| 1 | A . (i)Shifting and Installation of 1 MVA Power Transformer with control Panels bus bar and renovation of distrubution transformer bus bar and secondary control panel. |
| 2 | Earth work in excavation by mechanical means (Hydraulic excavator) /manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, for all lift, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.All kinds of soil.For Trench 1 Mtr X 1 Mtr X 60 Mir 60 CUMFor Transformer 3 Mtr X3 Mir X 1 Mir X 2018 CUMFor Switch 2 Mtr X3 Mtr X1 Mr X3-18 CUMFor GOAB/SupportLA 075 Mtr X0.75 Mtr X 0.75 Mir X 11 Nos-4.64 CUM |
| 3 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in:Cement mortar 1:6(1 cement:6 coarse sand) For Trench Repairing 1 Mtr X 0.12 Mtr X 60 Mtr X 2 side =14.40 CUM Transformer 3 Mtr X 1.50 Mir X 0.24Mtr X 4 Wall-4.32 CUM2.76 Mtr X 1.50 Mir X 0.24 Mir X 4 Wall-3.97 CUMSwitch 3 Mr X 1.50 Mtr XO 24 Mtr X 6 Wall-6.48 CUM 1.76 Mtr X 1.50 Mtr X 0.24 Mtr X6 Wall-3.80 CUMFor Trench 1 Mtr X 0.12 Mtr X 60 Mtr X-7.20 CUM |
| 4 | Cement plaster skirting up to 30 cm height, with cement mortar 1:3 (1cement: 3 coarse sand), finished with a floating coat of neat cement. 18 mm thick |
| 5 | Providing and laying in position cement concrete of specified grade excludingthe cost of centering and shuttering - All work up to plinth level 11:4:8 (1 Cement: 4 coarse sand: 8 graded stone aggregate 20 mm nominal size)For GOAB 1 Mtr X 0.75 Mir X 0.75 Mtr X 5 Nos X 2 Side 5.62 CUMfor Bus support/LA 0.75 Mtr X.0.75 Mtr X 0.75 Mtr X 2 Side X 6 Nos=5.06 CUMFor Transformer 3 Mtr X 3 Mir X 0.24 Mtr X 2 Nos 4.32 CUMFor Switch 3 Mtr X2 Mtr X 0.24 Mtr X 3 Nos-4.32 CUMFor Trench 0.75 Mtr X 0.12 Mtr X 60 Mtr X = 5.40 CUM |
| 6 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level: 1:1.5:3(1 cement: 1.5 coarse sand (zone-III) derived from natural sources: 3 graded stone aggregate 20 mm nominal size derived from naturalsources) size) 1 MtrX 0.12 Mtr X 60 Mtr=7.20 CUM |
| 7 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level-Thermo-Mechanically Treated bars of grade Fe-500D or more |
| 8 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.300 mm width X 62.5 mm depth X 2.0 mm thickness |
| 9 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays bends with perforation not more than 17.5%, joined with connectors, suspended from the celling with M.S. suspenders Including bolts & nuts, painting suspenders etc as required.300 mm width X 62.5 mm depth X 2.0 mm thickness |
| 10 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays Tee with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required 300 mm width X 62.5 mm depth X 2.0 mm thickness. |
| 11 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays Cross Member with perforation not more than 17.5%, joined with connectors, suspended from the celling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.300 mm width X 62.5 mm depth X 2.0 mm thickness |
| 12 | Supplying and filling in plinth with sand under floors, including watering. ramming, consolidating and dressing complete. For Transformer 3 Mtr X2.76 Mer X 1.25 Mtr X2-20.70 CUM For Switch 2.76 Mr X 1.25 Mb X 1.76 Mtr X3 Nos 18.21 CUM For Yard 25 Mtr X 25 Mr X 0.15 Mir-93.75 CUM |
| 13 | Collection and spreading of metal 40mm graded hard metal in sub-station yard or as required as mentioned below - Metal 40 mm 25 Mtr X 25 Mtr X 0.15 Mtr-93.75 CUM |
| 14 | Shifting, erection, & commissioning of Transformer 2 Nos, VCB 2 Nos & LT Switch 1 Nos |
| 15 | Steel work welded in built up sections/framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer usingstructural steel etc. as required. In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works |
