| 1 | Recessed wiring to light point / first light of group control/ call bell point/ exhaust fan point /wall fan point with 1.5 sq.mm FRLSH PVC insulated single core multistrand copper conductor of ISI marked in 20 mm dia non-metalic PVC conduit with 6 Amp, 250 V clip in type switch ISI marked and ceiling rose ISI marked mounted on G.I modular box with face plate & cover of suitable size , with 1.5 sq.mm FRLSH PVC insulated single core multistrand copper conductor as earth wire including all accesories and connection as per direction of Engineer in Charge. (Make of Wires- Finolex/Anchor/Polycab/HAVELLS/RR KABEL/KEI) or equivalent) (Make of Conduit-AKG/Anchor/Polycab or equivalent reputed make A catagory ISI marked as approved) (Make of switch/socket- Schneider(Zencelo)/Legrand( myrius) /Panasonic (Europa)/Havells(Equivalent model) or equivalent) (Make of accessories- Anchor/Havells) (Make of G.I box, face plate & cover-Schneider(Zencelo)/Legrand( myrius) /Panasonic (Europa) or equivalent reputed make & model A catagory ISI marked as approved) Group C |
| 2 | Recessed wiring to light point / first light of group control/ call bell point/ exhaust fan point /wall fan point with 1.5 sq.mm FRLSH PVC insulated single core multistrand copper conductor of ISI marked in 20 mm dia non-metalic PVC conduit with 6 Amp, 250 V clip in type switch ISI marked and ceiling rose ISI marked mounted on G.I modular box with face plate & cover of suitable size , with 1.5 sq.mm FRLSH PVC insulated single core multistrand copper conductor as earth wire including all accesories and connection as per direction of Engineer in Charge. (Make of Wires- Finolex/Anchor/Polycab/HAVELLS/RR KABEL/KEI) or equivalent) (Make of Conduit-AKG/Anchor/Polycab or equivalent reputed make A catagory ISI marked as approved) (Make of switch/socket- Schneider(Zencelo)/Legrand( myrius) /Panasonic (Europa)/Havells(Equivalent model) or equivalent) (Make of accessories- Anchor/Havells) (Make of G.I box, face plate & cover-Schneider(Zencelo)/Legrand( myrius) /Panasonic (Europa) or equivalent reputed make & model A catagory ISI marked as approved) Group B |
| 3 | Recessed wiring to light point / first light of group control/ call bell point/ exhaust fan point /wall fan point with 1.5 sq.mm FRLSH PVC insulated single core multistrand copper conductor of ISI marked in 20 mm dia non-metalic PVC conduit with 6 Amp, 250 V clip in type switch ISI marked and ceiling rose ISI marked mounted on G.I modular box with face plate & cover of suitable size , with 1.5 sq.mm FRLSH PVC insulated single core multistrand copper conductor as earth wire including all accesories and connection as per direction of Engineer in Charge. (Make of Wires- Finolex/Anchor/Polycab/HAVELLS/RR KABEL/KEI) or equivalent) (Make of Conduit-AKG/Anchor/Polycab or equivalent reputed make A catagory ISI marked as approved) (Make of switch/socket- Schneider(Zencelo)/Legrand( myrius) /Panasonic (Europa)/Havells(Equivalent model) or equivalent) (Make of accessories- Anchor/Havells) (Make of G.I box, face plate & cover-Schneider(Zencelo)/Legrand( myrius) /Panasonic (Europa) or equivalent reputed make & model A catagory ISI marked as approved) Group A |
| 4 | Recessed wiring for 5 / 6 amp socket outlet with 6Amp, 250 V clip in type modular switch ISI marked mounted on G.I moular box with face plate & cover of suitable size including all accesories and connection on same switch board as per direction of Engineer in Charge. (Make of switch/socket- Schneider(Zencelo)/Legrand( myrius) /Panasonic (Europa)/Havells(Equivalent model) or equivalent){GROUP SWITCH BOARD}. |
| 5 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess,including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 a modular switch,connections etc.as required. |
| 6 | Supply & Fixing of 1400mm ceiling fan with hook made of 10mm round still bar, Modular Reguletor.(Make-Legrand (myrius), Usha,Crompton /Havells (Equivalent model) or equivalent) |
