| 1 | SITC of Dia Cast aluminium top cover extruded aluminium housing powder coated in graphite/metallic silver anti glare UV Stablized clear opal diffuser acrylic (Triangular shape) having 10Watt LED Bollard light with 85 Lumens/Watt efficacy, IP65, IK07, CCT 3000K, THD<10% with constant current electronic driver complete etc as required.(Note - 5 Years OEM Warranty) |
| 2 | SITC of Dia Cast aluminium top cover extruded die cast aluminium housing with tempered glass for precise light distribution in graphite/metallic silver anti glare UV Stablized clear opal diffuser acrylic having 8Watt LED Spike Garden Light with IP65, IK06, CCT 3000K, THD<10%, CRI≥ 80 & beam angle 36 degree with constant current electronic driver & grouting in suitable CC foundation with complete connection etc as required. |
| 3 | Providing and laying in position 1:2:4 reinforced cement concrete foundation of size 250 mm.(L) X 250 mm. wide and 450 mm. deep i/c excavation of earth, providing cutting, bending and placing in position, reinforcement of cold twisted bars of 08 mm. dia- 1660mm long (approx)- 4 Nos. and reinforcement ring of cold twisted bar of 6mm - 3nos. (with 150mm spacing) as required along with 2/4 Nos. of foundation bolt M-8 x 150mm EN 8 grade having 2 galvanised locking nuts with 2 galvanised plain washer (as per item below) including welding the nuts and providing 38 mm. (O.D) DWC, HDPE Pipe for cable entry & exit as required. (For minimum 1 mtr. height Bollard.) |
| 4 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to 1S 14930, Part Il complete with fitting and cutting, jointing etc. in the existing trench, complete as required. |
| 5 | 38 mm dia (OD-63 mm & ID-51 mm nominal) |
| 6 | Supplying of following size XLPE insulated and PVC sheathed aluminium conductor armoured power cable of 1.1 KV grade in RCC/DWC Pipe/ by excavation of all type of soil having minimum depth 2 feet/Open Channel etc as required. |
| 7 | 3 x 6 Sqmm |
| 8 | 4 X 25 sq. mm |
| 9 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. |
| 10 | Upto 35 sq. mm |
| 11 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. with charcoal/ coke and salt as required. |
| 12 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 13 | Supplying and making outdoor end termination with cast resin compound including aluminium lugs and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 14 | 4 X 25 sq. mm (28mm) |
| 15 | Supplying of Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle 30 deg-120deg as per the application and the project requirement, suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 and <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 16 | 150 Watt |
| 17 | Installation, Testing and Commissioning of following type of LED flood light with suitable connection with the help of tower wagon and other accessories on existing 8m/10m/12m street light poles and 12m/16m/20m/30m high mast poles etc. as required. |
| 18 | 150 Watt Please Enable Macros to View BoQ information |