| 1 | fo|qr uxjh; forj.k [k.M&eksgn~nhiqj] xksj[kiqj ds vUrxZr fctusl Iyku 2026&27 esa Lohd`r ttZj ,0ch0 dscyksa dks cnyus ,oa ,0ch0 dscy ds ek/;e ls vfrfjDr fuekZ.k ds dk;ksZ dks djkus gsrq dk;Z dk fooj.k |
| 2 | Loading, unloading and safe carriage of following materials from Store Centre, Gorakhpur to JE dump Store and JE dump Store to work site with proper stacking :- |
| 3 | LT AB Cable (3X120+1X95+1X16) sq mm |
| 4 | PCC Pole 8.5 Mtr |
| 5 | Earthing complete |
| 6 | Supply of following material/fitting complete in all respect :- |
| 7 | LT Cable 1X35 sq mm |
| 8 | Nuts & bolts of different sizes |
| 9 | LT pole Clamp with nuts & bolts |
| 10 | LT Three Phase Distribution box |
| 11 | Clamp for LT Three Phase DB Box |
| 12 | Suspension Clamp with I hook (Insulated) |
| 13 | Dead end Clamp with I hook (Insulated) |
| 14 | Piercing Connector (Insulated) |
| 15 | The excavation of foundation pit of size 750mmX450mm and having depth of 1/6th of the full length of the pole. Fabrication & erection of PCC Pole with fixing of necessary clamps & accessories as per required. All required materials such as Holding clamp/PCC/LT clamp, Nuts & Bolts off size etc will be provided by the contractor.Grouting of Pole in cc 1:4:8 (Cement, sand & 40 mm brick ballast), Grouting will be done in the block of size 450x450 mm x depth upto ground level and backfilling of pits with mud completely and leveling etc (Material provided by Contractor).All work will be done as per RESSPO norms & relevent IS Specification. |
| 16 | Earthing of PCC Pole by MS earthing Rod & 6 SWG earthing Wire as per RESPO Norms. |
| 17 | Laying & sagging of LT ABC (3X120+1X95+1X16) Sq.mm. Cable of LT Line with fixing of Distribution Box with Clamp, Insulated Dead end clamp with I hook, Suspension clamp with I hook(Insulated), LT insulated Piercing connector, XLPE 1X35 Sq.mm. Al. cable for enerzing DB, XLPE 1X16 Sq.mm. Al. cable for giving connection to Street Light and including disconnection & reconnection of consumer cables, nuts&bolts off size by the contractor. |
| 18 | Dismentling & Carriage of Old Line including Pole |
| 19 | fo|qr uxjh; forj.k [k.M&eksgn~nhiqj xksj[kiqj ds vUrxZr fctusl Iyku 2026&27 esa Lohd`r ttZj ,p0Vh0@,y0Vh0 iksy cnyus ds dk;ksZ dks djkus gsrq dk;Z dk fooj.k |
| 20 | Loading, unloading and safe carriage of following materials from Store Centre, Gorakhpur to JE dump Store and JE dump Store to work site with proper stacking :- |
| 21 | PCC Pole 11 M Long |
| 22 | PCC Pole 8.5 M Long |
| 23 | Earthing Complete |
| 24 | 11 KV Pin insulator with Fitting |
| 25 | 11 KV V cross arm |
| 26 | Extra for stays at angle Location (Stay rod 16x1800mm, Stay wire 5 kg, stay clamp, bolts & nut) |
| 27 | Supply of following material/fitting complete in all respect :- |
| 28 | Danger board Barbed wire including jumper |
| 29 | GI Barbed Wire |
| 30 | F Bracket |
| 31 | Holding Clamp for V Cross Arm |
| 32 | LT pole Clamp with nuts & bolts |
| 33 | LT Shackle insulator |
| 34 | GI Nut & Bolts |
| 35 | The excavation of foundation pit of size 750mmX450mm and having depth of 1/6th of the full length of the pole. Fabrication & erection of PCC Pole with fixing of necessary clamps & accessories as per required. All required materials such as Holding clamp/PCC/LT clamp, F-Bracket, insulators, Nuts & Bolts off size etc will be provided by the contractor.Grouting of Pole in cc 1:4:8 (Cement, sand & 40 mm brick ballast), Grouting will be done in the block of size 450x450 mm x depth upto ground level and backfilling of pits with mud completely and leveling etc (Material provided by Contractor). including resagging of conductor wherever required & disconnection/reconnection of consumer cables (if required)All work will be done as per RESPO norms & relevent IS Specification. |
| 36 | Earthing of PCC Pole by MS earthing Rod & 6 SWG earthing Wire as per RESPO Norms. |
| 37 | Erection of Stay Complete as per RESPO Norms |
| 38 | Erection of Danger Board wire including jumper |
| 39 | Dismentling & Carriage of Old Line including Pole |
| 40 | fo|qr uxjh; forj.k [k.M&eksgn~nhiqj] xksj[kiqj ds vUrxZr fctusl Iyku 2026&27 esa Lohd`r ,p0Vh0 rkj dks cnyus ds dk;ksZ dks djkus gsrq dk;Z dk fooj.k |
| 41 | Loading, unloading and safe carriage of following materials from Store Centre, Gorakhpur to JE dump Store and JE dump Store to work site with proper stacking :- |