| 7 | Supply & Fixing of 380mm Heavy duty Exhaust Fan .(Make- Usha,Crompton /Havells (Equivalent model) or equivalent) |
| 8 | Supply & Fixing of suitable size modular blank plate,connections etc. as required.( IN EXISTING SWITCH BOARD EXCLUDING COST OF SWITCH BOARD & PLATE) .(Make- Legrand (myrius), L&T Hager (Equivalent model) or equivalent) |
| 9 | Providing and fixing extra conduit down rod of 20 mm dia, 2X10 cm length wirng with 2X1.5 sq . Mm FR PVC insulated single core multistrand copper conductor including painting etc. as erequired.( Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored) |
| 10 | Recessed wiring to submain in 2 x 1.5 sq.mm FR PVC insulated single core multistrand copper conductor of ISI marked confirming to IS-694/1990 in 20 mm dia non-metalic heavy duty PVC conduit 1.6 mm thick along with 1 x 1.5 sq.mm FR PVC insulated single core multistrand copper conductor as earth wire as required. (Make of wire- Finolex/ Anchor/ Polycab/ HAVELLS/RR KABEL or equivalent) (Make of conduit-AKG/Anchor/Kinjal or equievalant) |
| 11 | Recessed wiring to submain in 2 x 2.5 sq.mm FR PVC insulated single core multistrand copper conductor of ISI marked confirming to IS-694/1990 in 20 mm dia non-metalic heavy duty PVC conduit 1.6 mm thick along with 1 x 1.5 sq.mm FR PVC insulated single core multistrand copper conductor as earth wire as required. (Make of wire- Finolex/ Anchor/ Polycab/ HAVELLS/RR KABEL or equivalent) (Make of conduit-AKG/Anchor/Kinjal or equievalant) |
| 12 | Recessed wiring to submain in 2 x 4 sq.mm FR PVC insulated single core multistrand copper conductor of ISI marked confirming to IS-694/1990 in 20 mm dia non-metalic heavy duty PVC conduit 1.6 mm thick along with 1 x 1.5 sq.mm FR PVC insulated single core multistrand copper conductor as earth wire as required. (Make of wire- Finolex/ Anchor/ Polycab/ HAVELLS/RR KABEL or equivalent) (Make of conduit-AKG/Anchor/Kinjal or equievalant) |
| 13 | Recessed wiring to submain in 4 x 2.5 sq.mm FR PVC insulated single core multistrand copper conductor of ISI marked confirming to IS-694/1990 in 25 mm dia non-metalic heavy duty PVC conduit 1.6 mm thick along with 2 x 2.5 sq.mm FR PVC insulated single core multistrand copper conductor as earth wire as required. (Make of wire-Finolex/ Anchor/ Polycab/ HAVELLS/RR KABEL or equivalent) (Make of conduit-AKG/Anchor/Kinjal or equievalant) |
| 14 | Supplying and fixing following way,single pole and neutral,sheet steel,MCB distribution board,240 V,on surface/recess,complete with tinned copper bus bar,neutral bus bar,earth bar,din bar,interconnections,powder painted including earthing etc. as required.(But without MCB/RCCB/Isolator)12 way Double ddor |
| 15 | Supplying and fixing following way,single pole and neutral,sheet steel,MCB distribution board,240 V,on surface/recess,complete with tinned copper bus bar,neutral bus bar,earth bar,din bar,interconnections,powder painted including earthing etc. as required.(But without MCB/RCCB/Isolator)4 way(4+12) Double door |
| 16 | Supplying and fixing single pole blanking plate in the existing MCB DB complet etc.as required. |
| 17 | Supply and fixing of following rating 240 V Minature Circuit Breaker (MCB) having a breaking capacity up to 10kA in the existing MCB DB ISI marked complete with connection testing and commissioning etc as required. |
| 18 | 6A To 32A SP MCB |
| 19 | 6A To 32A DP MCB |
| 20 | 6A To 32A TPN MCB |
| 21 | Supply and fixing of following rating 240 V Residual Current Breaker with Overcurrent protection (RCBO) having a sensitivity current up to 100mA in the existing MCB DB ISI marked complete with connection testing and commissioning etc as required. |
| 22 | 6A to 40A DP RCBO |
| 23 | 6A to 40A TPN RCBO |