| 16 | Laying of one number PVC insulated and PVC sheathed/XLPE power cable of 11 KV grade of following size in the existing structure as required. Upto 120 sq. mm |
| 17 | Supply & Fixing of Support Connector, aluminium alloy material, 48.60 mm size |
| 18 | Supply & Fixing of Post Insulator, 10KA, 11KV rated, standard size. |
| 19 | Supply & Fixing of T Connector, aluminium alloy material, 48.60 mm size. |
| 20 | Supply & Fixing of Nut & Bolts of diiferent size as required |
| 21 | Supply & Fixing of Enamel Paint |
| 22 | Supply & Fixing of Red Oxide Paint |
| 23 | Supply & Fixing of Bi-Metalic connector, aluminium alloy material/brass, 48.60 mm X 12 mm size. |
| 24 | Supply & Fixing of Pad / Palm Connector, aluminium alloy material, 48.60 mm X 12 mm size. |
| 25 | Supply & Fixing of Lighting Arrestor line type/ Station Type 9 KV, 12 KA |
| 26 | Supply & Fixing of Lightning Arrestor Station Type 3.3 KV |
| 27 | Supply & Fixing of Support Insulator 90mm X 30mm 11KV/3.3KV grade |
| 28 | Supply & Fixing of Pipe to Pipe Connector, aluminium alloy material, 48.60 mm X 48.60 mm size |
| 29 | Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required:70 sq. mm |
| 30 | Supply & Fixing of Alloy aluminum pipe 48.3 mm dia inner dia 40.8mm wall thk 3.6mm |
| 31 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 32 | Supply & Fixing of Alurninium Unarmoured cable single core1100 voltage grade 35 sq mm 48 |
| 33 | Supply & Fixing of Aluminium tub terminal 35 sq mm |
| 34 | Supply & Fixing of 11 KV grade Air Break Switch 630Amp horizental type |
| 35 | Supply & Fixing of 11 KV/3.3KV grade Drop Out Fuse 400Amp |
| 36 | Supply & Fixing of Limit Switch, 800mA, 250VV, 10A |
| 37 | Supply & Fixing of Cable 2.5sq mm x 2 core copper |
| 38 | Supply & Fixing of Auxilary Contractor 4 pole, 4NO+4NC |
| 39 | A(ii)Shade Work |
| 40 | Providing ridges or hips of width 60 cm overall width plain G.S. sheet fixed with polymer coated J. or L hooks, bolts and nuts 8 mm dia G.I. limpet and bitumen washers complete. 0.63 mm thick with zinc coating not less than 275 gm/m² |
| 41 | Providing corrugated G.S. sheet roofing including vertical / curved surfacefixed with polymer coated J or L hooks, bolts and nuts 8 mm diameterwith bitumen and G.I. limpet washers or with G.I. limpet washers filledwith white lead, including a coat of approved steel primer and two coatsof approved paint on overlapping of sheets complete (up to any pitch inhorizontal/ vertical or curved surfaces), excluding the cost of purlins, raftersand trusses and including cutting to size and shape wherever required.0.63 mm thick with zinc coating not less than 275 gm/m² |
| 42 | Earth work in excavation by mechanical means (Hydraulic excavator) /manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, for all lift, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.All kinds of soil. 0.75 Mtr X0.75 Mtr X 0.75 Mtr X 4 Nos=4.64 CUM |
| 43 | Providing and laying in position cement concrete of specified grade excludingthe cost of centering and shuttering - All work up to plirith level :1:4:8 (1 Cement: 4 coarse sand: 8 graded stone aggregate 20 mm nominal size)0.75 Mtr X0.75 Mtr X 0.75 Mtr X 4 Nos-4.64 CUM |
| 44 | Steel work welded in built up sections/framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer usingstructural steel etc. as required. In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works |
| 45 | B.Extension of 11KV OH line for installation of 250KVA Transformer with control pannel,foundation shade fencing and energy meter with erection of 440OH line feeding power to outstanding camp and lighting purpose at karma project under kuju Area. |
| 46 | B. (i) Extension of 11KV OH Line. |
