and Supply and Fix MCCB 250 Amps, 415 Volts TPN, 36 KA breaking capacity and thermal magnetic release type Complete all as specified and directed by Engr-in-charges. |
| 38 | Taking out old Unsv MCCB 200 Amps and Supply and Fix MCCB 200 Amps, 415 Volts TPN, 36 KA breaking capacity and thermal magnetic release type Complete all as specified and directed by Engr-in-charges. |
| 39 | Taking out old Unsv MCCB 160 Amps and Supply and Fix MCCB 160 Amps, 415 Volts TPN, 36 KA breaking capacity and thermal magnetic release type Complete all as specified and directed by Engr-in-charges. |
| 40 | Taking out old Unsv MCCB 100 Amps and Supply and Fix MCCB 100 Amps, 415 Volts TPN, 25 KA breaking capacity and thermal magnetic release typeComplete all as specified and directed by Engr-in-charges. |
| 41 | Taking down old unsv & Supply & fixing GI 80mm light grade protection pipe Complete all as specified and directed by Engr-in-charges. |
| 42 | Taking down old unsv & Supply & fixing GI 50mm light grade protection pipe Complete all as specified and directed by Engr-in-charges. |
| 43 | Taking down old unsv & Supply & fixing GI 40mm light grade protection pipe Complete all as specified and directed by Engr-in-charges. |
| 44 | M&L for cold mix emulsion granules road patching material in making good of road 40mm thick complete all as specified and directed by Engr-in-charges. Please Enable Macros to View BoQ information |