| 24 | Supply, installation,testing & commissioning of floor mounting front operated front access extensible type cubicle panel totally enclosed, dust and vermin proof with IP-42 /55 protection with hinged and lockabale doors.CRCA sheets including Busbars, interconnections,tinned copper crimping lugs, bonding to earth and painting suitable for use at 415 V, 3phase 4 wire 50 Hz system, and to withstand a fault level of 35KA symmetrical for 1 sec at 415 V complete as per specifications, as required and as below : All switchboards shall have provision for entry of cables from the bottom as required. All live accessible parts shall be shrouded and all equipment shall be finger touch proof. The bus bars shall be insulated with heat shrinkable sleeves.SMC/DMC shrouds and busbar supports shall be used.(Make of switchgear - LEGRAND-Ekinox3 DB/ Siemens-Betaguard/ Schneider- Acti 9/L&T/ABB or Equivalant ISI marked). |
| 25 | OUT-DOOR TYPE PDB PANEL |
| 26 | 100A CAPACITY PDB PANEL(FOR COMMON LOAD) |
| 27 | PDB PANEL(FOR LIFT) |
| 28 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. |
| 29 | 3.5 C x 240 sq.mm Al (Above 185 sq. mm & upto 400 sq.mm) |
| 30 | 4 X C 25sq. mm (upto 35 sq. mm) |
| 31 | Laying and fixing of one number of PVC insulated and PVC seathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. |
| 32 | Supplying and making end termination with brass compression gland and aluminum lugs for following size of PVC insulated and PVC sheathed / XLPE aluminum conductor cable of 1.1 KV grade as required. |
| 33 | 3.5 C x 240 sq.mm Al |
| 34 | 3.5 C x 25 sq.mm Al |
| 35 | 4 C x 10 sq.mm Al |
| 36 | Supplying & installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. |
| 37 | 100 mm width X 50 mm depth X 1.6 mm thickness |
| 38 | 150 mm width X 50 mm depth X 1.6 mm thickness |
| 39 | 200 mm width X 50 mm depth X 1.6 mm thickness |
| 40 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 41 | Supply of one number of PVC insulated and PVC seathed / Armour /XLPE power cable of 1.1 KV grade of following sizes of cable as required. (Make- POLYCAB / FINOLEX / HAVELLS) or equievalant reputed ISI MARKED MAKE |
| 42 | 3.5 C x 240 sq.mm Al |
| 43 | 3.5 C x 25 sq.mm Al |
| 44 | 4 C x 10 sq.mm Al |
| 45 | 2 C x 6 sq.mm Al |
| 46 | Supply, installation and testing of Maintenance free safe Earthing Electrodes with ISI G.I pipe dia 75mm as Secondary electrode with wall thickness of 2.6 mm and the Primary Earthing Electrode will be 50mm X 6mm X 1no M.S hot dipped galavanized strip filled with a highly conductive & non-corrosive compound in between the Primary Earthing and the secondary Earthing, the surface Area in will be 7,06,500sqmm for 3mtrs length and cross sectional primary conducting area is 300 sq.mm An Solid G.I Base plat seals the unit at the bottom and providing of masonry enclosure with cover plate.as per direction of Engg.-in-charg (MES- GFC ground Filling compound will be provided in 25 kgs Bags.) (MES-GFC ground Filling compound will be provided in 25 kgs Bags.) (2 bags required for each earthing electrode.) 2nos earthing connection all motors and 2nos earthing connect in all panel. |
| 47 | Supplying and laying 25 mm x 6 mm G.I earth strip ISI marked at 0.5 meter below grond level as strip earth electrode including soldering etc. as required |
| 48 | Supply, delivery, installation and testing of ESE Air Terminal ESE-60 comprised of separate electrically isolated dual copper panels surrounding an Earthed central finial should be coated with chrome for environmental protection which will be install on the concrete base frame of size 900mm x 900 mm x 900 mm on the top of the roof of the building. The upper section of the central finial shall be rated to withstand 100KA impulse current and it should be made up of solid brass rod and its length should be more than 85mm above the surrounding panels. The insulation material used to electrically isolate the panel shall be