| 47 | Erection of pole of following length in cement concrete 1:3:6 (1 cement:3 coarse sand: 6 graded stone aggregate 40mm nominal size) foundation including excavation and refilling etc. as required. Above 10.00 metre and upto 12.00 metre |
| 48 | Erection of ACSR conductor of 7/3.35 mm to 7/4.00 diameter andabove including binding etc. as required. (02 spans 40m*3 wires)=240m @342.51 |
| 49 | Supplying and erection of 11 KV pin insulator complete with largesteel head G.I. pin, nuts, washers etc. as required |
| 50 | Supplying and erection of 11 KV disc insulator for 11 KV overhead lines with galvanised insulator fittings, ball and socket typeand complete with galvanised strain clamps, bolts, nuts, washers etc. as required |
| 51 | Supplying of channel iron 75 mm X 40 mm X 6 mm (7.14 kg permetre) pole top bracket/ cross arm for single 11 KV over head line conductor complete with 50 mm X 6mm flat iron clamp, bolts, nuts and washers including drilling holes for insulator pins, bolts and nuts etc and painting with primer and finish paint as required |
| 52 | Supplying of channel iron 75 mm X 40 mm X 6 mm (7.14 kg permetre) cross arm for 4 wire over head line complete with clamps, bolts, nuts and washer etc including drilling of holes for insulatorpins etc (as per drawing) and painting with primer and finishedpaint as required |
| 53 | Supplying of channel iron 75 mm X 40 mm X 6 mm (7.14 kg permetre) cross arm for two 11 KV over head line conductorscomplete with 50 mm X 50 mm X 6 mm (angle iron bracket welded to the channel iron and complete with 50 mm X 6mm M.S. flatiron clamps, bolts and nuts including drilling holes for insulatorpins, bolts, nuts and washers etc (as per drawing) and painting with primer and finish paint as required |
| 54 | Supplying and erection of bow stay set complete (galvanised)with 19/20 mm dia X 1.8 metres long stay rod, anchor plate ofsize 45 cm X 45 cm X 7.5 mm, thimble, stay clamps, turn buckle(20 mm X 60 cm), 7/4.00 mm dia G.I. stay wire and strain insulator etc in cement concrete 1:3:6 (1 cement: 3 coarse sand: 6 graded stone aggregate 40 mm nominal size) foundationincluding excavation and refilling and also with 0.6 m long braceof size 50 mm X 50 mm X 6 mm angle iron with 50 mm dia pulleyfixed at one end of the brace as required. |
| 55 | Supplying of two lengths of channel iron 75 mm X 40 mm X 6 mm(7.14 kg per metre) double pole cross arm for three wire 11KVover head line conductors complete with through bolts and nuts for clamping to the poles, 50 mm X 6 mm M.S. flats welded onone side to the channel iron and with bolts and nuts on the otherside for tying the cross arms together, including drilling holes forinsulator pins/fittings, bolts, nuts and washers etc (as per drawing) and painting with primer and finish paint as required |
| 56 | Supply & Fixing of Lighting Arrestor Station Type 11 KV |
| 57 | Support Insulator 90mm X 30mm 11KV/3.3KV grade |
| 58 | Supply & Fixing of 11 KV grade Air Break Switch 630Amp horizental type |
| 59 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required |
| 60 | Supply & Fixing of Aluminium Unarmoured cable single core1100 voltage grade 35 sq mm |
| 61 | Supply & Fixing of Aluminium tub terminal 35 sq mm |
| 62 | Supply & Fixing of 11 KV/3.3KV grade Drop Out Fuse 400Amp |
| 63 | Supplying and erection of a set of cross bracing FRLSame workfor 11 KV over head line double pole structure having four membersfabricated of 50 mm X 50 mm X 6 mm angle iron to form a rectangle of minimum size 1400 mm width X 2500 mm height, complete with 50 mm X 6mm M.S. flat iron clamps, bolts andnuts including drilling holes for insulator pins, bolts and nuts etc(as per drawing) and painting with primer and finish paint as required |
| 64 | Erection, & commissioning of Transformer 1 No & VCB 1 No |