| 42 | ACSR Dog Conductor |
| 43 | PCC Pole 11 Mtr |
| 44 | 11 kV V Cross Arm |
| 45 | 11 kV Pin Insulator with pin |
| 46 | 11 kV Disc Insulator with fitting |
| 47 | Earthing complete |
| 48 | Extra for stays at angle Location (Stay rod 16x1800mm, Stay wire 5 kg, stay clamp, bolts & nut) |
| 49 | Supply of following material/fitting complete in all respect :- |
| 50 | Danger baord Barbed wire including jumper |
| 51 | GI Barbed Wire |
| 52 | F Bracket |
| 53 | Holding Clamp for V Cross Arm |
| 54 | LT Clamps |
| 55 | GI Nut & Bolts |
| 56 | The excavation of foundation pit of size 750mmX450mm and having depth of 1/6th of the full length of the pole. Fabrication & erection of PCC Pole with fixing of necessary clamps & accessories as per required. All required materials such as V cross arms, Holding clamp/PCC clamp, F brackets, GI Nuts & Bolts off size etc will be provided by the contractor.Grouting of Pole in cc 1:4:8 (Cement, sand & 40 mm brick ballast), Grouting will be done in the block of size 450x450 mm x depth upto ground level and backfilling of pits with mud completely and leveling etc (Material provided by Contractor).All work will be done as per RESSPO norms & relevent IS Specification. |
| 57 | Earthing of PCC Pole by MS earthing Rod & 6 SWG earthing Wire as per RESPO Norms. |
| 58 | Laying, stringing, sagging, binding and jumpering of ACSR Dog conductor for HT Line with fixing of F brackets, Clamps/other clamps, insulator and nuts&bolts off size as per required. |
| 59 | Erection of Stay complete as per norms |
| 60 | Erection of Danger board with GI Barbed wire |
| 61 | Dismentling & Carriage of Old Line including Pole |
| 62 | fo|qr uxjh; forj.k [k.M&eksgn~nhiqj] xksj[kiqj ds vUrxZr fctusl Iyku 2026&27 esa Lohd`r Hkwfexe Lis;j dscy dks fcNkus ds dk;ksZ dks djkus gsrq dk;Z dk fooj.k |
| 63 | Loading, unloading and safe carriage of following materials from Store Centre, Gorakhpur to JE dump Store and JE dump Store to work site with proper stacking :- |
| 64 | 3x185 mm2 XLPE 11 KV |
| 65 | Supply of following material/fitting complete in all respect :- |
| 66 | Cable jointing kit 11 KV XLPE 3X185 sq mm |
| 67 | Cable Route Marker |
| 68 | G.I Nuts & Bolts off size |
| 69 | G.I Pipe dia |
| 70 | Laying of 11 KV XLPE Cable as per relevant Norms |
| 71 | making loop & hoisting of 11 KV XLPE Cable on double pole/existing single pole |
| 72 | Erection of 11 KV jointing kit |
| 73 | fo|qr uxjh; forj.k [k.M&eksgn~nhiqj] xksj[kiqj ds vUrxZr fctusl Iyku 2026&27 esa Lohd`r iksyksa ij ih0oh0lh0 jSfiax ds dk;ksZ dks djkus gsrq dk;Z dk fooj.k |
| 74 | Providing & fixing PVC wrapping of minimum 4 mm thick (or as per departmental approved specification) on ST Poles complete in all respects |
| 75 | fo|qr uxjh; forj.k [k.M&eksgn~nhiqj xksj[kiqj ds vUrxZr fctusl Iyku 2026&27 esa Lohd`r LVs bUlqysVj yxkus ds dk;ksZ dks djkus gsrq dk;Z dk fooj.k |
| 76 | Supply and erection of Stay Insulator in existing stay sets complete with all necessary fittings, clamps, tightening, adjustment and allied works, complete in all respects as required and as per RESPO norms, relevant IS Specifications and directions of Engineer-in-Charge |
| 77 | fo|qr uxjh; forj.k [k.M&eksgn~nhiqj xksj[kiqj ds vUrxZr fctusl Iyku 2026&27 esa Lohd`r LVs yxkus ds dk;ksZ dks djkus gsrq dk;Z dk fooj.k |
| 78 | Providing, supplying and erection of Stay Set complete in all respects, including stay wire, stay rod, stay insulator, turn buckle, guy clamps, anchor plate, nuts & bolts, excavation, concreting, fixing, tightening and allied works as required, complete in all respects as per RESPO norms, relevant IS Specifications and directions of Engineer-in-Charge |
| 79 | fo|qr uxjh; forj.k [k.M&eksgn~nhiqj] xksj[kiqj ds vUrxZr fctusl Iyku 2026&27 esa Lohd`r cSVªjh ,oa pktZj yxkus ds dk;Z dks djkus gsrq dk;Z dk fooj.k |
| 80 | Supply, installation, testing and commissioning of suitable 24 Volt Battery Charger along with Battery Set comprising 12 Nos. × 2 Volt, 200 Ah batteries, complete with all required accessories, inter-cell connectors, terminals, battery stand/rack, cable connections, earthing, nuts & bolts and allied works, complete in all respects as per approved specifications, RESPO norms, relevant IS Standards and directions of Engineer-in-Charge. Please Enable Macros to View BoQ information |