comprised of base polymer which provides high UV resistance with die electric strength of 24-38KV/MM ESE terminal must withstand a minimum switching impulse voltage of 500KV. Its adapter should be made up of non conductive material DELRIN, which should provide good abrasion resistance, good mechanical strength, pretty good heat resistance, good electric & dielectric properties & Low water absorption. Terminal performance should be tested as per NFC 17-102:2011 standard .Terminal should be tested for impulse current withstand test in CPRI for 40 KA. Terminal shall carry 05 yrs warranty by manufacturer. MAKE:INDELEC PREVECTRON-S6.6/SATELITE-3/PP STROMKING/ ESRICO DYNASPHERE 3000/PARATONEX |
| 49 | Supply of Lightning strike counter with eectro mechanical display and nonresettable,tested for 100ka 10/350 micro sec. as per NFC 17102(2011),en 50164-6,TS EN 62561-1, 6 DIGIT IN IP 67(IEC 529) protection.MAKE:INDELEC PREVECTRON-S6.6/SATELITE-3/PP STROMKING/ ESRICO DYNASPHERE 3000/PARATONEX |
| 50 | Supply delivery installation and testing of 07.62 mtr long of 50 mm dia Class “B’ S.S Pipe with base plate, guying kit and mounting accessories etc. Of lightning mast pole to be installs’ at the top of the roof which shall be non corrosive and PVC insulated metallic wire rope as guy wire. The down conductor shall pass through the centre of the pole for the entire length of the pole and it will be out at bottom of the pole complete as per the site requirements |
| 51 | Supply of one number of PVC insulated 70MM² single core/Multistand copper cable of 1.1 KV grade of following sizes of cable as required. (Make- POLYCAB / FINOLEX / HAVELLS) or equievalant reputed ISI MARKED MAKE (70MM² single core/Multistand/1.1 KV gradecopper cable.) |
| 52 | Laying and fixing of one number PVC insulated and PVC sheathed/ XLPE power cable of 1.1 KV grade of following size on cable tray as required.(Above 35MM² and upto 185MM² (Clamped with 25x3 mm MS flat clamp)) |
| 53 | Supply, Installation, Testing and Commissioning of pre-wired fluorescent fiiting / compact fluorescent fitting /LED fitting of all sizes complete with all accessories and lamp etc. directly on ceiling /wall or recessed in false ceiling , including connection with 1.5 sq.mm FR PVC insulated single core multistrand copper conductor and earthing as required. |
| 54 | Supply, Installation, Testing and Commissioning of surface mounted indoor type 20W/6500K SINGLE LED TUBE pride plusinverter LED batten.Similar to HAVELLS Cat No. LHEXAZP7PN1W020 / Wipro / Philips / Halonix / Panasonic or equivalent. |
| 55 | Supply, Installation, Testing and Commissioning of surface mounted indoor type 20W/6500K ROUND LED Luminaire with LED ceiling cutout ( Similar to HAVELLS Cat No. LHEABIP7IL1W020 / Wipro / Philips / Halonix / Panasonic or equivalent. |
| 56 | Supply, Installation, Testing and Commissioning of surface mounted indoor type 10W/3000K MIRROR LED Luminaire with LED Lamp (Similar to HAVELLS Cat No. LHEXACP5IN1W010 / Wipro / Philips / Halonix / Panasonic or equivalent. |
| 57 | Supply, Installation, Testing and Commissioning of outdoor type IP65 with surge protection 100W Flood LIGHT with LED Lamp Similar to HAVELLS Cat No. LHEECNP7PB7J100 or equivalent. |
| 58 | Supply and installation of Rubber Mats 12mm thick of size 2000mm x 1000mm x 12 mm thick Electrical tested with test certificate. |
| 59 | Supply and fixing of Co2 fire extinguisher with mounting clamps with pressure test certificate . |
| 60 | Supply and fixing of shock treatement charts duly laminated along with separate colour single line diagram laminated, to be fixed in Electrical control panel room. |
| 61 | Supply and fixing of first aid box with medicines complete with medicine with three years expiry date to be fixed in Electrical control panel room. |
| 62 | Danger Board.(200MM X 1500MM) Please Enable Macros to View BoQ information |