| 65 | Supply & Fixing of Pad / Palm Connector, aluminium alloy material, 48.60 mm X 12 mm size. |
| 66 | Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required:70 sq. mm |
| 67 | B(ii) Making of foundation for Transformer & VCB Installation |
| 68 | Earth work in excavation by mechanical means (Hydraulic excavator) /manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, for all lift, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.All kinds of soil. 3 Mtr X 3 Mtr X 1X2nos. 18 CUM (For foundation of Transformer and VCB) 0.75Mtr X 0.75 Mtr X 1MtrX10nos. =5.625 CUM 25 Mtr X 15 Mtr X 0.25 Mtr=93.75 CUM (For filing and dressing of site) |
| 69 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: Cement mortar 1:6(1 cement:6 coarse sand) 2.76 Mtr X 1.5 Mtr X 0.24 Mtr X 8 Wall=3.97 CUM (For foundation of Transformer and VCB) |
| 70 | Cement plaster skirting up to 30 cm height, with cement mortar 1:3 (1cement: 3 coarse sand), finished with a floating coat of neat cement. 18 mm thick (2.76m*1m*8nos.+2.76m*2.76m*2nos.) |
| 71 | Providing and laying in position cement concrete of specified grade excludingthe cost of centering and shuttering - All work up to plinth level 1:4:8 (1 Cement: 4 coarse sand: 8 graded stone aggregate 20 mm nominal size) 2.76 Mtr X2.76 Mtr X 0.24 Mtr X 2-3.66 CUM (For foundation top) X 0.6 Mtr X 0.8 Mtr X 10nos. 2.88 CUM (For foundation of steel frame for Shed) 0.6 Mtr |
| 72 | Supplying and filling in plinth with sand under floors, including watering, ramming, consolidating and dressing complete. 2.76 Mu X 2.76 Mr X 0.75 Mtr X 2 nos.=11.43CUM |
| 73 | B(iii)Shed & chain link mesh works |
| 74 | Providing ridges or hips of width 60 cm overall width plain G.S. sheet fixed with polymer coated J. or L hooks, bolts and nuts 8 mm dia G.I. limpet and bitumen washers complete. 0.63 mm thick with zinc coating not less than 275 gm/m² |
| 75 | Providing corrugated G.S. sheet roofing including vertical / curved surfacefixed with polymer coated J or L hooks, bolts and nuts 8 mm diameterwith bitumen and G.I. limpet washers or with G.I. limpet washers filledwith white lead, including a coat of approved steel primer and two coatsof approved paint on overlapping of sheets complete (up to any pitch inhorizontal/ vertical or curved surfaces), excluding the cost of purlins, raftersand trusses and including cutting to size and shape wherever required.0.63 mm thick with zinc coating not less than 275 gm/m² (6mX8M roof+4mX6m side+4mX8MX2 side) |
| 76 | Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer usingstructural steel etc. as required. In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works (Frame for Shed) |
| 77 | Supply & fixing fencing of chain link mesh 100 x 100 mm, 12 SWG GI wire for for D.P. structure electric substation switch yard including single post of angle iron size 50x50x5mm, 2.5 ml long should be provided upto 2.00 mt. apart or as required. The panel frame with required angle iron/ flat iron members/cross members including mesh welded in frame panel shall be erected between the posts. The angle iron post shall be erected in cement concrete M-15 (1:2:4) (20 mm graded metal) foundation, including excavation of pit and refilling the same. The fencing shall be provided with one entrance gate including locking arrangement as required as per specification. The height of fencing shall be 2 mt. above groun level. Fencing shall be painted with required shade (25+15)*2m*2m=160 |
| 78 | B(iv) Extention of 440Volt OH line |
| 79 | Supply & Fixing of 4 pole MCCB DN4-1250N (Release Range 320-800) with earth leakage relay protection |
| 80 | Erection of pole of following length in cement concrete 1:3:6 (1 cement: 3 coarse sand: 6 graded stone aggregate 40mm nominal size) foundation including excavation and refilling etc. as required. Above 10.00 metre and upto 12.00 metre |
| 81 | Supplying of two lengths of channel iron 75 mm X 40 mm X 6 mm(7.14 kg per metre) double pole cross arm for three wire 11KVover head line conductors complete with through bolts and nuts for clamping to the poles, 50 mm X 6 mm M.S. flats welded onone side to the channel iron and with bolts and nuts on the otherside for tying the cross arms together, including drilling holes forinsulator pins/ fittings, bolts, nuts and washers etc (as per drawing)and painting with primer and finish paint as required. |
| 82 | Supplying and erection of bow stay set complete (galvanised) with 19/20 mm dia X 1.8 metres long stay rod, anchor plate ofsize 45 cm X 45 cm X 7.5 mm, thimble, stay clamps, turn buckle(20 mm X 60 cm), 7/4.00 mm dia G.I. stay wire and strain insulator etc in cement concrete 1:3:6 (1 cement: 3 coarse sand: 6 graded stone aggregate 40 mm nominal size) foundationincluding excavation and refilling and also with 0.6 m long braceof size 50 mm X 50 mm X 6 mm angle iron with 50 mm dia pulleyfixed at one end of the brace as required. |
| 83 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/coke and salt as required |
| 84 | Supply & Fixing of Aluminium Unarmoured cable single core 1100 voltage grade 35 sq mm |
| 85 | Supply & Fixing of Aluminium Tubular Lug 35 sq mm |
| 86 | Supplying and erection of a set of cross bracing FRLSame workfor 11 KV over head line double pole structure having four membersfabricated out of 50 mm X 50 mm X 6 mm angle iron to form a rectangle of minimum size 1400 mm width X 2500 mm height, complete with 50 mm X 6mm M.S. flat iron clamps, bolts andnuts including drilling holes for Insulator pins, bolts and nuts etc(as per drawing) and painting with primer and finish paint as required. |
| 87 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/recessed steel/ PVC conduit as required 2 x 2.5 sq. mm |
| 88 | Providing and fixing 50 mm dia X 3.2 metres G.I. pipe (including accessories) complete with 50 mm X 50 mm X 6 mm angle iron bracket on wall and 75 mm X 90 mm shackle insulator with straps for house service connection including painting the angle and flat iron with primer and finish paint etc. as required |
| 89 | Supplying & drawing/laying of PVC insulated XLPE aerial bunch power cable conductor H2/H4 grade aluminium solid/stranded conforming to IS-14255-1995, alu, alloy insulated messenger 1100 volts grade cable of approved make in air with necessary material as per specification of required size as mentioned below-3x70 sq.mm, 1x16(st. light), 1x35 (insulated neutral messenger) (7spans*35m) |
| 90 | Supplying & fixing of aerial bunch cable accessories suspension clamp i/c required attachment for single core cable of approved make on pole with clamp, necessary material as per specification for required size |
| 91 | Supplying &fixing of aerial bunch cable accessories tension clamp (dead end) i/c required attachment for single core cable of approved make in air with clamp, necessary material as per specification for required size |
| 92 | Supplying & fixing of waterproof insulation piercing connector for aerial bunch cable i/c required attachment for single core cable of approved make in air with necessary material as per specification of required size as mentioned below-Main:50-150sq.mm |
| 93 | Supply & Fixing of Smc A B Cable Distribution Box Size |
| 94 | B(v) Installation of Energy Meter |
| 95 | Supply & Fixing of 11kv Ht Bi-directional Net Class-0.2s 3-phase Energy Meter |
| 96 | Supply & Fixing of CT ring type 400 S1 |
| 97 | Wiring with ferruls & Lugs |
| 98 | Total impact of GST for the purpose of CTC Please Enable Macros to View BoQ information |